26
NXW REVERSIBLE CHILLER INSTALLATION MANUAL
Unit Display and Interface cont.
MUI Menu Navigation for NXW Reversible Chiller cont.
Maintenance
Y1 Input
Auto
Y2 Input
Auto
B Input
Auto
Emerg SD
Auto
Acc1 Sel
ON Comp
Lead/Lag Select OFF
Lead/Lag Time
24 hr
Low Frz Setpt
15°F
Hi Frz Setpt
33°F
Acc1 Dly
9 S
LOG_IN REQUIRED
Must login through the
“Password” Menu before
Maint menu will appear.
Maint
Password
Log-In
User: maint
Code: 5667
Password
ALARM SUMMARY
^/High Pressure
Alarm
NOTE:
This FX10 application implements an
alarm history
which is reset
only by cycling power. This history shows on the Alm-History page. Any
alarm showing 2+ events has occurred more than 2 times.
Alarm lock-outs
are reset by cycling power, by pressing the “ESC” and
Return keys simultaneously for a minimum of 15 seconds, or by
commanding the nviAlarmReset over the BAS network.
Test mode
is enabled by holding the ‘Esc’ and Down Arrow simultaneously
for a minimum of 15 seconds and releasing. Test mode times out after 30
minutes, and may also be ended by pressing ‘ESC’ and Up Arrow
simultaneously and releasing. Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cycling
the reversing valve without compressor shutdown.
Alarm
#Events
Load Flow
0
Lo Press1
0
Src Freeze1
0
Ld Freeze1
0
Src Flow
0
Hi Press1
0
Src FP1 Bad
0
Ld FP1 Bad
0
Lo Press2
0
Src Freeze2
0
Src FP2 Bad
0
Ld Freeze2
0
Ld FP2 Bad
0
Hi Press2
0
Alm-History
Alarm
#Events
Cmp1 StrtFail
0
Cmp2 StrtFail
0
LossOfChrg1
0
LossOfChrg2
0
Press right arrow key one
time from Alm_History
Menu