DESCRIPTION / IDENTIFICATION

The  QPV1  is  a  high  resolution  electronic  pressure  regulator.  It 

provides a regulated output pressure that is proportional to an 

electrical command signal input. The QPV1 is available in a wide 

range  of  calibrated  pressure  ranges  covering  vacuum  through 

150 psig (10 Bar). The QPV1 is available in either 0 -10 VDC or 

4-20 mA analog signal types. 
The QPV1 is a complete closed loop control valve consisting of two 

internal solenoid valves, a manifold, an electronic control circuit 

board,  and  a  pressure  transducer  all  contained  in  a  protective 

IP65/NEMA4 housing. Pressure is controlled by the use of two 

solenoid valves. One valve functions as inlet control and acts to 

allow  supply  media  into  the  system  to  increase  the  controlled 

pressure. The other solenoid valve acts as the exhaust and will 

decrease  the  controlled  pressure  by  venting  to  atmosphere. 

The  inlet  solenoid  valve  operates  in  a  proportional  manner  to 

the  current  supplied  by  the  QPV1’s  electronic  control  circuit. 

This variable orifice affect allows precise control of pressure at 

low  flow  conditions  and  avoids  the  digital  steps  of  traditional 

ON/OFF  solenoids.  The  ability  to  vary  the  inlet  solenoid  valve 

orifice opening in an analog fashion allows the QPV1 to control 

pressure  with  extremely  high  resolution.  The  exhaust  solenoid 

is  a  standard  ON/OFF  solenoid  and  allows  excess  media  to  be 

vented from the system. 
The  regulated  pressure  output  is  measured  by  a  pressure 

transducer  internal  to  the  QPV1.  This  pressure  transducer 

provides a feedback signal to the QPV1’s electronic control circuit. 

The control circuit compares the internal sensor feedback signal 

to the command signal input. Any difference between the two 

signals causes the appropriate solenoid valve to open, allowing 

flow in or out of the system. Accurate pressure is maintained by 

controlling these two valves. 
The QPV1 is a relatively low flow regulator. This makes the QPV1 

a great choice any time low flow rates or small volumes require 

precise  pressure  control.  The  QPV1  is  often  used  to  provide 

the  pilot  pressure  signal  to  the  dome  of  either  an  Equilibar® 

back pressure regulator or an Equilibar® vacuum regulator. The 

QPV1 can then be used to electronically control back pressure 

or vacuum pressure in line sizes from 1/8 inch through 6 inch by 

pilot operating the appropriately sized regulator. 
An electronic monitor output signal from the internal pressure 

transducer is provided. All QPV1 valves come standard with an 

analog  voltage  monitor  output.  A  4-20mA  monitor  is  available 

optionally. 
The  QPV1  series  is  available  in  two  generations.  The  older  ‘T’ 

models  used  brass  hex  fittings  in  the  side  of  the  canister  for 

the  inlet  and  outlet  port  connections.  An  improved  ‘M’  series 

uses a solid aluminum base with integral inlet and outlet ports. 

Both  models  have  identical  performance  and  are  pin-  for-pin 

compatible. Both models use the same control circuit, solenoid 

valves, electrical connector, and internal pressure sensor.

QPV1 Electronic Pressure Regulator

INSTALLATION AND MAINTENANCE INSTRUCTIONS

¹ Others available 

ELECTRICAL

SUPPLY VOLTAGE

15-24 VDC

SUPPLY CURRENT

350mA required.

COMMAND SIGNAL

VOLTAGE 0-10 VDC single ended

CURRENT 4-20 mA differential

COMMAND SIGNAL IMPEDANCE

VOLTAGE 10 KΩ

CURRENT 100 Ω

ANALOG MONITOR SIGNAL

VOLTAGE 0-10 VDC @ 10mA max

CURRENT 4 - 20 mA (Sourcing @ 12 VDC)

PNEUMATIC

PRESSURE RANGES

29.9 in. Hg (vac) - 150 psig 

760 mmHg (vac) - 10.34 BAR)

FLOW RATE

Based on the inlet valve orifice size  

(ORDERING INFORMATION)

MINIMUM VOLUME

1 cubic in (17cc)

FILTRATION RECOMMENDED

20 micron nominal (included)

LINEARITY/HYSTERESIS

<±0.15% F.S. BFSL

REPEATABILITY

<±0.02% F.S.

ACCURACY

<±0.2% F.S.

RESOLUTION

<±0.02% F.S.

WETTED PARTS¹ 

Elastomers - Fluorocarbon
Manifold - Brass, Anodized Aluminum
Valves - Nickel plate brass
P.Transducer - Silicon, Aluminum

PHYSICAL

OPERATING TEMPERATURE

32-158ºF [0-70C]

WEIGHT

1.02 lb [0.50 Kg]

PROTECTION RATING

NEMA 4 / IP65

HOUSING

Aluminum

FINISH

Black Anodized Aluminum

SPECIFICATIONS

Summary of Contents for QPV1

Page 1: ...rolling these two valves The QPV1 is a relatively low flow regulator This makes the QPV1 a great choice any time low flow rates or small volumes require precise pressure control The QPV1 is often used...

Page 2: ...ssure is to be contolled to the FPP1 filter in the Outlet Port See Figure 2 4 Connect vacuum supply to the QPV Exhaust Port For the T style this is the 1 8 ID tube nipple installed in the 10 32 exhaus...

Page 3: ...ORD VOLTAGE COMMAND VALVES All voltage command QPV1 s use single ended voltage meaning the DC Common pin Pin 1 is the common reference for both power and command Pin 1 is used as both the command sign...

Page 4: ...the QPV1 7 Set the electrical command input to MAXIMUM value 8 Adjust the SPAN pot until MAXIMUM desired pressure is reached clockwise increases pressure 9 Set the electrical command input to MINIMUM...

Page 5: ...YLE UNIT DIMENSIONS QPV1 Electronic Pressure Regulator WARNING Installation and use of this product should be under the supervision and control of properly qualified personnel in order to avoid the ri...

Page 6: ...factory If Z for ZERO OFFSET 6 please leave blank 9 FULL SCALE PRESSURE TYPE N 100 Pressure Is Below Zero Requires L option 14 P 100 Pressure is Above Zero Z 100 Pressure is Zero Typical 10 FULL SCALE...

Page 7: ...edundant safety system should be installed in the system to prevent serious injury or loss of life 4 EXPLOSIVE ATMOSPHERES The QPV Series should not be used where harmful corrosive or explosive materi...