D03283R01.10
TESLA LITE User Manual
Appendix D-1
Appendix D Modbus Functions
The TESLA LITE recorder operates as a slave device on the Modbus network,
with an address of 1 to 247 (decimal), 0x01 to 0xF7. The Point List can be
printed through TESLA Control Panel to display the point names as they are
configured. Please refer to “Printing a SCADA Address List” on page 8-46.
For further information on Modbus, please refer to your Modbus master device
manual, or obtain Modicon’s
Modbus Protocol Reference Guide
, document PI-
MBUS-300.
Read Coil Status (Function Code 01, 0X References)
Channel
Address
Value
Hold Readings
00001
0: Readings not held
1:Readings held
Reserved
00257
Reserved
Contact 1
00513
0: Contact open (inactive)
1: Contact closed (active)
Contact 2
00514
0: Contact open (inactive)
1: Contact closed (active)
Contact 3
00515
0: Contact open (inactive)
1: Contact closed (active)
Contact 4
00516
0: Contact open (inactive)
1: Contact closed (active)
Contact 5
00517
0: Contact open (inactive)
1: Contact closed (active)
Contact 6
00518
0: Contact open (inactive)
1: Contact closed (active)
Logic Detector 1
00769
0: Off (inactive)
1: On (active)
Logic Detector 2
00770
0: Off (inactive)
1: On (active)
Logic Detector 3
00771
0: Off (inactive)
1: On (active)
Logic Detector 4
00772
0: Off (inactive)
1: On (active)
Logic Detector 5
00773
0: Off (inactive)
1: On (active)
Logic Detector 6
00774
0: Off (inactive)
1: On (active)
Logic Detector 7
00775
0: Off (inactive)
1: On (active)
Logic Detector 8
00776
0: Off (inactive)
1: On (active)
Logic Detector 9
00777
0: Off (inactive)
1: On (active)
Logic Detector 10
00778
0: Off (inactive)
1: On (active)
Logic Detector 11
00779
0: Off (inactive)
1: On (active)
Logic Detector 12
00780
0: Off (inactive)
1: On (active)
Logic Detector 13
00781
0: Off (inactive)
1: On (active)
Logic Detector 14
00782
0: Off (inactive)
1: On (active)
Logic Detector 15
00783
0: Off (inactive)
1: On (active)
High/low speed recording
active
01025
0: Off (inactive)
1: On (active)
High/low speed recording
space nearly full alarm
01026
0: Off (inactive)
1: On (active)
Trend Recording Active
01281
0: Off (inactive)
1: On (active)
Summary of Contents for tesla lite
Page 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 78: ......
Page 126: ......
Page 134: ......
Page 214: ......
Page 234: ......
Page 280: ......
Page 284: ......
Page 288: ......