6) INSTALLATION
Origo™ Arc are a three-phase welding rectifier, to be connected across three input phases. The mains
cable is connected to the circuit breaker. The primary terminal is reconnectable for different input voltages
(220, 380 or 440 V - 60Hz). The electrical diagram shows the different voltage connections procedures.
Remove the cover on the left panel and reconnect the terminal block as shown on the electric diagram.
Recommended cable areas and fuses ratings are listed below.
Connected the rectifier across three input phases and ground connection according to regulations.
IMPORTANT!
:
The grounding terminal is connected to the rectifier chassis. It
must to be connected to an efficient grounding point to the general power
supply system.
18
Origo™ Arc 256/406/456
440V 60Hz
380V 60Hz
220V 60Hz
01
02
02
01
01
02
TABLE 6.1
Voltage
(V)
456
91
49
45
406
87
48
44
256
109
63,5
54
256
120
70
63
406
100
63
50
456
100
63
50
16,0
10,0
10,0
Cable
(Cu - mm2)
Primary current (A)
for 60% duty cycle
Fuse delay (A) or
Circuit-breaker (A)
220
380
440