2. INSTALLATION RULES
2.1
For connections to PLC or to other devices please use the provided units with galvanically isolated entry.
2.2
DO NOT REMOVE the PL connector with power supply ON. TC probe could be damaged in no reparable way.
2.3
For the electrical connections use antiflame shielded cable 3 x 0,75 mm²
2.4
Remove the TC probe in case of electric weldings on the support structure of it and during the maintenance.
2.5
Pretect the 'head' of the probe against the direct exposure to sun light.
2.6
Every kind of operation on TC probe must be done without dust in the air and, when it is possible, with supply voltage Off
2.7
A remarkable quantity of rain or water in the sampled gases could distort the reading of the signal.
3. WIRING DIAGRAM
4. TECHNICAL FEATURES
Supply Voltage
16 ÷ 24 VDC 100 mA
Output signal
4 ÷ 20 mA Activ. Maximum load 350 Ohm
GAS temperature:
120°C with BS40 (Standard)
GAS temperature:
200°C with BS200 (On Request)
GAS temperature:
400°C with BS400 (On Request)
Operating temperature
- 10 ÷ + 50 °C
Relative humidity
80 %
Protection degree
IP65
Particle Size
>= 0.3 µm
We reserve the right to make any change without notice