Hold by hand.
.10"[2.5mm]
1/2 Turn to open.
General Application
1
2
3
4
5
TIGHTEN TORQUE BY TOOL
Tighten by hand.
Turn down by hand
and tighten by tool.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
U.S.
PART NUMBER
EUROPE ARTICLE
NUMBER
ROD SIZE
DESCRIPTION
LOAD RATING
SN25
N/A
1/4"
1/4" SN Nut
500 lbs
SNM6
390005
M6
M6 SN Nut
1,650 N
SN37
N/A
3/8"
3/8" SN Nut
1,350 lbs
SNM8
390006
M8
M8 SN Nut
4,500 N
SNM10
390007
M10
M10 SN Nut
6,000N
SN50
N/A
1/2"
1/2" SN Nut
2,250 lbs
SNM12
390008
M12
M12 SN Nut
10,000 N
PART NUMBER
TORQUE
SN25
40 in-lb
SNM6(390005)
4.5 N-m
SN37
60 in-lb
SNM8(390006)
6.8 N-m
SNM10(390007)
6.8 N-m
SN50
125 in-lb
SNM12(390008)
14.1 N-m
TECHNICAL SUPPORT:
www.erico.pentair.com
CFS412_D
INSTRUCTION SHEET
1 OF 2
© 2009-2016 Pentair All Rights Reserved
SN SERIES NUT
WARNING:
Pentair products shall be installed and used only as indicated in Pentair product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.pentair.com and from your Pentair customer service representative.
PENTAIR products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2.
All instructions must be completely followed to ensure proper and safe installation and performance.
3.
Improper installation, misuse, misapplication or other failure to completely follow Pantair's instructions and warnings may cause product malfunction, property
4.
damage, serious bodily injury and/or death, and void your warranty.
Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment.
5.
All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any
6.
other purpose.
NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted.
The customer is responsible for:
a. Conformance to all governing codes.
b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified
engineer.
c. Using appropriate industry standard hardware as noted above.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
Pentair, CADDY, ERICO CADWELD, ERICO CRITEC, ERICO, ERIFLEX, and LENTON are owned by Pentair or its global affiliates. All other trademarks
are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.