5.3.4 Parameters user define
Display
Parameters
Default
User define
Output voltage class
①
220VAC
220VAC/230VAC/240VAC
110VAC
100VAC/110VAC/120VAC
Output frequency class
①
50Hz
50Hz/60Hz
LCD backlight time
30s
30s/ 60s/100s(ON solid)
Power Saving Enable
OFF
ON/OFF
Power Saving In
20VA
20VA ~ (20%*rated power)
Power Saving Out
40VA
(20VA + PSI) ~ (50%*rated power)
Baud Rate Select
②
115200
9600/115200
Low voltage disconnect
voltage
③
12V: 10.8V
24V: 21.6V
48V: 43.2V
12V: 10.5V~14.2V; step size 0.1V
24V: 21V-30.2V; step size 0.1V
48V: 42V-62.4V; step size 0.1V
Low voltage reconnect
voltage
③
12V: 12.5V
24V: 25V
48V: 50V
12V: 11.5V~15.2V; step size 0.1V
24V: 22V-31.2V; step size 0.1V
48V: 43V-63.4V; step size 0.1V
Over voltage reconnect
voltage
③
12V: 14.5V
24V: 29V
48V: 58V
12V: 11.5V~15.2V; step size 0.1V
24V: 22V-31.2V; step size 0.1V
48V: 43V-63.4V; step size 0.1V