Chimney
CAUTION
The TR is only deemed CE tested and approved
when used with the coaxial chimney described in
“Accessories”.
▷
Do not exceed the maximum length (5 m) of
the chimney.
▷
The design of the chimney depends on the prem-
ises and the roof construction.
▷
Various chimney elements for individual appli-
cations can be supplied, see page 20 (Ac-
cessories).
▷
The wall bracket cannot be installed in the correct
position until the chimney has been selected.
Wall bracket
▷
The wall bracket is the support and wall mount-
ing for the heater.
▷
The design of the mounting depends on
the premises and the wall construction, see
page 20 (Accessories).
▷
For its alignment, we recommend that the heater
is positioned at the correct height using a forklift
truck.
▷
The heater must remain on the forklift truck until
the wall bracket has been mounted to make it
easy to install.
CAUTION
To avoid damage to the heater TR, please observe
the following:
– If the slide is used for the wall bracket, position
the TR so that when the slide is extended it
does not tip over.
<– 0,2 m
≥ 1,6 m
Siphon connection
DANGER
Risk of poisoning!
–
If the TR is operated without a siphon or with
an empty siphon, toxic flue gases may escape.
▷
A siphon must be connected before commission-
ing. This prevents the escape of toxic flue gases
and will also collect any condensate contained
in the flue gas.
▷
The siphon is not included in the delivery and
must be ordered separately for the nominal size
of DN 40.
▷
Fill the siphon with water before commissioning.
▷
If large volumes of condensate are discharged,
we recommend that an additional drain pipe is
connected to the siphon.
▷
If the heater has not been used for a lengthy
period, the siphon must be checked, cleaned
and filled with water before commissioning.
•
Unscrew the siphon, remove it and fill it until
water flows out of the side drain.
•
Secure the siphon again and ensure that the seal
is correctly positioned.
Connecting the gas supply
▷
The TR is set to the correct gas type as specified
in the purchase order.
▷
If you wish to use a different gas type, see
page 3 (Changing the gas type).
Disconnect the system from the electrical power
supply.
Shut off the gas supply.
Remove the sealing plug from the gas inlet on the
combination control on the underside of the TR.
4
Connect the gas pipe with an R ¾" threaded
connection or gas hose with an R ¾" connector,
see page 20 (Accessories).
▷
Use approved sealing material only.
5
MOD
E
RES
ET
ON/O
FF
6
Changing the gas type
▷
If you wish to use a gas type other than the one
specified in the purchase order, you will have to
order an appropriate burner chip card.
▷
The TR must be set to the new gas type, see
page 9 (Adjusting the heater).
▷
Mark the new gas type on the type label using
waterproof ink.