Edge Power Solutions
IPS-32-1 / IPS-32-2 / IPS-16 Installation Manual Revision 4.0 0322021
2.4
Attach Rack Mounting Brackets
•
Attach mounting brackets to each side of chassis with provided screws.
•
Mount PDU into a properly secured wall mount, 2 post or 4 post rack.
•
For wall mounting turn mounting brackets 90 degrees so that the mounting ear is flush with the bottom of the chassis.
o
Units should be mounted in a manner that allows for proper air intake and venting. Do not block
the side or top vent openings. When mounting in an enclosure or cabinet, the enclosure or cabinet
should have a means of ventilation in the form of side vents, open or perforated doors and or
mechanical ventilation methods. Allow at minimum 3” of clearance on each side of the unit and
1.75”(1RU) of clearance from the top of the unit.
2.5
Chassis Grounding
•
Attach properly sized ground wire as required and secure to an approved earth ground prior to making any other
connections to this device.