The Auto-E-Connect function automatically recognizes ESERA chips, sensors and actuators, starts suitable 
libraries and outputs fully formatted data. 
The Auto-E-Connect functionality will be available from mid-2020 via 1-Wire Controllers, 1-Wire Gateways and  
1-Wire ECO from ESERA available. 
Further information on ESERA Auto-E-Connect can be found on the ESERA website, ESERA Config-Tool 3, or in 
the download area for this article in the ESERA Webshop. 
 

Technical data 

Embedded Computer 

CPU: 

 

 

Quad-Core processor ARM-Cortex-A53 64Bit, 1400 MHz 

Memory: 

 

RAM 1024 MB LPDDR2 memory  
microSD card 8GB for operating system and software application 

Operating system: 

Linux Debian (Raspian), software already installed 

Software, option: 

- IP-Symcon, basic, professional or unlimited 

 

- Codesys 3.x 

External interface: 

LAN RJ45 10/100/1000 Mbit (Gigabit LAN by USB 2.0 with up to 300 Mbit) 
- Auto negotiation (full-duplex and half-duplex) 

 

 

 

- Support for DHCP and IP-address 
- DNS support 
- Auto MDI/MDIX 

 

 

 

WLAN 802.11 b/g/n/ac (2,4 + 5,0 GHz) 

 

 

 

Bluetooth 4.2 

System clock (RTC): 

DS1307 with ability to bypass power failure with Goldcap for min. 24 hours 

 
1-Wire Gateway 

Data interface:   

Modbus RTU and ESERA ASCII text protocol 

Internal interface: 

serial, 19200 baud 8 data bit, 1 start bit, no stop bit 

Firmware update and  
configuration 

 

by ESERA Config-Tool 3 

 
1-Wire interface:  

1-Wire bus (Masse/GND, 5V, 12V and data) 

Protection circuits: 

ESD- and reverse polarity protection 

Connection: 

 

Push In connector for cables up to 1.5qmm cable cross section 

Output voltage: 

5V max. 1A, 12VDC max. 1,2A  
Overload and short circuit proof 

Digital- /binary input: 

2 x input 10-30VDC, max. 10mA per channel 
isolated with common negative pole 
Push In connector for cables up to 1.5qmm cable cross section 

Digital- /binary output: 

2 x output (relays) 16A switching current (NO), isolated 
 Push In connector for cables up to 2.5qmm cable cross section 

System clock (RTC): 

DS1307 with ability to bypass power failure with Goldcap for min. 24 hours

 

 

Entire system 

Power supply:   

16 

– 30 VDC 

Input: 

3,4 

– 38W* 

* depending on the CPU load and load on the 1-wire interface 

 

Ambient conditions 

Temperature, operation   -10 °C up to +55 °C (extended temperature range available upon request)

 

Air humidity:   

10 

– 92 % (non-condensing)  

Protection system:  

IP20  

Protection class:  

III  

Dimensions:   

35 x 90 x 70mm (WxHxD)  

 
 
 

Summary of Contents for ESERA-Station 200

Page 1: ... Networks Top hat rail case for switchboard assembly 1 Introduction Before you start assembling the ESERA Station 200 and before you take the device into operation please read this assembly and operating instruction carefully to the end especially the section referring to the safety notes 2 Product description The ESERA Station 200 is a modern and system open hybrid system consisting of two module...

Page 2: ...th 2 decimal places You only need to divide this number by 100 Within the 1 Wire Gateway a product specific transformation table is available for all 1 Wire sensor and actuator products offered by ESERA Designed for all 1 Wire Networks The 1 Wire interface of the ESERA Station 200 is specially designed to securely support all sizes of 1 Wire networks even for huge cable length 1 Wire sensor device...

Page 3: ...and half duplex Support for DHCP and IP address DNS support Auto MDI MDIX WLAN 802 11 b g n ac 2 4 5 0 GHz Bluetooth 4 2 System clock RTC DS1307 with ability to bypass power failure with Goldcap for min 24 hours 1 Wire Gateway Data interface Modbus RTU and ESERA ASCII text protocol Internal interface serial 19200 baud 8 data bit 1 start bit no stop bit Firmware update and configuration by ESERA Co...

Page 4: ...e refer to the following table for their functions LED Status Description Function Embedded Computer LED green front PWR Display supply voltage Embedded Computer LED green front DATA LED can be programmed for individual use GPIO 27 LED green Ethernet DATA Flashes while transferring data LED green Ethernet LINK Is lit if Ethernet connection is active 1 Wire Gateway LED green PWR Display supply volt...

Page 5: ...rmware update upgrade Optional input not equipped 2 x digital input 10 30VDC isolated Module bottom side left to right lower level 1 Wire bus output Masse GND Data 5V max 1A and 12V max 1 2A Reset button for 1 Wire Gateway inside Digital output 1 max 16A Digital output 2 max 16A upper level 3 x USB output 5V max 0 5A Ethernet input RJ45 10 100 1000 MBit Note Basics and tips for 1 Wire bus systems ...

Page 6: ...of this user guide complete or in part requires the written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH ESERA Automation 2020 www esera de 19200 V2 0 R1 0 Manual Page 6 of 10 10 Connection ESERA Station 200 sensors and actuators ...

Page 7: ...ils can be found in the sample script 13 Configuration and communication 1 Wire Gateway The well tested 1 Wire Gateway is installed inside the ESERA Station The 1 Wire Gateway has a wide range of configuration and formatting options which are read out and operated with the ESERA Config Tool 3 For communication among 1 Wire Gateway and Config Tool 3 the open ESERA ASCII text protocol is used Any co...

Page 8: ...anual which can be found in the download area of this product on our website and by the configuration software ESERA Config Tool 3 Partial Modbus address specification Specification reading address number of words 16Bit type of data Controller No 60000 1 text Article No 60001 1 text Firmware Version 61000 4 string Hardware 61010 3 string Serial number 61020 9 string Time 61030 4 string Date 61035 ...

Page 9: ... a qualified electrician must be consulted It must be examined generally before the commissioning of a device whether this device or module is basically suitable for the application in which it is to be used In case of doubt consultation with experts or the manufacturer of the components used is absolutely necessary For operational and connection errors outside of our control we assume no liabilit...

Page 10: ...g those which are not explicitly marked are trademarks registered trademarks or other copyright or trademarks or titles or legally protected designations of their respective owners and are hereby expressly recognized as such by us The mention of these designations logos names and trademarks is made for identification purposes only and does not represent a claim of any kind on the part of ESERA Gmb...