EpiSensor ZHM-20 User Manual Download Page 7

 

Configuration 

Scanning 

The ZHM-2x node scans for devices at Baud Rate 2400 starting at address 1 and proceeding to address 250. If 
none are found, it tries all addresses again at Baud 9600 and finally Baud 300. The process restarts and 
continues until a slave device is found. 

Preset Settings 

The ZHM-21 can be pre-configured through the Gateway if either the Baud or Address of the M-Bus device are 
known. If one parameter is provided, the other will be scanned - so if a Baud Rate is provided, the 250 addresses 
will be scanned at that baud rate only, or if the address is provided it will be scanned across baud rates 2400, 
9600 and 300. When both are provided, no scanning is done. 

Valid Baud Rates 

When preconfiguring the settings on the ZHM-21, the following Baud Rates can be configured; 300, 600, 1200, 
2400, 4800 and 9600. Of these, only 300, 2400 and 9600 are listed as recommended. 

PARITY is always EVEN and STOP BITS are always 1 for M-Bus communication. 

Connection 

The connection to the M-Bus slave is done using a 2-core cable. T

he bus interfaces of the slaves are polarity 

independent: that is, the two bus lines can be interchanged without affecting the operation of the slaves. 
Besides protection aspects, this also results in simplified installation of the bus system. 

Reading Data 

The ZHM requests data from the Slave device using the M-Bus REQ_UD2 (Request for Class 2 Data). When the 
RSP_UD (Data Transfer from Slave to Master after Request) has been received is it parsed by the ZHM which 
then maps particular M-Bus “Value Information Fields” to EpiSensor Sensor IDs. It also converts from value 
specific data types to EpiSensor data types.  

The mapping is as follows; 

M-Bus VIF 

Description 

Sensor ID  Description 

E000 0nnn 

Energy, 10(nnn-3) Wh, 0.001Wh to 10000Wh 

370 

Energy (KWH) 

E010 1nnn 

Power, 10(nnn-3) W, 0.001W to 10000W 

376 

Power (W) 

E011 1nnn 

Volume Flow, 10(nnn-6) m

3

/h, 0.001l/h to 

10000l/h 

377 

Volume Flow (Litres per Hour) 

E101 10nn 

Flow Temperature, 10(nn-3)

o

C, 0.001

o

C to 1

o

371 

Heat Celsius Out (C) 

E101 11nn 

Return Temperature, 10(nn-3) 

o

C, 0.001

o

C to 1

o

C  372 

Heat Celsius In (C) 

 
 

 

 

Page 7

 of 18 

 

Summary of Contents for ZHM-20

Page 1: ...User Guide Wireless M Bus Interface Applies to ZHM 20 ZHM 21 EPI 085 00 EpiSensor...

Page 2: ...ning 7 Preset Settings 7 Valid Baud Rates 7 Connection 7 Reading Data 7 Valve Control 8 User Interface 9 Status LED 10 Alt LED 11 Mode Button 11 Install Mode 11 Electrical Installation 12 Mechanical 1...

Page 3: ...Sensors 16 Ordering Information 17 Troubleshooting Support 17 Warranty 18 Glossary 18 Page 3 of 18...

Page 4: ...d be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by EpiSensor for any consequences arising out of the use of this material A qualified person is...

Page 5: ...fundamental installation requirements may lead to personal injury as well as damage to electrical equipment or other property Before performing Dielectric Hi Pot or Megger testing on any equipment in...

Page 6: ...M Bus wired communications standard The ZHM 21 also includes a relay output that can control a valve allowing remote shut off via the API on the EpiSensor Gateway The ZHM reports report data through...

Page 7: ...on Connection The connection to the M Bus slave is done using a 2 core cable T he bus interfaces of the slaves are polarity independent that is the two bus lines can be interchanged without affecting...

Page 8: ...communications terminals and polarity are shown on the following diagram Valve Control This section of the document has information on the switching capability of the ZHM 21 The relay on the ZHM 21 c...

Page 9: ...l information on the relays like rated voltages currents and type please check the ZHM datasheet User Interface There are two LED s and one button on the front panel of the ZHM product range that are...

Page 10: ...table below lists all possible LED flash sequences and their meaning Flash Sequence Description Diagram Heartbeat The node is operating correctly and has successfully joined a wireless network Inverse...

Page 11: ...pulse speed indicating the wireless signal strength of the reply Automatically expires after 5 minutes 6 Reboot the node Security keys for the wireless network the node is joined to will not be erase...

Page 12: ...HM should be connected via a switched junction box and breaker to protect the cable Also please ensure that the live connection is made on the same circuit as the neutral connection where residual cur...

Page 13: ...ed on a vertical surface spaced 122mm vertically apart The head of the screw should be less than 8 5mm in diameter and the screw thickness should be less than 4 5mm The screws should be left unscrewed...

Page 14: ...lid apply pressure to the enclosure so the gasket is compressed and tighten each screw gradually and in sequence Tamper Evident Seals Some applications particularly applications where data is used fo...

Page 15: ...uipment Safety Alert This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death Dan...

Page 16: ...io module used across the EpiSensor product range a power amplified version and non power amplified version The power output of nodes with a power amplified module can be configured with an output pow...

Page 17: ...ing Information EpiSensor products are available to order directly or via EpiSensor s distribution partners The following table lists the available ZHM options SKU Description ZHM 20 Mains powered M B...

Page 18: ...data within the EpiSensor system Node Used to describe a physical EpiSensor product Gateway The central computer that managed the EpiSensor system ZigBee IEEE 802 15 4 Wireless communications standard...

Reviews: