The CADWELD
®
PLUS ONE SHOT Process
Fig. 4
The conductors should be clean and dry before the
connection is made. Use a propane torch to dry wire
conductors and remove remaining cleaning residue,
solvent, or water before making the CADWELD
®
connection.
Fig. 5
Next, use a wire brush to further prepare the surface
of the conductors and ground rod (CADWELD T-313
or T-314 brush).
Scrape the outer surface to remove dirt and
oxidation. You will notice a slight color change.
Fig. 6
Each CADWELD PLUS ONE SHOT contains a copper
wire at the bottom of the mold.
Place the mold onto the ground rod until the ground
rod reaches the wire stopper and cannot go any
further.
34