ERNITEC Eagle PIR-100 Installation Manual Download Page 8

 
 
 
 

Page 8 (12) 

 

www.ernitec.com 

14 External Sensitivity Adjustment via RS 485 Data Bus 

If the 

DIP - Switches 1 and 2

 are both set to 

„on“

, the detection performance can be adjusted via the RS 485 two 

way communication port. Range sensitivity of the model PIR-100 can be set to values between 60 m and 
maximum, and model PIR-100H to values between 75 m and maximum. In addition to this, the overall sensitivity 
can be fine adjusted by using the software sensitivity button. 
The external sensitivity adjustment may also be used if overall sensitivity has to be changed at certain periods of 
the day or year depending on the prevailing thermal contrasts. Field tests in the actual environment will determine 
the optimum settings. 

15 Signal Processing 

The sophisticated signal processing ensures an optimum performance and reliability of the detector. 
The background noise is sampled and averaged over a large number of cycles giving a noise dependent value for 
the alarm threshold and to start the adaptive signal shape analysis whenever a certain amplitude value is 
exceeded. If the threshold has temporarily been increased by high background noise or repeated movements in the 
field of view, the exponential decay of the threshold level to its original value will take app. 1 … 2 minutes from the 
end of the event. 
Once the threshold level value has been exceeded, the microprocessor starts its signal shape analysis routine 
where a number of interdependent parameters are calculated and analysed. 
Only if a signal meets all the predetermined criteria an alarm will be generated. 

16 Accessories 

16.1  Interface Module PIRIF 485/2 and Installation Software 

The Installation Software is very useful for alignment and signal check during setting up and routine maintenance. It 
will indicate the amplitudes generated by wanted as well as unwanted targets and help setting the gain control 
correctly during walk tests and also show the magnitude of disturbance signals. The installation software is to be 
installed on a PC; an interface module is required to convert RS 232/USB to RS 485. The information for 
installation and signal monitoring is displayed on the screen of the PC. 
If more than one detector is connected to the same RS 485 communication bus, each detector needs to have a 
different address (ID). 

Please see the PIRIF-485/2 Installation and Setup Manual, for further details. 

16.2  Pole Mount Hardware ZA P-L1 

Pole mounting bracket with two strap bands for poles of 4 – 16 cm diameter 

Summary of Contents for Eagle PIR-100

Page 1: ...Nominal Range 120 m 400 feet PIR 100H High Performance Nominal Range 150 m 500 feet Highlights Gap Free Coverage with Creep Zones 4 Meter 13 Feet Mounting Height Advanced Tamper Detection Low Power Co...

Page 2: ...Page 2 12 www ernitec com www ernitec com...

Page 3: ...Heater H version only 7 14 External Sensitivity Adjustment via RS 485 Data Bus 8 15 Signal Processing 8 16 Accessories 8 16 1 Interface Module PIRIF 485 2 and Installation Software 8 16 2 Pole Mount H...

Page 4: ...d for wall mounting using screws For pole mounting the original accessory ZA P L1 is available pole mounting bracket with two strap bands for poles of 4 16 cm diameter For further information please r...

Page 5: ...ve on the top of the detector This line of sight corresponds to the upper edge of the detection pattern Accurate fine alignment is easily achieved with the help of the Universal Telescopic Sight ZA P...

Page 6: ...eeding a certain minimum value will activate the ATD and increase the threshold levels depending on its strength The time constants for increase and decrease are chosen in a way to adapt to gradual ch...

Page 7: ...over RS 485 communication All the detectors connected to the same data bus provide all the information relevant to an alarm in a defined protocol frame For further information please contact the manuf...

Page 8: ...or repeated movements in the field of view the exponential decay of the threshold level to its original value will take app 1 2 minutes from the end of the event Once the threshold level value has be...

Page 9: ...on is a function of thermal contrast speed and size of a target crossing the field of view Contrast conditions can vary significantly in the course of the day and year Detection depends also on the se...

Page 10: ...d Output Transistor OC Not used GND Supply voltage 10 5 30 V DC 24 V AC 1 2 3 4 5 6 7 8 50 mA 6 V RS 485 A B 4 7 k 100 mA Sensitivity SW1 SW2 PIR 100 PIR 100H ON ON SW settings ON OFF HW setting maxim...

Page 11: ...nk it is necessary that the detectors have different addresses IDs For operation with a standard PC a converter to RS 485 is required The interface box is available as accessory 21 1 1 Application of...

Page 12: ...Weight app 900 g 2 0 lbs incl mounting bracket Cable Feeds 2 x M 16 with cable clamp Outer Cable Diameter 4 5 10 mm 0 18 0 40 inch Electrical Supply Voltage 10 5 30 V DC 24 V AC 15 Current Consumption...

Reviews: