product description

The Custodian

®

 Smart Board directly controls and monitors the delivery of water in secure or 

controlled bathroom environments. The compact and easy to install unit houses the Electronic 
Thermostatic Mixing Valve (eTMV), eTMV Control Hub (WMSSB-000 model), with Basin/
Shower solenoids and service isolation/strainers and check valves (WMSSB-001 model).

Features:

•  Rapid installation of pre-assembled and tested plumbing assembly

•  Integrated control of water flow and thermostatic temperature control of shower and basin

•  Toilet full and half flush connections

•  Plug-and-play cable connectors for all fixtures and Smartflow Water Management System

The eTMV Control Hub is designed to be a generic smart hardware platform which is used for 
multiple applications such as shower and basin tapware and toilet flush valves in domestic / 
public / aged care / hospital / detention plumbing systems depending on the configuration. 
The hub has a RS485 network interface to connect to either a local or cloud based water 
management system. The network connection allows the hub to be configured, monitored 
and updated remotely. 

When activated, water is delivered to the shower or basin outlet at the selected thermostatic 
temperature and for a pre-configured runtime. This is achieved by using an Electronic 
Thermostatic Mixing Valve (eTMV) for temperature control and a solenoid for flow control. The 
available activation methods depend on the configured mode.

Summary of Contents for Custodian WMSSB-000

Page 1: ...nce Instructions The Custodian Smart Board Call 1300 369 273 www enware com au Enware Australia Pty Limited 9 Endeavour Rd Caringbah NSW 2229 Australia Ph 02 8536 4000 info enware com au WMSSB 000 wit...

Page 2: ...all fixtures and Smartflow Water Management System The eTMV Control Hub is designed to be a generic smart hardware platform which is used for multiple applications such as shower and basin tapware and...

Page 3: ...41 SOLENOID MIXED TO SHOWER SOLENOID MIXED TO BASIN HOT INLET ISOLATION STRAINER CHECK VALVE COLD INLET ISOLATION STRAINER CHECK VALVE ETMV CONTROL HUB ELECTRONIC TMV TRANSFORMER 12V DC All measureme...

Page 4: ...d Cold Supplies Must be less than 100 kPa Static Inlet Pressure For Testing Purposes System Commissioning Max 1600kPa Minimum Flow Rate 2 Litres min Maximum Flow Rate 32 Litres min 300 kPa pressure lo...

Page 5: ...pe of Port Smartflow Communication Port Number of Connectors 1 Serial Port Protocol RS485 Serial Port Speed 38400 baud Piezo Button Ports Number of Inputs 4 Type of Inputs Piezo Buttons Number of Conn...

Page 6: ...SEE IMAGE 01 Enware products are to be installed in accordance with the Plumbing Code of Australia PCA and AS NZS3500 Installations not complying with PCA and AS NZS 3500 may void the product and perf...

Page 7: ...nes are clear of any debris 3 Connect water lines to each connection SEE IMAGE 02 CONNECTION TO SHOWER CONNECTION TO BASIN COLD INLET 1 2 BSP MALE HOT INLET 1 2 BSP MALE IMAGE 02 ETMV OUTLET CONNECTIO...

Page 8: ...re should be taken with the position and orientation of the connections Align white marking on the connectors when connecting When unplugging cables hold the cable connectors themselves and do not pul...

Page 9: ...ternal 2x TLI control wheels external 1x ETMV output on Smart Board 2x shower basin solenoid outputs on Smart Board 1x flushing solenoid output external ETMV CONTROL HUB SHOWER SOLENOID BASIN SOLENOID...

Page 10: ...au operation Piezo Button Activation WC HALF FLUSH ACTIVATION WC FULL FLUSH ACTIVATION BASIN OUTLET ACTIVATION SHOWER ACTIVATION PRESS ONCE TO ACTIVATE CONTROL PANEL IMAGE 03 Lightly press the piezo b...

Page 11: ...The TLI will pulse green orange or red depending on how long the shower has been running The time between each set of pulses is configurable End Flash The TLI will flash in the last few seconds of the...

Page 12: ...e and outlet fixture To do this press the piezo button or Temperature Control Wheel on the Fascia Control Plate to activate shower or basin tap The default maximum run time per activation is 2 minutes...

Page 13: ...allowed by the applicable standard or code of practice for each state 3 Restore the cold water supply to the valve After the mixed water temperature has stabilised note the outlet temperature again e...

Page 14: ...twork Cable or by a standalone laptop connected directly to the Custodian eTMV Control Hub Manager Activation It can be enabled or disabled using the Smart Flow Software or manually by unscrewing the...

Page 15: ...ly unless the installed conditions dictate more frequent servicing is necessary Every 12 months eTMV should be inspected and tested The valve and surrounding area should be inspected for leaks or wate...

Page 16: ...alve for damage or any debris Clean or replace the combination ball valve if necessary If water does not leak through this indicates the check valve is working correctly 4 Re install Strainer Cap 5 Tu...

Page 17: ...gh Smart Flow Software the temperature control wheels TLI will start flashing red and white Note this will automatically disable after 3 minutes if left in this state 2 Within 3 minutes press a TLI bu...

Page 18: ...crews that was taken in step 2 Fit 2 screws taken in step 3 to lock the water inlet adaptors in place Re fit cover When reconnecting cables align the white marking on the connectors to ensure correct...

Page 19: ...d water temperature too hot or cold 3 Flow rate reduced or fluctu ating 4 eTMV is noisy 5 The valve will not shut down Supply water temperature too high or too low Ceramic disc in eTMV has failed Debr...

Page 20: ...hority 2 The valve manufacturer supplier requirements 3 The Australian Standards for Plumbing and Drainage YES NO YES NO YES NO If NO give details and action taken Use a separate form for each valve T...

Page 21: ...Element Not Applicable Checked Replaced max 5 year intervals Valve Replaced Yes No Other Items Replaced Inlet Temperature and Pressure Tests Set Temperature C Temperature Range Neonatal and children...

Page 22: ...r Business Name Name Contractor Name print Name Contractor Lic Cert No Phone No Name of Authorised Tester Licensed Plumber Name Signature of Authorised Tester Licensed Plumber Signature Date Owner Occ...

Page 23: ...ng product transit or transportation making a claim To make a claim under this warranty you must notify us in writing within 7 days of any alleged defect in the product coming to your attention and pr...

Page 24: ......