7 Acceptance/Protection Function Test Guide
7-12
L-PRO 4000 User Manual
D02706R02.30
60 Loss of
Potential (LOP)
Test
Settings
• Voltage = 0.75 per unit phase-to-neutral fixed (In this case minimum op-
erate = 0.75 per unit = 0.75 * V
nominal
= 0.75 * 66.4 V = 49.8 V)
• I
1
Blocking = 10.0 A (positive sequence current that blocks LOP if
exceeded)
• 3
I0
Blocking = 1.0 A (zero sequence current that blocks LOP if exceeded)
Figure 7.10: Loss of Potential Logic (60)
60 Test Procedure:
1. In Relay Control Panel access relay
Metering>Logic>Protection
.
Monitor: 60 Alarm
2. Apply balanced 3-phase nominal voltages (66.4 V) to the relay terminals:
Ph A: 330, 66.4 V
0
Ph B: 331, 66.4 V
-120
Ph C: 332, 66.4 V
+120
Ph N: 333
3. Connect 3-phase current sources (0.5 A) to the relay terminals (must be
greater than 0.2 A (4% I
nominal
) to enable due to low set supervision, for
details see Figure 7.10: Loss of Potential Logic (60) on page 7-12).
Ph A: 300
–
301, 0.5 A
0
Ph B: 302
–
303, 0.5 A
-120
Ph C: 303
–
304, 0.5 A
+120
Observe: 60 Alarm = Low
4. Instantaneously reduce single-phase voltage to 48 V or less.
60 Alarm = High
Contact 2 Closed
5ms
12ms
0
17ms
50 Ipos
168
171
173
174
169
167
170
172
50 3I0
50 ILA (4% I nominal)
50 ILB (4% I nominal)
50 ILC (4% I nominal)
dVpos/dt < -3V/cycle
dVpos/dt > 3V/cycle
ABS | dIpos/dt | > 0.1A/cycle
27 VLa (0.75 pu fixed)
27 VLc (0.75 pu fixed)
27 VLb (0.75 pu fixed)
0
20ms
59 VLa (0.1 pu fixed)
59 VLc (0.1 pu fixed)
59 VLb (0.1 pu fixed)
175
176
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......