GB
Offset / Parallel adjustment
1.
To set the offset / parallel adjustment of the
characteristic heating curve press the middle button for 5
seconds to reach advanced settings (A).
2.
Choose menu “OFS” by pressing the left or right button
(B) OK (C).
3.
Decide the offset by pressing the left or right button
(D) OK (C).
4.
Press the middle button for 5 seconds to return to
main menu (A).
Note: When the offset setting is negative (-1 to -90ºC)
the minimum flow temperature will be the lower limit but
other than that the complete characteristic heating curve
will be parallel adjusted. When the offset setting is positive
(+1 to +90ºC) the maximum flow temperature will be the
upper limit but other than that the complete characteristic
heating curve will be parallel adjusted.
DE
Einstellen von Offset bzw. Parallelverschiebung
1.
Die Kennlinie kann parallel nach oben bzw. unten
verschoben werden. Drücken Sie 5 Sekunden den Punkt um
in die erweiterten Einstellungen zu gelangen (A).
2.
Wählen Sie den Menüpunkt “OFS” (B) durch drücken der
Pfeiltasten, dann Punkt drücken (C).
3.
Verschieben Sie die Kennline um +/- ...°C durch drücken
der Pfeiltasten (D), dann Punkt drücken (C).
4.
Drücken Sie den Punkt (A) für 5 Sekunden um in das
Hauptmenü zurückzukehren.
Hinweis: Wenn die Offset- Einstellung (Parallelverschiebung)
negativ ist (-1 bis -90°C) ist, entspricht die Soll-
Vorlauftemperatur mindestens der eingestellten
minimalen Vorlauftemperatur. Wenn die Offset- Einstellung
(Parallelverschiebung) positiv ist (+1 bis +90°C) ist, entspricht die
Soll- Vorlauftemperatur höchstens der eingestellten maximalen
Vorlauftemperatur. Die restliche Kennlinie wird innerhalb der
eingestellten Minimal/Maximal- Grenzen parallel verschoben.
B
C
D
Offset
7
5s
A
OK
—
+
—
+