8

  

 

Pedestrian open/close programming

This is carried out in the same way as total open/close
programming, with the following differences:

DIP1 and DIP3 are used instead of DIP1 and DIP2

ST2 is used instead of ST1 (except in step 1)

DIP

Modes and functions

Option

Effect

DIP1

Programming mode

ON

Programming mode enabled. The door can also be opened or closed by
holding down ST1 or ST2 (in order to check turning direction, position the
door, etc.).

OFF

Operating mode (programming disabled)

DIP2

Without use

OFF

Always place in OFF

DIP3

Opening mode

ON

alternative stop

 (the door stops if a key command is enabled during

opening, and closes if enabled again)

OFF

collective opening

 (the control board does not obey the key commands

during opening)

DIP4

Automatic or step-by-step mode 
(for pedestrian and total 
operation)

ON

automatic mode

 (the door closes automatically after standby time has

passed, which is adjusted using T.E.). Standby time restarts if the photocell
is enabled

OFF

step-by-step mode

 (the door only closes when receiving the key command)

DIP5

ST1 and ST2 functions 
(A.T. and A.P.)

ON

ST1: opening; ST2: closing (PAC)

OFF

ST1: total operation; ST2: pedestrian operation

DIP6

Automatic mode optional 
(only if DIP4 = ON)

ON

during standby, the door obeys the key commands (can be closed before
standby time finishes)

OFF

the door cannot be closed until standby time finishes; a key command will
cause standby time to restart

DIP7

Braking due to reverse

ON

braking due to reverse enabled

OFF

braking due to reverse disabled

DIP8

Slowdown

ON

slowdown enabled in opening and closing: the leaves reduce their speed
before reaching the stopper

OFF

no slowdown:  the leaves reach the stopper at high speed

DIP9

Door type selection

ON

sliding door

OFF

up-and-over door with shadow function

DIP10

Dead-man mode
Only with DIP4=OFF

ON

with DIP5=ON: 

dead-man mode in closing (HPC)

; the door is opened

by briefly holding down ST1, and closed by holding down ST2

with DIP5=OFF: 

dead-man mode in opening and closing (HPAC)

; the

door is opened by holding down ST1, and closed by holding down ST2

OFF

Dead man function disabled

Function and mode selection using SW2 (DIP1 = OFF)

P311M

Potentiometer adjustment

T.LG. (garage light time):

 if the garage lighting circuit has been connected to

the control panel, regulate the time which the lights remain on using T.LG.

T.E. (door open standby time):

 if automatic functioning mode has been

programmed (DIP4=ON), set T.E. to adjust standby time with the door open
(before automatic closing begins).

P.M (motor torque):

 use P.M. to adjust the operator's maximum power value.

Hydraulic operators: set P.M. at the maximum value.

Electromechanical operators (anti-crushing function sensitivity): set P.M at
the minimum value possible, compatible with the proper operation of the
door.

Torque adjustment, respecting the maximum closing forces set out in
Standard EN12453:2000. Make the measurements as described in
Standard EN 12445:2000.