Auto-E-Connect® Support 

The ESERA 

Auto-E-Connect®

 1-Wire Plug and Play system will be used for the  

1-Wire Bus supported. This enables fully automatic configurations of 1-Wire sensors 
and actuators on the 1-Wire bus. It is optimized for industrial applications and 
enables significant added value beyond the sensor and chip data. 
The Auto-E-Connect function automatically recognizes ESERA chips, sensors and actuators, starts suitable 
libraries and outputs fully formatted data. 
The Auto-E-Connect functionality will be available from mid-2020 via 1-Wire Controllers, 1-Wire Gateways and  
1-Wire ECO from ESERA available. 
Further information on ESERA Auto-E-Connect can be found on the ESERA website, ESERA Config-Tool 3, or in 
the download area for this article in the ESERA Webshop. 
 

Technical data 

1-Wire function:  

DS2450 commands, current and voltage output measurement 

 

Port function: 

 

Port 0 = current 12 V 

(12 Bit, 5 V) 

 

 

 

Port 1 = voltage 12V 

(12 Bit, 5 V) 

 

 

 

Port 2 = current 5V 

(12 Bit, 5 V) 

 

 

 

Port 3 = voltage 5V  

(12 Bit, 5 V) 

Input voltage: 

 

typ. 24 V DC (18 

– 36 V DC) 

Energy Efficiency: 

>= 90 % 

Output Power:    

max. 15W 

Output:   

 

5 V maximum 0,5 A  
12 V maximum 1 A (in total for 5 V and 12 V maximum 15W) 

Indicator:  

 

Power LED (5 V) and 1-Wire activity 

Interfaces: 

Input for 1-Wire Controller or 1-Wire Bus Coupler  
Output for 3 x 1-Wire network (output 1 adjacent top-hat rail modules) 

Function: 

The devices has no repeater function for 1-Wire data lines 
Outputs are connected internally.  

Connection: 

 

Screw terminals up to 2.5 qmm cable cross section 

Auto-E-Connect: 

will be supported 

 

Ambient conditions 

Protection system: 

IP20 

Protection class: 

III 

Temperature, operation:  -10°C to +50°C  
Air humidity: 

 

10 - 92% (non condensing) 

Dimensions:  

 

71 x 71 x 90 mm (WxHxD) 

Weight:  

 

174 g 

 

Conformity 

EN 50090-2-2 
EN 61000-4-2, ESD 
EN 61000-4-3, HF 
EN 61000-4-4, Burst 
EN 61000-4-5, Surge 
EN 61000-6-1, Fault-free operation 
EN 61000-6-3, Stray radiation 
RoHS 

 

LED indicators 

The module has different display LED`s. Please refer to the following table for their functions: 

LED status 

Description 

Function 

LED green 

Power 

Display for 5 V output voltage (if LED is lit, 12 V output voltage is 
available due to the system) 

LED green 

Data 

 

Flashes at 1-Wire activity 

 

Is permanently lit if 1-Wire Bus Coupler is missing or input is 
not connected 

 

Is permanently lit in case of a short circuit of one of the 1-
Wire outputs  

Summary of Contents for 1-Wire Hub III DC

Page 1: ...e in a network and is connected directly to a 1 Wire Bus Coupler or 1 Wire Controller Due to the input voltage range of 18 36 V the device is ideally adapted to the system environment of PLC controls for 24 VDC supply To operate the 1 Wire Hub III an upstream system power supply providing the input voltage of 24 V e g a DIN rail power supply is necessary The 1 Wire Hub III DC is equipped with a me...

Page 2: ...age 12V 12 Bit 5 V Port 2 current 5V 12 Bit 5 V Port 3 voltage 5V 12 Bit 5 V Input voltage typ 24 V DC 18 36 V DC Energy Efficiency 90 Output Power max 15W Output 5 V maximum 0 5 A 12 V maximum 1 A in total for 5 V and 12 V maximum 15W Indicator Power LED 5 V and 1 Wire activity Interfaces Input for 1 Wire Controller or 1 Wire Bus Coupler Output for 3 x 1 Wire network output 1 adjacent top hat rai...

Page 3: ... V mA DS2450_Port2 20 current 12 V mA DS2450_Port0 22 9 Connection plan A connection plan and a connection example with further modules are available in our webshop Pin assignment input power supply Bus Coupler Controller 14 plus supply voltage 15 minus supply voltage 16 grounding PE 23 Ground 1 Wire input 24 1 Wire data line 25 5 V input from master e g 1 Wire Controller or 1 Wire Bus Coupler Pin...

Page 4: ... requires the written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH ESERA Automation 2020 www esera de 11322 V2 0 R1 1 Manual Page 4 of 6 10 Connection Example Example with 1 Wire Controller or 1 Wire Gateway 1 Wire Hub III Dual Digital Output and 8 fold digital input ...

Page 5: ...ischarged Live cables or wires to which the device or an assembly is connected must always be tested for insulation faults or breaks If an error is detected in the supply line the device must be immediately taken out of operation until the faulty cable has been replaced When using components or modules it is absolutely necessary to comply with the requirements set out in the accompanying descripti...

Page 6: ...SERA GmbH accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical or electronic errors in the online offer We are constantly developing our products further and reserve the right to make changes and improvements to any of the products described in this documentation without prior notice Should you require documents or information on older versio...

Reviews: