background image

Operating Instructions

Page 2 of 3

CDT2 Room Thermostat 

with Delay Start

20221103_CDT2-230-DS-TPI_Opsins_PK

EPH Controls Ireland

[email protected]    www.ephcontrols.com

EPH Controls UK

[email protected]    www.ephcontrols.co.uk

11. Adjusting the switching differential (Normal)

12. Adjusting the setpoint temperature

Press the        button once, Diff set will appear on the screen.
The factory default switching differential of 0.40C will appear on the screen.
Press the         and         buttons to select the desired differential from 0.2 - 1˚C.
Press the        button to return to normal operation. 

Set

Press the         or          buttons to adjust the temperature setpoint.

13. Changing the thermostat mode

14. Normal control mode (On/Off )

15. Delay start control mode 

P

1

  - Normal On/Off  mode

P

2

  - Delay Start mode (DS)

P

3

  - Time Proportional Integral Mode (TPI)

Press the ‘

Reset’

 button at the side of the thermostat. 

P

will appear on the screen. 

Use the         or          buttons to change between P

1  

to P

2

 and  P

3.

Select P

1  

for normal operation.

Select P

2  

for delay start.

Select P

3  

for TPI – If P3 is selected you can press the         button to choose 

the amount of cycles and then press the           button to choose the 
proportional bandwidth.
Press the         

‘standby’ 

button to confirm.

See section 16 for more information on TPI.

When the temperature falls below the setpoint temperature, the flame 
symbol           will appear and the thermostat will switch on.  
When the temperature rises above the setpoint temperature, the flame 
symbol           will disappear and the thermostat will switch off.

22˚C

21˚C

20˚C

19˚C

18˚C

17˚C

Temp

Time Minutes

Graph (14.1):  On / Off Control 

Setpoint Temperature

20

0

40

60

80

100

Delay start is an energy saving mode.
When the delay start function is active the flame symbol will continuously 
flash on the screen. When in this mode the activation of the thermostat is 
delayed by a variable time depending on the current temperature, setpoint 
temperature and also the fall in temperature from when the delay start has 
activated. See graph (15.1) Delay Start Control. 

The flame symbol          will continue to flash until the thermostat activates. 
When activated the thermostat will allow the heating system time to reach 
the setpoint and delay start will remain inactive until it reaches this setpoint. 

Delay start can be reactivated by: 

Lowering the setpoint below the current temperature, pressing the      

‘standby’ 

button to set the temperature, then raising the setpoint above the 

zone temperature within 6˚C of the setpoint.
The heating will be delayed as per the line on the graph. 
If the difference between the actual temperature and the setpoint is 10C the 
thermostat will delay starting for circa 40 minutes.
If the difference between the actual temperature and the setpoint is 30C the 
thermostat will delay starting for circa 24 minutes.
If the difference is 60C or more, the heating will be switched on immediately.
The time delay will change if the temperature drops from the original 
calculation.
To deactivate Delay Start, see section 13.

10. High and Low temperature limitation

OFF

Set

An upper and lower temperature limit may be chosen.
Press and hold the       and       buttons for 10 seconds.
“Limit OFF” will appear on the screen.
Press the         button to select “Limit ON” mode.
Press the       button to confirm you wish to adjust the high limit temperature.
Press the         and         buttons to select the high limit temperature.
Press the       button to select the low limit temperature mode.
Press the         and         buttons to select the low limit temperature.
Press the       button and the thermostat is ready for operation.
“Limit” will appear on the screen.

To deactivate High and Low temperature limitation.

Press and hold the       and       buttons for 10 seconds.
“Limit ON” will appear on the screen.
Press the         button to deactivate this function.
“Limit OFF” will appear on the screen.
Press the       button and the thermostat is ready for operation.

Set

Set

Set

Set

Set

48.0

42.0

36.0

30.0

24.0

18.0

12.0

6.0

0.0

0

1

2

3

4

5

6

Temperature below thermostat setting °C

Time dela

y af

ter D

ela

y S

tar

t ac

tiv

at

ed in minut

es

Graph (15.1):  Delay Start Control 

Reviews: