Erie water treatment SOF-WHF series Technical Manual Download Page 11

TROUBLESHOOTING 

 

 

Page 11 

 

PROBLEM 

CAUSE 

SOLUTION 

Untreated water to 
service
 

Open or defective bypass 

Close or replace bypass 

Appliance in regeneration 

Wait  until  regeneration  finishes  or  manually 
advance regeneration to end 

Excessive water usage 

Initiate regeneration manually 

Change in raw water hardness 

Verify  composition  of  incoming  untreated  water 
and adjust regeneration frequency accordingly 

Appliance fails to regenerate 

Refer to problem “Appliance fails to regenerate”  

Appliance fails to backwash properly 

Refer  to  problem  “Appliance  fails  to  backwash 
properly” 

Valve body and timer out of synchronisation 

Synchronize valve body and timer 

Decreasing filter capacity of filter media 

Clean or replace filter media 

Loss of filter media 

Refer to problem “Loss of filter media” 

Leak at riser tube 

Verify that riser tube is seated correctly and is not 
cracked     

Low levels of 
contaminant in treated 
water
 

Bypass not completely closed  

Close bypass 

Excessive service flow rate  

Lower service flow rate 
Increase filter capacity by increasing volume of filter 
media  

Leak at riser tube 

Verify that riser tube is seated correctly and is not 
cracked     

Appliance fails to 
regenerate 

Faulty electrical supply 

Verify electrical service (fuse, transformer,...) 

Defective PCB 

Replace PCB 

Defective drive motor 

Replace drive motor 

Regeneration frequency not programmed 

Program regeneration frequency 

Loss of water pressure 

Mineral or iron build-up in resin tank 

Clean  resin  bed  and  control  valve;  increase 
regeneration frequency  

Plugged lower and/or upper distributor  

Verify that distributors are free of debris  

Crushed lower and/or upper distributor 

Replace distributor(s) 

Drain line from control 
valve flows 
continuously 

Appliance in regeneration 

Wait  until  regeneration  finishes  or  manually 
advance regeneration to end 

Faulty electrical supply 

Verify electrical service (fuse, transformer,...) 

Defective drive motor 

Replace drive motor 

Defective micro switch 

Replace micro switches 

Defective PCB 

Replace PCB 

Valve body and timer out of synchronisation 

Synchronize valve body and timer 

Loss of filter media 

Lower and/or upper distributor damaged 

Replace distributor(s) 

Leak between riser tube and upper distributor 

Verify that riser tube is seated correctly and is not 
cracked     

Appliance fails to  
backwash properly
 

Low operating pressure  

Check operating pressure; must be higher than 2,0 
bar 

Insufficient water supply 

Check water supply (flow rate/dynamic pressure) 

Restricted drain line  

Verify drain line for kinks or restrictions 

Excessive build-up of impurities in pressure tank  Clean  or  replace  filter  media  and  control  valve; 

increase regeneration frequency 

Plugged backwash flow control 

Clean or replace backwash flow control 

Plugged top or bottom distributor 

Verify that top and bottom distributor are clean and 
slots are not clogged by iron or other impurities 

Filter media is completely ‘caked’ (solid block) 

Replace  filter  media  and  reduce  regeneration 
interval 

Control valve cycles 
continuously
 

Defective micro switch 

Replace micro switches 

 
 

 

 

Summary of Contents for SOF-WHF series

Page 1: ...2017 erie water treatment TM EN SOF WHF Rev2017 01 Technical Manual WHOLEHOUSE WATER FILTER Models SOF WHF...

Page 2: ...Installation Page 5 Commissioning Page 6 Electronic control panel Page 7 Maintenance Page 10 Troubleshooting Page 12 Electrical wiring diagram Page 13 Default configuration parameter settings Page 14...

Page 3: ...nly be undertaken by a competent person aware of the local codes in force All plumbing and electrical connections must be done in accordance with local codes Before setting up the appliance make sure...

Page 4: ...ironment where high ambient temperatures e g unvented boiler house or freezing temperatures can occur the appliance cannot be exposed to outdoor elements such as direct sunlight or atmospheric precipi...

Page 5: ...nlet of appliance untreated water outlet of appliance treated water 1 Install the 3 valve bypass system 2 Screw the connection kit with nuts onto the in out ports on the control valve make sure to ins...

Page 6: ...tting it into service factory bypass 1 open the outlet valve 2 slowly open the inlet valve 3 valve bypass 1 close the bypass valve 2 open the outlet valve 3 slowly open the inlet valve 6 After 2 3 min...

Page 7: ...REGENERATION MODE In regeneration mode the display shows the remaining regeneration time and the remaining cycle time The appliance can be reset to service mode at any time by pressing the scroll but...

Page 8: ...the appliance is in service mode All configuration parameters on this appliance have been pre programmed in the factory to offer optimal performance in a wide range of applications and situations Neve...

Page 9: ...on to advance to the next diagnostics parameter Available diagnostics parameters Regen X days ago number of days since last regeneration In Srvc total number of days in service of Regens number of reg...

Page 10: ...rgent technical problem when it is not necessary to supply treated water to the house application refill swimming pool irrigation WITH FACTORY BYPASS optional Picture 6 a SERVICE POSITION inlet valve...

Page 11: ...r iron build up in resin tank Clean resin bed and control valve increase regeneration frequency Plugged lower and or upper distributor Verify that distributors are free of debris Crushed lower and or...

Page 12: ...ELECTRICAL WIRING DIAGRAM Page 12 position switches power lead drive motor auxilliary contact 24 VAC max 500mA key pad...

Page 13: ...ON PARAMETER SETTINGS Page 13 Model SOF WHF Filter media 12 26 44 Units Metric Metric Metric MaintInt mths OFF OFF OFF Cycle 1 BACKWASH min 5 5 5 Cycle 2 SLOW RINSE min 0 0 0 Cycle 3 PURGE min 2 2 2 R...

Page 14: ...EXPLODED VIEW SYSTEM Page 14...

Page 15: ...9099 Label Softena mini 12L 39100 Label Softena midi 26L 39101 Label Softena maxi 44L 7 J 1018 W Tank jacket 10x18 white 12L J 1035 W Tank jacket 10x35 white 26L J 1054 W Tank jacket 10x54 white 44L 8...

Page 16: ...EXPLODED VIEW TIMER ASSEMBLY Page 16...

Page 17: ...ive motor assembly 2x 9 74267 Cable clamp 10 70312 Strain relief power lead 11 75158 Retaining ring worm drive shaft 12 72261 Drive motor 13 75156 Worm drive shaft 14 70965 Switch cam 15 568 386 Brack...

Page 18: ...EXPLODED VIEW VALVE BODY Page 18...

Page 19: ...16 568 270 4 Float valve 17 568 274 5 Injector green 18 186 118 O ring plug small 19 541 273 Plug small 20 541 254 Spring clip plug small 21 570 251 Gasket riser 22 568 334 Riser insert 23 185 214 1...

Page 20: ...SOF WHF Filter media cuft 12 26 44 Service flow rate p 1 bar m hr 3 3 6 3 4 3 2 Recomm max service flow m hr 4 1 0 1 2 1 4 Rinse water usage per regeneration ltr 132 132 132 Backwash flow rate ltr mi...

Page 21: ...Page 21...

Page 22: ...Page 22...

Page 23: ...Page 23...

Page 24: ...Manufactured Assembled by erie water treatment a division of Aquion Inc www eriewatertreatment com...

Reviews: