ES-System ES-AW-8 User Manual Download Page 2

User manual  – ES-AW-8

GENERAL CONDITIONS

Moduł awaryjny należy instalować zgodnie z niniejszą instrukcją, z zachowaniem norm dotyczących bezpieczeństwa użytkowania. Wszelkie czynności instalacyjne i konserwacyjne należy wykonywać  

The emergency module must be installed in accordance with these instructions, while maintaining safety standards. All installation and maintenance activities must be carried out after disconnecting the 

supply voltage and the battery. Installation and maintenance may only be performed by authorized persons. 

Making changes in the device’s design and using it under conditions other than those described in these instructions is prohibited. 

FEATURES

Emergency module for use with LED light sources.

•  The emergency module’s electronic system features the following functions:

•  - automatic battery charging

•  - battery protection against deep discharge

•  - indicating correct functioning or damage to the module

The set includes:

•  - the electronics encased in housing

•  - maintenance-free Ni-MH batteries

•  - mounting brackets or battery housing depending on the application

•  - instruction manual

OPERATION MODE INDICATION

LED

Operation mode

On

Correct operation, charger working

Off

Emergency operation, not charging

GUARANTEE

ES-SYSTEM guarantees the correct and reliable operation of its devices (according to the general terms and conditions), provided they are used as intended and in accordance with the principles in the 

instructions. The products are manufactured using the latest technologies and compliant with Polish standards and harmonized European Union standards. 

WIRING DIAGRAMS

FUNCTIONING PRINCIPLES

First-time operation

Due to the construction of the Ni-MH battery and in order to ensure its proper formation, it is recommended that its first charging lasts 48 hours. During this time, emergency operation is not allowed and no 

testing can be performed. After this time, the module must be switched to emergency operation (by disconnecting the voltage in the L* line). The module should operate in this mode until the batteries are 

completely depleted. The power supply voltage must then be switched back on, and the batteries must be charged for at least 36 hours in order to complete the formation cycle.

USE

Testing:

The emergency module functionality must be tested regularly (in accordance with the PN-EN 50172 standard) by disconnecting the voltage in the L* control line or by using the optional P2 button connec-

ted to the T1, T2 terminals.

Supporting functions:

Emergency mode blocking is possible using the control signal from the RM unit. Once the block is activated, the module will not switch to the emergency mode during a power failure in the L* line. Once mains 

power is restored to the L*line, normal operation will resume. Blocking the emergency mode from the RM control unit with a bi-stable connector maintains the emergency mode block until it is removed. 

Detailed technical information and wiring diagrams can be found in the instruction manual of the RM control unit.

INSTALLATION

The components of the emergency module are intended for installation in a luminaire. The LED indicator must be visible during use and in different conditions, for example in the ceiling void – this is mandatory 

due to safety requirements applicable during the use of electrical devices and installations. The cable length between the emergency module and the 1W LED may not be longer than 1 m. The emergency 

module and the battery must not be placed near heat sources. The temperature of the electronics housing measured at the Tc point must not exceed the maximum value. The voltage control line L* must not 

include switches or other devices which could disconnect the line. The luminaire connection system should be carried out according to one of the wiring diagrams included in this instruction manual. Before 

switching on the voltage, it is necessary to make sure that all the connections have been performed correctly.

Charging the battery with any device other than the electronics system of the emergency module is not allowed.

ES-AW-8 STI technical data

Power supply voltage

230 VAC +-10% 50-60Hz

Maximum power consumption

6W

Ingress protection rating

IP20

Safety class

II

Operating temperaturę range

Ta = 0..+50*C

Weight of the electronics

0,36 kg

Wire cross-section

0,2 – 1,5 mm^2

  

 

 

 

 

 

 

      

Ordering codes

Autonomy time

ES-AW-8

1h

3h

260mA

 

9346110

 ES-AW-8-SKTA/TC1

9346130

 ES-AW-8-SKTA/TC3

450mA

 

9346210

 ES-AW-8-SLTA/TC1

9346230

 ES-AW-8-SLTA/TC3

700mA

9346310

 ES-AW-8-SMTA/TC1

9346330

 ES-AW-8-SMTA/TC3

1200mA

9346410

 ES-AW-8-SNTA/TC1

9346430

 ES-AW-8-SNTA/TC3

         

Faulty emergency modules and batteries must  

be returned to the supplier for recycling.

 The dimensions of the emergency module and the battery

RM
RM

RM
RM

L*
L
N

N
L*
L

RM
RM

-

+

-

+

INHIBIT MODE

230 V

50 Hz

INHIBIT MODE

LED

BAT

ES-AW-8 MODULE

N
L*
L

RM
RM

-

+

-

+

230 V

50 Hz

LED

BAT

ES-AW-8 MODULE

L*
L
N

N
L*
L

DA
DA

-

+

-

+

DALI / CTI

230 V

50 Hz

LED

BAT

ES-AW-8 MODULE

DA
DA

N
L*
L

DA
DA

-

+

-

+

DALI / CTI

230 V

50 Hz

LED

BAT

ES-AW-8 MODULE 

DA
DA

STI

CTI/A

TI

/CTI-DALI

LED INDICATOR

LED INDICATOR

LED INDICATOR

LED INDICATOR

190

23

232

30

31

30

32

02.2016