installation in-wall
50mm min.
70mm max.
110mm
55mm
WALL CUT OUT
EMW803A
SENSOR BRACKET
IMAGE 04
IMAGE 05
IMAGE 02
INSTALLING THE SOLENOID
The solenoid valve is installed into the water supply
line before the outlet spout. Quick-connect fittings
or unions should be fitted on either end of the
solenoid, and an isolation valve and a mesh strainer
should be fitted before the solenoid, for ease of
servicing and trouble-free solenoid operation.
SEE IMAGE 01
Note: Ensure the solenoid is installed in the correct
direction. The arrow on the solenoid body must align
with the direction of water flow.
SEE IMAGE 02
The black casing for solenoid can be turned around
to suit the direction of wiring connection, by first
loosening the hex nut on top.
SEE IMAGE 03
INSTALLING THE SENSOR BRACKET
Once the position of the sensor is determined,
fix the sensor mounting bracket inside wall. Take
note of the maximum and minimum depths for the
sensor.
SEE IMAGE 04
Minimum wall depth 50mm, maximum 70mm.
Wall Cut Out Dimensions
Before the wall is sheeted or finished, allow for a
cut out in the finished wall surface, of 110mm wide
x 55mm high rectangular hole, and at least 50mm
deep to allow for installation of bracket. Sensor
cable to come through the top, bottom, or back of
sensor inside wall.
SEE IMAGE 05