CURRENT SINKING MONITOR

  (Special Order Option)

PIN 6 {BLACK}

DC POWER (+)

PIN 5 {RED} 4-20 mA
4-20mA MONITOR (-)

MA

-

+

METER

ELECTRICAL CONNECTIONS

1. 

Make sure all electrical power is OFF while making electrical connections.  Improper connections can damage the QPV.

2. 

Identify the command input and analog output signal types for your specific QPV part number using the ordering information 

section on the last page of this sheet.  Confirm this against the calibration card included in the packaging.

3. 

Use the information below to wire the QPV according to your specific part number and signal type(s).

NOTE: ALL COLOR CODES RELATE TO THE FACTORY WIRED QBT-C-x POWER CORD.

VOLTAGE COMMAND VALVES

All voltage command QPV1’s use single ended voltage, meaning 

the DC Common pin (Pin 1) is the common reference for both 

power and command. Pin 1 is used as both the command signal 

common and power supply common. 

CURRENT COMMAND VALVES

All  current  command  QPV1’s  use  a  differential  current  loop 

scheme (not isolated), meaning current flow is from Pin 4 to Pin 

2 on the QPV valve. Some applications may require the common 

of the power supply that provides loop power for the 4-20mA 

command to be tied to power supply common. 

VOLTAGE MONITOR

PIN 1 {GREEN}

DC COMMON (-)

(POWER & COMMAND)

PIN 1 {GREEN}

DC COMMON (-)

PIN 2 {BLUE}

4-20MA COMMAND (-)

PIN 1 {GREEN}

DC COMMON (-)

(POWER, COMMAND,

& MONITOR)

PIN 6 {BLACK}
DC POWER (+)

PIN 6 {BLACK}
DC POWER (+)

PIN 4 {WHITE}
0-10 COMMAND (+)

PIN 4 {WHITE}
4-20 mA COMMAND (+)

PIN 5 {RED}
0-10V MONITOR (+)

v

-

+

METER

CURRENT SOURCING MONITOR

PIN 1 {GREEN}

DC COMMON (-)

PIN 5 {RED}
SIGNAL OUT

MA

-

+

METER

QPV1 Electronic Pressure Regulator

Summary of Contents for QPV1

Page 1: ...rolling these two valves The QPV1 is a relatively low flow regulator This makes the QPV1 a great choice any time low flow rates or small volumes require precise pressure control The QPV1 is often used...

Page 2: ...ssure is to be contolled to the FPP1 filter in the Outlet Port See Figure 2 4 Connect vacuum supply to the QPV Exhaust Port For the T style this is the 1 8 ID tube nipple installed in the 10 32 exhaus...

Page 3: ...ORD VOLTAGE COMMAND VALVES All voltage command QPV1 s use single ended voltage meaning the DC Common pin Pin 1 is the common reference for both power and command Pin 1 is used as both the command sign...

Page 4: ...the QPV1 7 Set the electrical command input to MAXIMUM value 8 Adjust the SPAN pot until MAXIMUM desired pressure is reached clockwise increases pressure 9 Set the electrical command input to MINIMUM...

Page 5: ...YLE UNIT DIMENSIONS QPV1 Electronic Pressure Regulator WARNING Installation and use of this product should be under the supervision and control of properly qualified personnel in order to avoid the ri...

Page 6: ...factory If Z for ZERO OFFSET 6 please leave blank 9 FULL SCALE PRESSURE TYPE N 100 Pressure Is Below Zero Requires L option 14 P 100 Pressure is Above Zero Z 100 Pressure is Zero Typical 10 FULL SCALE...

Page 7: ...edundant safety system should be installed in the system to prevent serious injury or loss of life 4 EXPLOSIVE ATMOSPHERES The QPV Series should not be used where harmful corrosive or explosive materi...

Reviews: