background image

 

 
 

Art. No. 19200  

 

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of 
ESERA GmbH. Errors and technical modification subject to change. 



ESERA GmbH, ESERA-Automation 2020 

www.esera.de 

19200 V2.0 R1.0  Manual 

Page 1 of 10 

 

User Guide 

ESERA-Station 200  

 

 

  Central hard- and software control (system-open) 

for smart home, building automation, IoT and 
commercial automation 

  Hybrid construction consisting of Embedded 

Computer and 1-Wire Gateway  

  Powerful, modern quad core computer with 1.4GHz 

CPU speed 

  Fast reading of all 1-Wire devices within 1-2 

seconds 

  Data exchange among 1-Wire Gateway and 

computer via Modbus or text protocol 

  Large 1-wire libraries for sensors and actuators 

  2 x binary output 16A  

  2 x binary input 10-30VDC 

  2 x System clocks with power-failure buffering 

  Convenient configuration program for 1-Wire 

Gateway and interface parameters 

  24V power supply for Embedded Computer and 

1-Wire gateway 

  Designed for all sizes of 1-Wire Networks 

  Top-hat rail case for switchboard assembly 

 

 
 

   
 

 

Introduction 

Before you start assembling the ESERA-Station 200 and before you take the device into operation, please 
read this assembly and operating instruction carefully to the end, especially the section referring to the safety 
notes. 
 

Product description

 

The ESERA-Station 200 is a modern and system-open hybrid system consisting of two modules, a powerful 
1-Wire gateway and an Embedded Computer. 
Both modules are internally connected by a serial data interface and the power supply. 
Each module has an own power supply and a system clock (real time clock) with power-failure buffering by a low-
maintenance, high-performance capacitor (Goldcap). 
 

2.1 

Embedded Computer 

The ESERA-Station 200 includes a standardized and powerful computer that comes with a  
Quad Core CPU with 1400MHz. This CPU provides enormous power reserves by low power consumption. Given 
to its 1024 MB RAM memory, even large automation projects can be implemented. 
All modern interfaces such as LAN, WLAN with 2.4GHz and 5GHz, as well as Bluetooth with standard 4.2 are 
available for connection with the "outside world". 
The Embedded Computer also has 3 external and one internal USB 2.0 interfaces. 
  
 

Summary of Contents for ESERA-Station 200

Page 1: ... Networks Top hat rail case for switchboard assembly 1 Introduction Before you start assembling the ESERA Station 200 and before you take the device into operation please read this assembly and operating instruction carefully to the end especially the section referring to the safety notes 2 Product description The ESERA Station 200 is a modern and system open hybrid system consisting of two module...

Page 2: ...th 2 decimal places You only need to divide this number by 100 Within the 1 Wire Gateway a product specific transformation table is available for all 1 Wire sensor and actuator products offered by ESERA Designed for all 1 Wire Networks The 1 Wire interface of the ESERA Station 200 is specially designed to securely support all sizes of 1 Wire networks even for huge cable length 1 Wire sensor device...

Page 3: ...and half duplex Support for DHCP and IP address DNS support Auto MDI MDIX WLAN 802 11 b g n ac 2 4 5 0 GHz Bluetooth 4 2 System clock RTC DS1307 with ability to bypass power failure with Goldcap for min 24 hours 1 Wire Gateway Data interface Modbus RTU and ESERA ASCII text protocol Internal interface serial 19200 baud 8 data bit 1 start bit no stop bit Firmware update and configuration by ESERA Co...

Page 4: ...e refer to the following table for their functions LED Status Description Function Embedded Computer LED green front PWR Display supply voltage Embedded Computer LED green front DATA LED can be programmed for individual use GPIO 27 LED green Ethernet DATA Flashes while transferring data LED green Ethernet LINK Is lit if Ethernet connection is active 1 Wire Gateway LED green PWR Display supply volt...

Page 5: ...rmware update upgrade Optional input not equipped 2 x digital input 10 30VDC isolated Module bottom side left to right lower level 1 Wire bus output Masse GND Data 5V max 1A and 12V max 1 2A Reset button for 1 Wire Gateway inside Digital output 1 max 16A Digital output 2 max 16A upper level 3 x USB output 5V max 0 5A Ethernet input RJ45 10 100 1000 MBit Note Basics and tips for 1 Wire bus systems ...

Page 6: ...of this user guide complete or in part requires the written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH ESERA Automation 2020 www esera de 19200 V2 0 R1 0 Manual Page 6 of 10 10 Connection ESERA Station 200 sensors and actuators ...

Page 7: ...ils can be found in the sample script 13 Configuration and communication 1 Wire Gateway The well tested 1 Wire Gateway is installed inside the ESERA Station The 1 Wire Gateway has a wide range of configuration and formatting options which are read out and operated with the ESERA Config Tool 3 For communication among 1 Wire Gateway and Config Tool 3 the open ESERA ASCII text protocol is used Any co...

Page 8: ...anual which can be found in the download area of this product on our website and by the configuration software ESERA Config Tool 3 Partial Modbus address specification Specification reading address number of words 16Bit type of data Controller No 60000 1 text Article No 60001 1 text Firmware Version 61000 4 string Hardware 61010 3 string Serial number 61020 9 string Time 61030 4 string Date 61035 ...

Page 9: ... a qualified electrician must be consulted It must be examined generally before the commissioning of a device whether this device or module is basically suitable for the application in which it is to be used In case of doubt consultation with experts or the manufacturer of the components used is absolutely necessary For operational and connection errors outside of our control we assume no liabilit...

Page 10: ...g those which are not explicitly marked are trademarks registered trademarks or other copyright or trademarks or titles or legally protected designations of their respective owners and are hereby expressly recognized as such by us The mention of these designations logos names and trademarks is made for identification purposes only and does not represent a claim of any kind on the part of ESERA Gmb...

Reviews: