The enclosed instructions must be read carefully and should be kept together with the 
apparatus. Do not touch the detectors or the internal electronic circuitry for any reason. 
The 

Sensigas

®

 sensors are electronic devices and therefore should not be tampered. 

More  detailed  instructions  for  mounting  and  commissioning  are  contained  in  the 
apparatus packaging. 
UCE13.5 is provided with 3 resistances on terminals C.. and S.. Leave the resistance 
only if the relevant terminals are used to connect the sensor . 

Note: Sensors must be substituted before the end of the 5th year of use 

 

_______________________________________________________________________________________________  

UCE13.5 

UCE13.5 housing has standard DIN dimension (144 x 144 mm) used for wall mounting 
or  front  panel  mounting.  For  wirings  the  underside  of  the  unit  are  provided  with  5 
knockout holes for cable entry glands PG11 or rubber grommets. On front cover there 
are: 

-

 

3 LEDs (red) sensors state 

-

 

2 LEDs (1 green e 1 yellow) central unit state 

-

 

1 push button for alarm RESET  

Positive  logic  operation  (factory  preset)  causes,  in  case  of  sensor  failure  or  sensor 
cable  breakdown,  the  valve  shut  off  and  the  activation  of  the  auxiliary  devices  if 
present. 

 

_____________________________________________________________________________________________ 

 

    

                                                      

                

                          

 

 

 

 

 

 

Commissioning 

Layout 

UZY-13CB 

UZY20-R 

UCE13.5 

LEDs 

Jumper for valve type selection: 

NC (factory preset) 
NO 

End of line 
resistences 
18K

 ¼ W 

TEST / RESET 
push button 

Fixing supports for 
auxiliary cards 

Summary of Contents for Sensigas UR 13/A Series

Page 1: ...carbon monoxide with tin dioxide semiconductor sensing element ______________________________________________________________________________________________ The UCE13 5 Central Unit with one or more...

Page 2: ...al UZY20 R relay card and external buzzer if present When the cause of alarm has been removed is necessary to push the reset button on the front cover to return to normal operation After reset red LED...

Page 3: ..._______________________________________________________________ UCE13 5 EXT6 5 Installation has to be made respecting the temperature and humidity conditions indicated in Technical Data and in an acce...

Page 4: ...use _______________________________________________________________________________________________ UCE13 5 UCE13 5 housing has standard DIN dimension 144 x 144 mm used for wall mounting or front pan...

Page 5: ...mpliance with all the laws in force Caution There is no protection against accidental connection with 230VAC on the wrong terminals ____________________________________________________________________...

Page 6: ...osivity Limit Expected lifetime average 5 years from installation date Expander EXT6 5 Power supply 230VAC 10 15 Frequency 50 60 Hz Power consumption 30VA Optional card UZY 13CB Optical signalling Gre...

Page 7: ..._________________________________________________________________________________ Diagram 1 Central unit UCE13 5 with 1 3 UR 13 A sensors with 12VDC external buzzer and 12VDC solenoid valve __________...

Page 8: ...d of the product life or in the event of its replacement For disposal this product is defined as waste from electrical and electronic equipment electronic waste do not dispose of it as household waste...

Reviews: