WARNING:

 Risk of electric shock! Exercise caution when handling solar wiring. The solar 

module(s) high voltage output can cause severe shock or injury. Be careful operation when 
installing solar wiring.

 

Step 3

Grounding 

VS BN series is a common-negative controller, where all the negative terminals of PV array, battery and 
load can be grounded simultaneously or any one of them will be grounded. However, according to the 
practical application, all the negative terminals of PV array, battery and load can also be ungrounded, 
but  the  grounding  terminal  on  its  shell  must  be  grounded,  which  may  effectively  shield  the 
electromagnetic interference from the outside, and prevent some electric shock to human body due to 
the electrification of the shell. 

CAUTION: 

For common-negative system, such as motorhome, it is recommended to use a 

common-negative  controller;  but  if  in  the  common-negative  system,  some  common-positive 
equipment are used, and the positive electrode is grounded, the controller may be damaged. 

Step 4

Powered on the controller 

Closing the battery fuse will switch on the controller. Then check the status of the battery indicator (the 
controller is operating normally when the indicator is lit in green). Close the fuse and circuit breaker of 
the load and PV array. Then the system will be operating in the preprogrammed mode. 

CAUTION:

 If the controller is not operating properly or the battery indicator on the controller 

shows an abnormality, please refer to 5

.2 “Troubleshooting”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for ViewStar Series

Page 1: ...ViewStar series Solar Charge Controller User Manual Model VS4524BN...

Page 2: ...inside the controller DO NOT disassemble or attempt to repair the controller Mount the controller indoors Avoid exposure the components and do not allow water to enter the controller Install the contr...

Page 3: ...ation Notes 3 2 2 Installation and Wiring 3 3 HMI Interface 6 3 1 Button 6 3 2 Indicator 7 3 3 Operation Interface 7 4 Accessories optional 18 5 Protections Troubleshooting and Maintenance 20 5 1 Prot...

Page 4: ...eatures 12 24VDC automatically identifying system voltage 3 Stage intelligent PWM charging Bulk Boost Equalize Float Support 4 charging options Sealed Gel Flooded and user Lithium battery self activat...

Page 5: ...Mounting Hole 4mm Charging LED indicator Load Terminals LCD Battery Terminals Buttons PV Terminals The controller is charging and discharging at the local temperature sensor when the remote temperatur...

Page 6: ...onnections and use cable clamps to secure cables and prevent them from swaying in mobile applications Gel Sealed or Flooded batteries are recommended other kinds please refer to the battery manufactur...

Page 7: ...y in accordance with Figure 2 2 Schematic Wiring Diagram and disconnect the system in the reverse order CAUTION While wiring the controller do not close the circuit breaker or fuse and make sure that...

Page 8: ...from the outside and prevent some electric shock to human body due to the electrification of the shell CAUTION For common negative system such as motorhome it is recommended to use a common negative c...

Page 9: ...6 3 HMI Interface 3 1 Button Button Note Menu Cursor left button Cursor up Number add button Cursor down Number reduce button Enter cursor right button...

Page 10: ...er controller is initialized the monitoring interface will update automatically Press button to main menu 1 interface which displays the following contents Indicator Color Status Instruction Green On...

Page 11: ...s the following contents 3 Monitoring Display Solar array voltage and current Battery voltage and current Battery temperature and battery SOC Load voltage and current Real time clock and imaging syste...

Page 12: ...D LVD Icons indicating battery charging are dynamic effects System status System Status System Status PV Connect BATT LVD Measure Err Normal MOS C Short Rated V Err Disconnect UVW MOS I Short OVD MOS...

Page 13: ...isplay Date set ID and LCD backlight time set TempUnit set Device parameters Parameter Detail ID Range 1 200 Clock Format dd mm yyyy hh mm ss Password Default 000000 Clear Energy Press and hold both a...

Page 14: ...11 5 Parameter Set The interface will prompt only when the SOC is selected in the Batt Mng Mode Display Temperature compensation coefficient Control parameters interface 1 2 3 4 5...

Page 15: ...1V 11 1V 9 17V Discharging Limit Voltage 10 6V 10 6V 10 6V 9 17V Equalize Duration 120 min 120 min 0 180 min Boost Duration 120 min 120 min 120 min 10 180 min Note 1 When the battery type is sealed g...

Page 16: ...13 6 Load Set Display Manual Light On Off Light On Timer Time Threshold voltage value Night Time Threshold Voltage 6V 12V 12V 24V Day Time Threshold Voltage 5V 12V 10V 24V...

Page 17: ...N OFF of the load via the button or remote commands 2 Light ON OFF 3 Light ON Timer 4 Time Control the load ON OFF time through setting the real time clock NOTE In the mode of Light ON OFF and Light O...

Page 18: ...ttery Type Note Sealed default Constant value GEL Constant value Flooded Constant value User Defined by user The parameters refer to the Lead acid battery parameters Parameter Set 8 Test Mode Press or...

Page 19: ...16 9 Password 10 Batt Mng Mode SOC parameters Precent of charging 100 constant value Precent of discharging 10 80 Low SOC reconnect is higher Low SOC disconnect than 5...

Page 20: ...17 11 Factory Reset 12 Reboot Device...

Page 21: ...e standard length of the cable is 3m length can be customized Super Parameter Programmer SPP 02 SPP 02 can realize one key setting parameter operation Remote Meter MT50 MT50 can display various operat...

Page 22: ...19 WARNING Do not use the standard twisted net cable to connect the device and PC net interface or the permanent damage will occur...

Page 23: ...lly it needs to be cleared by pressing the Load button restarting the controller Load Short Circuit Fully protected against load wiring short circuit 2 times rated discharge current After five automat...

Page 24: ...ng interface shows Over Temp Fault indicator flashing Operating Ambient Temperature local temperature sensor Or Battery Temperature remote temperature sensor Over Temperature When operating ambient te...

Page 25: ...t the air flow and ventilation around the controller is not blocked Clear all dirt or fragments on the heat sink Check all the naked wires to make sure insulation is not damaged for serious solarizati...

Page 26: ...9V Discharge circuit voltage drop 0 17V Battery type Sealed Gel Flooded User Temperature compensate coefficient 3mV 2V 25 Self consumption 15mA 12V 13mA 24V RS485 interface RS485 RJ45 Remote temperatu...

Page 27: ...24 Annex Mechanical Dimension Diagram VS4524BN Unit mm Any changes without prior notice Version number 1 0...

Page 28: ...BEIJING EPSOLAR TECHNOLOGY CO LTD Tel 86 10 82894112 82894962 Fax 86 10 82894882 E mail info epsolarpv com Website http www epsolarpv com http www epever com...

Reviews: