22
7. Protection
1)
Input reverse polarity protection
The electronic circuit works to protect the inverter from damage during input
reverse polarity. After correcting the connection, the inverter will work
properly.
2
)
Input overvoltage protection
Input overvoltage protection (
“Ui” is DC input voltage)
Models
Protection
Default User-defined
Phenomenon
IP***-1*-Plus
16V
<
Ui
<
16.2V
16V
15.5
~
16.2V The output is OFF
after 5s
Blue indicator fast
flashing
Buzzer sounds
LCD display
IP***-2*-Plus
32V
<
Ui
<
32.2V
32V
31
~
32.2V
IP***-4*-Plus
64V
<
Ui
<
64.4V
64V
62
~
64.4V
IP***-1*-Plus
Ui≥16.2V
★
—
—
The output is OFF
immediately
Blue indicator fast
flashing
Buzzer sounds
LCD display
IP***-2*-Plus
Ui≥32.2V
★
—
—
IP***-4*-Plus
Ui≥64.4V
★
—
—
★
WARNING: The inverter has the input over voltage protection,
but the surge voltage less than 20V for 12V system, 40V for 24V
system, 80V for 48V system)
Input overvoltage recover protection (
“Ui” is DC input voltage)
Models
Recover
Default
User-defined
Phenomenon
IP***-1*-Plus
Ui≤14.5V
14.5V
14
~
15V
The blue indicator
on solid
Output is ON
IP***-2*-Plus
Ui≤29V
29V
28
~
30V
IP***-4*-Plus
Ui≤58V
58V
56
~
60V
3
)
Low voltage protection
Low voltage protection (
“Ui”is DC input voltage)
Models
Protection
Default User-defined
Phenomenon
IP***-1*-Plus
10.5V
<
Ui
<
10.8V
10.8V
10.5
~
11.3V The output is OFF
after 5s
The blue indicator
slowly flashing
Buzzer sounds
IP***-2*-Plus
21V
<
Ui
<
21.6V
21.6V
21
~
22.6V
IP***-4*-Plus
42V
<
Ui
<
43.2V
43.2V
42
~
45.2V