Escea DL850 User Manual Download Page 11

Flame Failure or 

Power Flue trip

The fire has tried to light three times and failed.

• 

Check gas supply and check other gas appliances to see if they are 

affected. If you have two separate LPG cylinders, switch over to the 

full bottle or contact your gas supplier. You may need to retry ignit-

ing the fire a few times after re-establishing gas supply. 

• 

Check correct gas pressure to the appliance with all other appliances 

running

• 

Check the electrode placement in relation to the pilot flame. Ensure 

it is well enveloped in flame as per the diagram in the installation 

instructions. Ensure no small coals have dropped onto the ignition 

electrodes between the burners.

• 

Ensure the electrode is not contacting any metalwork including the 

burners and has the correct air gap.

• 

Check that the electrical power cable between the appliance and 

the power-flue wall terminal is connected and not damaged

• 

Check that the fan inside the powerflue wall terminal is running dur-

ing startup. This fan may need servicing if it is slowed or stalled.

Appliance Over 

Temperature 

Sensor Trip

The bimetallic snap disk mounted on the spigot seal plate at the rear of 

the fire has tripped. The possible causes for this could include:

• 

Possibly fascia panels installed incorrectly resulting in restricted air 

flow at the top of the fire.

• 

Room air fans may be slowed or stalled. Remove firebox, check that 

fans are plugged in, cleaned, and free turning

• 

The gas regulator being set too high resulting in excess heat build-

up.

• 

The inlet flue not being connected and the appliance drawing warm 

air from the cavity. Check flues are securely connected at both ends.

Valve Solenoid 

Check Failure

The valve solenoids have failed the pre-ignition test. This is to detect a 

faulty valve solenoid. However, it is possible a wire has dislodged. 

• 

Check that the connections to each solenoid are secure and in place. 

It may be that the connections on the ends of the wires need to be 

tightened a little (e.g. with a pair of pliers) to ensure a robust con-

nection to the valve terminal.

• 

Disconnect and reconnect the firebox connectors ensuring they are 

firmly pushed into place.

• 

It could also be that one of the solenoids on the valve inside the fire 

has failed. If this is the case the valve will need to be replaced.

Remote Cannot 

communicate 

with fire

The remote cannot communicate with the fire. Reasons for this could 

include:

• 

The fire being turned off “at the wall” i.e. a loss of power to the fire or 

the remote is outside of its effective radio frequency range (too far 

away from the fire). Typical remote range is 1m to 12m. 

• 

Ensure there is power to the fire by pressing the auxiliary on/off (red) 

button on the fire, then press the on/off button on the remote to 

clear the error.

Summary of Contents for DL850

Page 1: ...User Guide For the latest documentation visit www escea com 630160_1 DX1500 DL850 Gas Fireplace...

Page 2: ...D SERVICED AT LEAST ANNUALLY BY AN AUTHORISED TECHNICIAN THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER S WRITTEN INSTRUCTIONS THIS APPLIANCE IS NOT INTENDED FOR USE BY YOUNG CHI...

Page 3: ...4 Keylock 06 5 Timer Operation 06 Activate Timer De activate Timer 6 Auxiliary On Off Button 07 7 Over Temp Shutoff Operation 07 8 Sound and Smell 09 Sounds Fan Gas Control Valve Appliance Metalwork...

Page 4: ...tatus of timers and other functions On Off Switches the appliance on and off Flame Effect Places the fire in a constant low output mode Minus Adjusts the temperature and time settings down NOTE The fa...

Page 5: ...e set by the remote Fan Boost The fire has four FAN SPEED settings The first low fan speed will run automatically on start up The second and third fan speed will automatically switch on or off with th...

Page 6: ...ill change the hour Pressing the TIMER SELECT button 5 again will make the minute figures start flashing You will continue to see the ON and the number 1 This indicates that you are currently editing...

Page 7: ...Set temperature This is referred to as the Overtemp Shut Off Mode To enable Overtemp Shut Off Mode so the fire will turn off all burners when the Room temperature climbs above the Set temperature you...

Page 8: ...he fire is switched off after being run for a while there may be popping and fluttering noises as the residual gas in the burner burns away These are normal and should be no cause for concern Applianc...

Page 9: ...cleaner Cleaning maintenance will need to be carried out whenever soot builds up on the logs and or inside of the glass If soot build up becomes excessive or regular then it is recommended that you co...

Page 10: ...e order and test run heater 10 Trouble shooting Escea gas fires communicate both to and from the fire and remote This enables the remote to provide some basic fault finding information that is useful...

Page 11: ...in restricted air flow at the top of the fire Room air fans may be slowed or stalled Remove firebox check that fans are plugged in cleaned and free turning The gas regulator being set too high resulti...

Page 12: ...dance with ESCEA operating and maintenance instructions then for the first period of 12 months from the date of purchase ESCEA will pay the cost of repairing or replacing any part of the Product that...

Reviews: