29
a
Djusting
t
he
p
iLot
f
Lame
:
The pilot flow adjustment is set to maximum at the factory and should not need to be adjusted. The pilot
flame should envelope ⅜” to ½” (10 to 13mm) of the thermocouple (see Figure 36). However, should
the need arise, follow Steps 1- 2 below.
1. The adjustment screw can be reached through the front of the
unit using a 10 inch long blade head screw driver (see Figure 35
for location on valve).
2. Turn the adjustment screw clockwise to decrease or
counterclockwise to increase pilot flame.
s
witching
to
c
ontinuous
p
iLot
m
oDe
:
In cold climates, it may be required to run the pilot continuously to keep the vent termination from
freezing up. Flip the toggle switch on the bottom right of the unit to switch between intermittent and
continuous pilot.
Figure 36: Proper Pilot Flame.
Initial Installation
QUALIFIED INSTALLERS ONLY
Figure 37: Pilot Mode Toggle Switch.