Replacement instructions
The primary purpose of the low limit cutout is to prevent
the coil from freezing. Therefore, before mounting the
control, you need to consider all possible factors that
help protect the coil from freezing. It is important that
the cutout capillary not be cut, kinked or pinched in
mounting to unit elements. Also, ensure tubing clamps
and wells are of compatible material with the control
sensing element to prevent corrosion.
a. Disconnect the main power on the unit.
b. Locate the two inner mounting holes between
control enclosure and coil.
c. Use two supplied screws to mount the low
temperature cutout in place.
d. Work your way back up to the bellows, stringing
the sensing element throughout the drain pan,
e. Position the sensing element horizontally across
the face of the coil, and secure the sensing element
with mount tape and wire tie. (See Figure 14.)
f. Wire the NC relay using the .250 quick connectors.
g. Once all of the connections are made, reconnect
the main power of the unit.
Figure 14
TABLE 5: UNIT WEIGHT DATA (LBS./KG)
COMPONENT
UNIT SIZE
02
03
04
06
08
09
10
12
HLF BASE UNIT
22 [10]
25 [12]
33 [15]
43 [20]
53 [24]
60 [27]
74 [34]
83 [38]
HLP BASE UNIT
24 [11]
28 [13]
36 [16]
47 [21]
58 [26]
65 [30]
81 [37]
91 [41]
HLE BASE UNIT
56 [25]
63 [29]
75 [34]
92 [42]
108 [49]
118 [54]
141 [64]
158 [72]
COIL
ROWS
1 ROW - DRY
6 [3]
7 [3]
8 [4]
10 [4]
11 [5]
13 [6]
15 [7]
17 [8]
1 ROW - WET
8 [4]
9 [4]
10 [4]
12 [5]
13 [6]
15 [7]
17 [8]
19 [9]
2 ROW - DRY
7 [3]
8 [4]
10 [4]
12 [5]
14 [6]
16 [7]
19 [9]
22 [10]
2 ROW - WET
9 [4]
10 [5]
12 [5]
14 [6]
17 [8]
19 [8]
23 [10]
27 [12]
3 ROW - DRY
8 [4]
10 [4]
12 [5]
14 [6]
17 [8]
19 [9]
23 [10]
26 [12]
3 ROW - WET
10 [5]
12 [5]
15 [7]
17 [8]
21 [10]
23 [10]
28 [13]
32 [14]
4 ROW - DRY
9 [4]
11 [5]
13 [6]
17 [8]
20 [9]
22 [10]
27 [12]
30 [14]
4 ROW - WET
13 [6]
15 [7]
18 [8]
22 [10]
26 [12]
28 [13]
34 [15]
38 [17]
5 ROW - DRY
11 [5]
13 [6]
15 [7]
19 [9]
23 [10]
25 [11]
30 [14]
35 [16]
5 ROW - WET
17 [8]
19 [8]
22 [10]
26 [12]
31 [14]
33 [15]
39 [18]
45 [20]
6 ROW - DRY
12 [5]
14 [6]
17 [8]
21 [10]
26 [12]
28 [13]
34 [16]
39 [18]
6 ROW - WET
19 [9]
21 [10]
25 [11]
29 [13]
36 [16]
38 [17]
45 [21]
51 [23]