GD350A series high-performance multifunction VFD
-194-
Function
code
Name
Description
Default Modify
multi-step speed running has the priority
Hundreds place: Action selection for stop
0: Setting is valid.
1: Valid during running, cleared after stop
2: Valid during running, cleared after a stop
command is received
P08.45
Frequency
increment integral
rate of the UP
terminal
0.01–50.00Hz/s
0.50Hz/s
○
P08.46
Frequency integral
rate of the DOWN
terminal
0.01–50.00Hz/s
0.50Hz/s
○
P08.47
Action selection at
power-off during
frequency setting
0x000–0x111
Ones place: Action selection at power-off
during frequency adjusting through digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
Action selection at power-off during frequency
adjusting through Modbus/ Modbus TCP
communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
Hundreds place: Action selection at power-off
during frequency adjusting through other
communication methods
0: Save the setting at power-off.
1: Clear the setting at power-off.
0x000
○
P08.48
Initial electricity
consumption high-
order bits
Used to set the initial electricity consumption.
Initial electricity consumption =P08.48*1000+
P08.49
Setting range of P08.48: 0–59999 kWh (k)
Setting range of P08.49: 0.0–999.9 kWh
0°
○
P08.49
Initial electricity
consumption low-
order bits
0.0°
○
P08.50
Magnetic flux
braking
The function code is used to enable magnetic
flux braking.
0: Invalid
0
○