ets-lindgren.com
EMControl Command Set
75
VS?
Description:
Queries the variable speed capability of the device.
Devices:
Turntables, towers
Syntax:
VS?
Response:
<flag>
: Indicates if a device is capable of variable speed
control
0
: Device is not capable of
variable speed control
1
: Device supports variable speed
Example:
Write
sdVS?\n
: Is device variable speed?
Read response
Response is
1\n
: Is a variable speed device
WL
Description:
Changes the clockwise limit of the device. The specified value
must be greater than the counterclockwise limit and between
–999 and 999.
Devices:
Turntables
Syntax:
WL [+/-] XXX
+
: Optional for positive values
–
: Necessary for negative values
XXX
: Decimal value for the clockwise limit to be set in
degrees. Leading zeroes are optional.
Response:
OK
, or an error (error number)
Example:
Write
sdWL 90\n
: Change CW limit of the turntable to
90 degrees
See Also:
WL?
Summary of Contents for ETS-Lindgren EMControl 7006-001
Page 1: ...Model 7006 001 EMControl Positioner Controller Plug In Card User Manual...
Page 8: ...viii ets lindgren com This page intentionally left blank...
Page 12: ...12 Introduction ets lindgren com This page intentionally left blank...
Page 16: ...16 Specifications ets lindgren com This page intentionally left blank...
Page 18: ...18 EMControl Plug In Card Installation ets lindgren com This page intentionally left blank...
Page 88: ...88 EMControl Command Set ets lindgren com This page intentionally left blank...
Page 90: ...90 Warranty ets lindgren com This page intentionally left blank...