EW0826D1_en 

 rev. A 

CO

2

 gas detectors 

 URD20SE 

05/10/2020 

Gas detection systems for industrial environments 

1/8

 

 

 

 

 

 

Sensigas

®

 

Gas detectors 
Carbon dioxide  (CO

2

ATEX II 2G Ex d IIC T6 Gb certified 

 

URD20SE 

 
 
 
 
 

 

Sssssss 

 

 

 
11…28Vdc power supply. 
Nondispersive infrared (NDIR) sensor designed for the detection of carbon dioxide 
(CO

2

). 

Up to three alarm thresholds plus sensing element fail. 

LED on sensing element body to indicate operating status. 

Automatic countdown of sensor life. 

Use 

The URD20SE detectors are used to detect the presence of carbon dioxide (CO

2

), in 

areas classified as Zone 1. 

It detects carbon dioxide leaks or emissions in industrial environments, hospitals, 
fermentation plants, greenhouses, stables and, more in general, where carbon dioxide 
is stored, generated or produced. 

URD20SE sensors can be used in stand-

alone mode with 4…20mA output or with an 

optional voltage-free contact relay card having the following four digital outputs: 

Pre-alarm, 1

st

 alarm threshold, 2

nd

 alarm threshold, Sensor fail. 

Operation 

If there is a gas leakage, the detector compares the measured concentration value 
with the threshold limit setpoints and energises the associated relays. Information on 
the measured concentration value is always at the 4…20mA output. 

Ordering 

To order, simply state the part number: 

URD20SE

For special versions, on request, please contact Customer Service. 

 

Summary of Contents for Sensigas URD20SE

Page 1: ...carbon dioxide leaks or emissions in industrial environments hospitals fermentation plants greenhouses stables and more in general where carbon dioxide is stored generated or produced URD20SE sensors...

Page 2: ...table polarity 4 20mA output load resistor up to 200 at 12Vdc power supply 200 700 at 24Vdc power supply Operating Temperature Storage Temperature 20 50 C 20 70 C Relative Humidity without condensing...

Page 3: ...uctions for location of the detectors The detectors must be installed 1 where accidental gas leakages are possible 2 at least 1 5m away from heat sources or from vent holes 3 not in spaces where venti...

Page 4: ...up again in particular The default setting for the 4 20mA signal is the negative power signal Output reference selection should be made by JP2 triple of jumpers to change this setting operator has to...

Page 5: ...low Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection slo...

Page 6: ...stallation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The detec...

Page 7: ...pplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 gas calibration kit and the TUS40 handheld terminal which must be connected to t...

Page 8: ...ded for use in explosive gas atmosphere caused by mixture of air and gas vapours flammable mist Ex d IIC T6 Gb Type of protection complying with EN60079 0 and EN60079 1 BVI 07 ATEX 0032 Ext 02 14 EC t...

Reviews: