Enviro Sienna Indoor Gas Fireplace Owner'S Manual Download Page 17

NOTE: 

If the Sienna unit is pulled 

out of its installation, and the vent 

air intake system is disconnected 

for  any  reason,  ensure  that  the 

vent-air intake pipes are re-sealed 

with  high-temperature  sealant 

or  silicone  and  reconnected  with 

three  (3)  sheet  metal  screws 

evenly spaced.
IMPORTANT: The Sienna is to be 

vented  only  with  vertical  venting 

– no horizontal.

2ft (0.6m)

Minimum

3ft (0.9m)

Minimum

Within

10ft (3m)

Roof ridge or 

any other portion 

of a building

Figure 21: Roof Clearances.

Table 3: Vent termination clearances

Minimum Clearance 

Description

3 ft (0.9 m)

Clearance above the highest point where it passes through a roof surface, refer 

to Figure 21.

24 in (0.6 m)

Clearance above a roof ridge, any other portion of a building, or any other ob-

struction within a horizontal distance of 10 feet (3 m), refer to Figure 21.

5 ft (1.5 m)

Clearance for a vent or chimney above either the highest connected appliance 

drafthood outlet, or flue collar.

6 ft (1.83 m)

Clearance to mechanical air supply inlet.

3ft (0.9m) 

Clearance to each side of center line extended above meter/regulator assembly.

6 ft (1.83 m)

Radial clearance around service regulator vent outlet.

12 in (30 cm)

Clearance above grade, verandah, porch, deck, or balcony.

3 ft (0.9 m)

Clearance to a building opening or combustion air inlet of another appliance, 

except with the approval of the authority having jurisdiction for the following 

reduced clearances.

9 in  (0.23 m)

Exception for inputs up to and including 50,000 Btu/h (15kW)

12 in (0.3 m)

Exception for inputs exceeding 50,000 Btu/h (15kW) but not exceeding 100,000 

Btu/h (30kW)

z

eRo

 c

LeaRance

 f

iRePLace

 i

nstaLLation

:

The metal floor of the ZC solid fuel firebox can be removed to allow the installation of the insert. THE 

CLEARANCE TO COMBUSTIBLE MATERIAL UNDER THE INSERT IS ½” (13mm). YOU MUST USE THE 

LEVELING LEGS TO RAISE THE INSERT A MINIMUM OF ½” (13mm) IF THE UNIT IS TO BE INSTALLED 

ON COMBUSTIBLE MATERIAL. The sidewalls and top structure of the solid fuel firebox cannot be altered 

with  the  exception  of  removable  dampers  and  baffles.  THE  ORIGINAL  FIREPLACE  MAY  NEVER  BE 

RETURNED TO SOLID FUEL USE IN THIS CONDITION. 
IMPORTANT: If the factory-built fireplace has no gas access hole(s) provided, an access hole of 1.5 inch 

(37.5 mm) or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship 

like manner. This access hole must be plugged with non-combustible insulation after the gas supply line 

has been installed. Cutting any sheet-metal parts of the fireplace, in which the gas fireplace insert is to 

be installed, except as tested for the floor is prohibited.

Initial Installation

QUALIFIED INSTALLERS ONLY

17

Summary of Contents for Sienna Indoor Gas Fireplace

Page 1: ...fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in this manual is not followed exactly a fire or explo...

Page 2: ...ho is unfamiliar with the stove to operate it To prevent injury if the pilot or pilot and burners have gone out on their own open the glass door and wait 5 minutes to air out before attempting to re l...

Page 3: ...l Conversion 11 Initial Installation 13 Clearances to Combustibles 13 Minimum Fireplace Size 14 B Vent Model 14 Automatic Flue Gas Spill Switch B Vent Model Only 14 Direct Vent Model 15 Preparing Your...

Page 4: ...GAS FIREPLACE HEATER SIENNA BV DV NG LPG TESTED TO ANSI Z21 88a 2003 CSA 2 33a 2003 VENTED GAS FIREPLACE HEATERS CAN CGA 2 17 M91 GAS FIRED APPLIANCES FOR HIGH ALTITUDES CSA P 4 1 02 TESTING METHOD F...

Page 5: ...Surround 14 369 mm 14 365 mm From Back Sensor To Surround 17 1 16 434 mm 18 11 16 474 mm 33 x 46 840 x 1930 mm Surround with Trim From Flue To Trim 13 337 mm 13 1 16 333 mm From Back Sensor To Trim 1...

Page 6: ...rim 33 338 mm 20 5 8 523 mm 22 3 4 577 mm 22 11 16 576 mm With Trim 46 1 8 1171 mm Without Trim 46 1168 mm 21 533 mm 13 1 16 333 mm 1 3 8 36 mm 17 3 8 441 mm Shown B Vent with 33 x 46 84cm x 193 cm su...

Page 7: ...to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppliers instructions If you...

Page 8: ...blower off turn the knob COUNTER CLOCKWISE until it clicks off Figure 6 It is advisable not to operate the blower below 1 3 speed as it puts a strain on the windings of the blower and running the blo...

Page 9: ...the logs carefully as they are very fragile Gently remove all the embers and rock wool and place on a paper towel Vacuum the bottom of the firebox thoroughly Carefully clean any dust off the logs and...

Page 10: ...igure 8 Lift the bottom of the door up and remove from unit see Figure 9 CAUTION GLASS MAY SEPARATE FROM DOOR remove the complete gas and electrical tray assembly from the firebox ensuring that no wir...

Page 11: ...s is not followed exactly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency is responsible for the prope...

Page 12: ...d to pay special attention when installing the burner that the venturi adjustment rod is properly installed into the venturi adjustment piece welded to the burner venturi tube 9 Reconnect the main gas...

Page 13: ...inimum height of 43 1092 mm from the bottom of unit If installed at floor level a minimum 16 406 mm non combustible material must be installed in front of the unit If installed on a 12 305 mm wide hea...

Page 14: ...tch B Vent Model Only NOTE This heater must be properly connected to a venting system This heater is equipped with a vent safety shutoff system designed to protect against improper venting of combusti...

Page 15: ...ue before installing the stove Failure to do so may result in fumes or dirt being blown into the room and may cause a fire leading to death or serious injury 1 Remove the unit from the box and remove...

Page 16: ...ovincial State and local building codes and has been constructed of non combustible materials This appliance must not be connected to a chimney flue serving a separate solid fuel burning appliance Bef...

Page 17: ...m Clearance to a building opening or combustion air inlet of another appliance except with the approval of the authority having jurisdiction for the following reduced clearances 9 in 0 23 m Exception...

Page 18: ...to a line voltage electrical supply WARNING The electrical grounding instructions must be followed The fan kit is equipped with a three prong grounding plug for your protection against shock hazard a...

Page 19: ...r less than psi 3 5 kPa The unit must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at press...

Page 20: ...Ensure the tabs are under the brackets at the back and the holes at the front line up Secure into place with the two 2 T 20 screws at the front of the unit 4 Disconnect the two 2 blue wires at the ope...

Page 21: ...ver tighten the screw in each corner bracket in the side trims then tighten the top trim 2 Slide the two 2 attached trim pieces onto the surround panel 3 Attach the other side trim piece to the top tr...

Page 22: ...re 32 First Stage Log Set Installation Figure 33 Second Stage Log Set Installation Figure 32 The left log and the right log both have two 2 holes in them that will rest over their corresponding two 2...

Page 23: ...his ember material as this could create an unsafe condition The pieces should be lightly placed so they don t block any of the burner ports DO NOT allow any of the embers to rest against the pilot ass...

Page 24: ...as door Never operate the fireplace with the glass door removed When lighting the fireplace for the first time since the log set and embers have been installed replaced watch for ignition at ALL the b...

Page 25: ...n the firebox If the side and front panels must be removed continue with steps 5 6 7 and 8 5 Lift the front panel located on the firebox bottom from one end and remove the panel at an angle through th...

Page 26: ...replace thermocouple Air in gas line pilot dies while knob is depressed Bleed line Check gas line pressure Contact dealer Burners will not remain lit Problem with thermopile circuit Check gas line pre...

Page 27: ...lot Tube with End Furrels 1 piece 30 043 11 Blank Orifice 73 50 343 Embers 50 491 On Off Remote Control Kit 50 559 Programmable Wall Mounted Remote Control 50 583 12 Dual Bulb Door Gasket 10 feet 50 6...

Page 28: ...Parts Diagram Components SIENNA Components October 2004 19 18 20 12 21 2 16 22 17 23 24 28...

Page 29: ...29 Parts Diagram Burner SIENNA Burner October 2004 10 7 6 8 3 15 13 1 5 11 4 14 9...

Page 30: ...e Cottage Trim Kit Pewter 50 549 1A The Cottage Trim Kit Antique Copper 50 550 1A The Cottage Trim Kit Painted Black 50 694 2A Cape Cod Doors 50 1097 3A Unit Panel Keystone 50 1108 4A Cottage 50 1109...

Page 31: ...31 Parts Diagram Options SIENNA Options October 2004 1A 4A 7A 5A 3A 2A 6A...

Page 32: ...ust be provided by you or the dealer including serial number Exclusions An expanded list of exclusions is available at www enviro com help warranty html This warranty does not cover Damage as a result...

Page 33: ..._____________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy DIRECT V...

Reviews: