P09.28
P10 group––Simple PLC and multi-step speed control
P10.00 Simple PLC mode
0: Stop after running once; the VFD stops
automatically after running for one cycle, and
it can be started only after receiving running
command.
1: Keep running in the final value after
running once; The VFD keeps the running
frequency and direction of the last section
after a single cycle.
2: Cyclic running; the VFD enters the next
cycle after completing one cycle until receiving
stop command and stops.
0
○
P10.01
Simple PLC
memory selection
0: No memory after power-off
1: Memory after power-off; PLC memories its
running stage and frequency before power-off.
0
○
P10.02 Multi-step speed 0 Frequency setting range for steps from step 0
to step 15: -100.0–100.0%. 100.0%
corresponds to the max. output frequency
P00.03.
Running time setting range for steps from step
0 to step 15: 0.0–6553.5s(min). The time unit
is specified by P10.37.
When simple PLC operation is selected, it is
required to set P10.02–P10.33 to determine
the running frequency and running time of
each step.
Note:
The symbol of multi-step speed
determines the running direction of simple
PLC, and the negative value means reverse
running.
P10.02
P10.04
P10.06
P10.32
P10.30
P10.28
Deceleration time
(two steps)
Acceleration time
(two steps)
P10.03
P10.05
P10.07
P10.31
P10.33
0.0%
○
P10.03
Running time of
step 0
0.0s(min)
○
P10.04 Multi-step speed 1
0.0%
○
P10.05
Running time of
step 1
0.0s(min)
○
P10.06 Multi-step speed 2
0.0%
○
P10.07
Running time of
step 2
0.0s(min)
○
P10.08 Multi-step speed 3
0.0%
○
P10.09
Running time of
step 3
0.0s(min)
○
P10.10 Multi-step speed 4
0.0%
○
P10.11
Running time of
step 4
0.0s(min)
○
P10.12 Multi-step speed 5
0.0%
○
P10.13
Running time of
step 5
0.0s(min)
○
P10.14 Multi-step speed 6
0.0%
○
P10.15
Running time of
step 6
0.0s(min)
○