IMPORTANT
1000W/m2.)
2.3 Wire size
The wiring and installation methods must conform to the national and local electrical code requirements.
PV wire size
The PV array's output current varies with size, connection method, and sunlight angle. Its ISC (short
circuit current) can calculate the minimum wire size. Please refer to the ISC value in the PV module's
specifications. When the PV modules are connected in series, the total ISC equals any PV module's ISC.
When the PV modules are connected in parallel, the total ISC equals the sum of all the PV module's ISC.
The PV array's ISC must not exceed the controller's maximum PV input current. For max. PV input
current and max. PV wire size, please refer to the table below:
Model
Max. PV input current
Max. PV wire size
Tracer5415AN
Tracer5420AN
50A
16mm
2
/6AWG
Tracer6210AN
Tracer6415AN
Tracer6420AN
60A
16mm
2
/6AWG
Tracer8415AN
Tracer8420AN
80A
25mm
2
/4AWG
Tracer10415AN
Tracer10420AN
100A
35mm
2
/2AWG
CAUTION
The total voltage must not exceed the max when the PV modules are connected in
series. PV open circuit voltage (Tracer**10AN)/138V
(Tracer**15AN)/180V(Tracer**20AN)at 25 environment temperature.
Battery wire size
The battery wire size must conform to the rated current. The reference size is as below:
Model
Rated charging current
Battery wire size
Tracer5415AN
Tracer5420AN
50A
16mm
2
/6AWG
Tracer6210AN
Tracer6415AN
Tracer6420AN
60A
16mm
2
/6AWG
Tracer8415AN
Tracer8420AN
80A
25mm
2
/4AWG
Tracer10415AN
Tracer10420AN
100A
35mm
2
/2AWG
Summary of Contents for Tracer10415AN
Page 2: ......
Page 4: ......
Page 31: ...27 Appendix 1 Dimensions Unit mm Tracer5415 5420AN...
Page 32: ...28 Tracer6210AN...
Page 33: ...29 Tracer6415 6420AN...
Page 34: ...30 Tracer8415 8420AN...
Page 35: ...31 Tracer10415 10420AN Any changes without prior notice Version number V3 4...