MIXING VALVES

Water temperature over 125°F (52°C)

can cause severe burns instantly

resulting in severe injury or death.
Children, the elderly and the

physically or mentally disabled are at

highest risk for scald injury.
Feel water before bathing or

showering.
Temperature limiting devices such as

mixing valves must be installed

when required by codes and to

ensure safe temperatures at fixtures.

Water heated to a temperature which will satisfy clothes washing, 

dish  washing,  and  other  sanitizing  needs  can  scald  and  cause 

permanent  injury  upon  contact.  Short  repeated  heating  cycles 

caused  by  small  hot  water  uses  can  cause  temperatures  at  the 

point of use to exceed the water heater’s temperature setting by 

up to 20°F (11°C).
Some people are more likely to be permanently injured by hot water 

than others. These include the elderly, children, the infirm and the 

physically/mentally disabled. Table 4 shows the approximate time-

to-burn relationship for normal adult skin. If anyone using hot water 

provided by the water heater being installed fits into one of these 

groups or if there is a local code or state law requiring a certain 

water  temperature  at  the  point  of  use,  then  special  precautions 

must be taken.
In  addition  to  using  the  lowest  possible  temperature  setting  that 

satisfies the demand of the application a Mixing Valve should be 

installed  at  the  water  heater  or  at  the  hot  water  taps  to  further 

reduce system water temperature.
Mixing  valves  are  available  at  plumbing  supply  stores.  Consult 

a  Qualified  Installer  or  Service  Agency.  Follow  mixing  valve 

manufacturer’s instructions for installation of the valves.
In all cases, the following burn table must be used.

Table 4

Water Temperature

 °F (°C)

Time for 1st Degree Burn

(Less Severe Burns)

Time for Permanent 

Burns

2nd & 3rd Degree

(Most Severe Burns)

110 (43.3)

(normal shower temp.)

116 (46.7)

(pain threshold)

116 (46.7)

35 minutes

45 minutes

122 (50)

1 minute

5 minutes

131 (55)

5 seconds

25 seconds

140 (60)

2 seconds

5 seconds

149 (65)

1 second

2 seconds

154 (67.8)

instantaneous

1 second

(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15, 1978)

GAS PIPING

Make sure gas supplied is same type listed on model rating plate. The 

inlet gas pressure must not exceed 14 inch water column (3.5 kPa) for 

natural and propane gas (L.P.). The minimum inlet gas pressure shown 

on rating plate is that which will permit firing at rated input.

SEDIMENT TRAPS

A  sediment  trap  shall  be  installed  as  close  to  the  gas  inlet  of  the 

water heater as practical at the time of water heater installation. The 

sediment trap shall be either a tee fitting with a capped nipple in the 

bottom  outlet  or  other  device  recognized  as  an  effective  sediment 

trap.

Contaminants in the gas lines may cause improper operation of the 

gas control valve that may result in fire or explosion. Before attaching 

the gas line be sure that all gas pipe is clean on the inside. To trap 

any dirt or foreign material in the gas supply line, a sediment trap 

must be incorporated in the piping. The sediment trap must be readily 

accessible. Install in accordance with the Gas Piping section. Refer 

to the current edition of the CAN/CSA-B149.1, the Natural Gas and 

Propane Installation Code.

Use pipe joint compound or teflon tape marked as being resistant to 

the action of petroleum [Propane (L.P.)] gases. 
The water heater and its gas connection must be leak tested before 

placing the water heater in operation.
The water heater and its individual Shut-off valve shall be disconnected 

from the gas supply piping system during any pressure testing of that 

system at test pressures in excess of 1/2 pound per square inch (3.5 

kPa). It shall be isolated from the gas supply piping system by closing 

its individual manual Shut-off valve during any pressure testing of the 

gas supply piping system at test pressures equal to or less than 1/2 

pound per square inch (3.5 kPa).

Summary of Contents for 6G50100 NPDVH02

Page 1: ...N P PDVH 02 05 SERIES 130 131 ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL CALL THE TECHNICAL SUPPORT PH...

Page 2: ...e Pressure Relief Valve 22 Condensate Piping 23 High Altitude Installations 23 Filling The Water Heater 23 VENTING INSTALLATION 24 Vent Installation Considerations 24 Polypropylene Installations 25 Ve...

Page 3: ...you do not follow the safety message and how to avoid the risk of injury DANGER WARNING CAUTION CAUTION DANGER indicates an imminently hazardous situation which if not avoided will result in injury o...

Page 4: ...sing any electrical appliance connected to the hot water system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow THERE S...

Page 5: ...5 GENERAL SAFETY INFORMATION...

Page 6: ...Install water heater in accordance with the instruction manual Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Monoxide...

Page 7: ...safety Detailed installation diagrams are also found in this manual These diagrams will serve to provide the installer with a reference It is essential that all venting water piping gas piping and wir...

Page 8: ...T Table 1 ROUGH IN DIMENSIONS Units A B C D E F G H I 50G Inches 66 75 49 25 22 00 15 75 3 00 8 00 8 00 62 00 65 00 cm 169 5 125 09 55 88 40 00 7 62 20 32 20 32 157 48 165 1 75G Inches 64 71 45 64 27...

Page 9: ...ply Pressure for Natural Gas 3 50 87kPa Minimum Supply Pressure for Propane Gas 8 00 1 99kPa Minimum pressure must be maintained under both load and no load dynamic and static conditions Table 3 RECOV...

Page 10: ...CODES 50 GALLON UNIT FEATURES AND COMPONENTS 24 18 35 31 9 4 2 3 19 29 20 22 23 21 1 12 16 25 11 17 33 13 26 27 34 SEE ACCESS PANEL CAUTION 28 30 32 21 18 5 14 15 Caution Thisaccesspanelcovers a 2 NPT...

Page 11: ...stallation of Vent System and Condensate Piping for more information VACUUM RELIEF VALVE INSTALL PER LOCAL CODES 75 GALLON UNIT FEATURES AND COMPONENTS CONT 24 18 35 31 9 4 2 3 19 22 23 21 1 12 17 25...

Page 12: ...Board 12 Top Plastic Enclosure 13 Display Enclosure 14 Exhaust Elbow Assembly 15 Condensate Tubing 16 Off On Switch 17 Display Label 18 Hot Water Outlet 19 Gas Supply 20 Main Manual Gas Shutoff Valve...

Page 13: ...d to flow freely from the exhaust elbow and for obstructions in the exhaust venting and exhaust vent terminal Also verify that the vent length does not exceed the maximum allowed as shown in the Vent...

Page 14: ...er where an adequate supply of fresh air for combustion and ventilation can be obtained See Combustion Air and Ventilation on Page 15 9 Locate the water heater where the vent and intake air piping whe...

Page 15: ...proper combustion potentially resulting in fire asphyxiation serious personal injury or death Do not apply insulation to the top of the water heater as this will interfere with safe operation of the b...

Page 16: ...ngs to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan Undersized openings will cause air to be drawn into the room through the...

Page 17: ...the bottom of the enclosure The horizontal ducts shall communicate directly with the outdoors See Figure 7 Each duct opening shall have a minimum free area of 1 square inch per 2 000 Btu hr 1100 mm2...

Page 18: ...alified Installer or Service Agency Follow manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat read theTemperature Regulation section in th...

Page 19: ...er temp 116 46 7 pain threshold 116 46 7 35 minutes 45 minutes 122 50 1 minute 5 minutes 131 55 5 seconds 25 seconds 140 60 2 seconds 5 seconds 149 65 1 second 2 seconds 154 67 8 instantaneous 1 secon...

Page 20: ...essure limit of 14 W C 3 48 kPa The maximum supply pressure is measured while gas is not flowing static pressure AND while gas is flowing dynamic pressure SUPPLY GAS REGULATOR The maximum allowable ga...

Page 21: ...as pressure reducing valves check valves and back flow preventers Devices such as these cause the water system to be a closed system THERMAL EXPANSION As water is heated it expands thermal expansion...

Page 22: ...quipment of materials as meeting the requirements for Relief Valves for Hot Water Supply Systems ANSI Z21 22 CSA 4 4 and the code requirements of ASME If replaced the new T P valve must meet the requi...

Page 23: ...copper tubing iron or steel pipe for the condensate drain line Condensate drain lines should be installed in conditioned areas only Drain lines installed in areas that are subject to freezing temperat...

Page 24: ...Installation Code which requires the vent system components be certified to ULC S636 This water heater has been design certified to be vented with PVC CPVC pipe and Polypropylene pipe certified and ma...

Page 25: ...PPS PAC 2PPS LB 2PPS E90 2PPS 2PPS 2PPS BG for Exhaust 2PPS E90 2PPS BG for Intake Direct Vent only 3 3PPS AD PPS PAC 3PPS LB 3PPS E90 3PPS 3PPS 3PPS BG for Exhaust 3PPS E90 3PPS BG for Intake Direct...

Page 26: ...TERMINATION VENT PIPE TERMINATION The first step is to determine where the vent pipe will terminate See Figures 12 Figure 13A and Figure 14 The vent may terminate through a sidewall as shown in Figur...

Page 27: ...ow be positioned on the outside wall using the drilled holes as a centering point for the template A MASONRY SIDE WALLS Chisel an opening approximately 1 2 1 3 cm larger than the marked circle B WOODE...

Page 28: ...learance to a non mechanical air supply inlet into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between...

Page 29: ...J Clearance to a non mechanical air supply inlet into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances betw...

Page 30: ...ing 3 The air intake termination and the exhaust vent termination must penetrate the same side of roof 4 The center line of the air intake termination and the center line of the exhaust vent terminati...

Page 31: ...E HIGHEST ANTICIPATED SNOW LEVEL 12 MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL 24 MINIMUM SEPARATION EXHAUST MUST BE AT SAME LEVEL OR ABOVE INTAKE TERMINAL Figure 20 Figure 22 Figure 23 Fi...

Page 32: ...ration INSTALLATION VERTICAL ROOF TERMINATION 1 Determine best location for termination kit NOTE Roof termination is preferred since it is less susceptible to damage has reduced chances to intake cont...

Page 33: ...ioned where the vent vapors will not damage plants shrubs or air conditioning equipment Termination kit positioned so it will not be affected by wind eddy that may allow recirculation of combustion pr...

Page 34: ...re than 60 1 5 m See Figure 24 Do not use field supplied couplings to extend pipes Airflow restriction will occur and the heater pressure switch may cause intermittent operation 7 Cement heater combus...

Page 35: ...as a template 4 Screw the Cap to the Base using the supplied screws 5 Once the vent termination and pipes are secured the wall penetrations will need to be sealed from the interior using a PVC compati...

Page 36: ...36 LIGHTING AND OPERATION LABELS...

Page 37: ...ply to the water heater must be turned off and on again to reset the control system Contact your dealer or servicer if continued high limit switch operation occurs It is recommended that lower water t...

Page 38: ...stem The Combustion Blower Igniter and the 24 Volt Gas Control Valve are all energized by the control system The main components of the control system are a UIM user interface module and a CCB central...

Page 39: ...tion Blower is being energized The Blower Prover pressure switch contacts have closed The check mark icon is visual confirmation of contact closure The Igniter is being energized GAS OFF O N The 24 Vo...

Page 40: ...on that caused the Fault has not been corrected Heating Disabled The heating is disabled by the Enable Disable On Off switch in front of the unit CONTROL SYSTEM MENUS From the Desktop screen pressing...

Page 41: ...d description of control system menus Use the Up and Down Buttons to view all control system menus from the Main Menu With Temperatures menu selected highlighted in black in the Main Menu screen press...

Page 42: ...ies greatly from the Operating Set Point setting These settings are adjusted in the same way described for the Operating Set Point and Differential Adjustment Operating Set Point 140 F Differential 8...

Page 43: ...mulated time the control system has been in the heating operating state burner run time Total Cycle Count Total accumulated count of heating cycles Config CRC A number associated with the configuratio...

Page 44: ...event will replace the oldest Press the Operational Button under VIEW to view details for each Fault or Alert message stored NOTE fault history memory is cleared after 30 days 1 Blocked Air Intake A7...

Page 45: ...m Show Contact Information Yes Change Contact Name Change Contact Phone Current Contact Info 000 000 0000 Access Code UPDATE CANCEL Service Contact Information Using the UP and DOWN buttons select hig...

Page 46: ...itions will cause a reaction between this rod and the water The most common complaint associated with the anode rod is one of a rotten egg smell in the hot water The smell is a result of four factors...

Page 47: ...ciated with the anode rod is a rotten egg smell produced from the presence of hydrogen sulfide gas dissolved in the water IMPORTANT Do not remove this rod permanently as it will void any warranties A...

Page 48: ...ning And Flushing on Page 48 Replace the Temperature Pressure Relief Valve with a properly rated sized new one see Temperature Pressure Relief Valve on Page 21 for instructions on replacement DISCHARG...

Page 49: ...and terminate it to an adequate drain 5 Ensure the drain hose is secured before and during the entire flushing procedure Flushing is performed with system water pressure applied to the water heater 6...

Page 50: ...tting G Leakage from recirculation plug or pipe connection H Leakage from the plug under the cleanout cover I Leakage from the temperature probe connection Not shown in figure J Condensate from the ex...

Page 51: ...cycle to purge the water heater of all combustion gases When the post purge cycle is complete the blower is de energized and will coast to a stop 12 The control system now enters the standby mode whi...

Page 52: ...le is activated Blower Prover switch contacts confirmed closed by control system Igniter is energized 24 V Gas Valve is energized gas flows to Main Burner Is flame sensed at the Main Burner control sy...

Page 53: ...e water heater Refer to the parts list for more information or call the parts department or technical support phone number listed on the back cover of this manual for further assistance OPERATIONAL PR...

Page 54: ...ONDITIONS When the control system declares an Alert condition it will display an Alert message on the control system s LCD with a question mark The water heater will continue to operate during an Aler...

Page 55: ...CHANGE BACK ADVANCED Ignition Failure Fault occurred 2 mins ago The water heater has failed to ignite the burner Call a service professional Your Company Name Here press DOWN for more The control syst...

Page 56: ...Blocked Intake Air Switch contacts are open Loose or open wiring to the Blocked Intake Air Switch Excessive equivalent pipe length exceeded the maximum number of 90 elbows or wrong pipe size used in...

Page 57: ...ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING Figure 40 POWER VENT WIRING SCHEMATIC WIR...

Page 58: ...58 NOTES...

Page 59: ...s or lightning any misuse abuse or alteration of it any operation of it in a modified form or any attempt to repair tank leaks or parts will void this warranty SERVICE AND LABOR RESPONSIBILITY UNDER T...

Page 60: ...1 Should you have any questions please Email us at techsupport gsw wh com or Visit our websites www gsw wh com or www johnwoodwaterheaters com or Call our Technical Support line at 1 888 GSW TECH 479...

Page 61: ...es questions veuillez Envoyez un courriel techsupport gsw wh com ou Visitez nos sites Web www gsw wh com ou www johnwoodwaterheaters com ou Appelez notre ligne de support technique en composant 1 888...

Page 62: ...dant la p riode de garantie sous un usage r sidentiel normal en raison d une corrosion naturelle provenant de l eau potable le garant fournira un chauffe eau de remplacement de grandeur quivalente et...

Page 63: ...58 REMARQUES...

Page 64: ...ir 4 Noir 3 Jaune 2 Vert 1 Bleu CAVALIER Vert Connecte au boulon de br leur Jaune lectrode de d tection de flamme Bleu Bleu pissure Barre de terre Anode lectrode de d tection de flamme Condens Condens...

Page 65: ...surveillance de l entr e d air sont ouverts C blage desserr ou d couvert vers le manostat de surveillance de l entr e d air Longueur de tuyau quivalente excessive a exc d le nombre maximum de coudes...

Page 66: ...ssion de gaz de collecteur au br leur principal CHANGE BACK ADVANCED Ignition Failure Fault occurred 2 mins ago The water heater has failed to ignite the burner Call a service professional Your Compan...

Page 67: ...LLANCE ET D ALERTE CONDITIONS DE D FAILLANCE Lorsque le syst me de commande d clare une condition de d faillance il affiche un message de d faillance sur le LCD du syst me de commande avec un point d...

Page 68: ...ste des pi ces pour de plus d informations ou appeler le service de pi ces ou l assistance technique au num ro de t l phone list sur la couverture arri re de ce manuel pour une assistance suppl mentai...

Page 69: ...est activ Le syst me de commande effectue les tests de diagnostic L tat normal de tous les manostats et ECO est v rifi Manostat du ventilateur v rifi ouvert Tous les autres manostats et ECO sont v ri...

Page 70: ...e combustion Lorsque le cycle de post purge est termin le ventilateur est d sactiv et fonctionnera au d bray jusqu l arr t 12 Le syst me de commande entre maintenant en mode stand by tout en continuan...

Page 71: ...onde de temp rature Non illustr dans la figure J Condensat du raccordement de l vacuation Une fuite provenant d autres chauffe eau conduites d eau ou suintement du sol devrait galement tre v rifi Pour...

Page 72: ...rer que le tuyau de vidange est s curis avant et pendant toute la proc dure de rin age Le rin age s effectue avec la pression d eau de syst me appliqu e sur le chauffe eau 6 Ouvrir le robinet de vidan...

Page 73: ...atement l arriv e d eau froide au chauffe eau et vidanger le chauffe eau voir Vidange et rin age la page 48 Remplacer la soupape de d charge s curit thermique par une nouvelle soupape de valeur nomina...

Page 74: ...a temp rature de l eau plus chaude une plus grande consommation d eau chaude les appareils de chauffage eau chaude et les m thodes d adoucissement de l eau peuvent augmenter le taux d appauvrissement...

Page 75: ...re la corrosion Certaines conditions d eau causeront une r action entre cette tige et l eau La plainte la plus commune relativement la tige d anode est une odeur d oeuf pourri dans l eau chaude L odeu...

Page 76: ...ntact Information Yes Change Contact Name Change Contact Phone Current Contact Info 000 000 0000 Access Code UPDATE CANCEL Service Contact Information l aide des boutons vers le HAUT et vers le BAS s...

Page 77: ...ent remplacera le plus ancien Appuyer sur le bouton Op rationnel sous VIEW affichage pour afficher les d tails de chaque message de D faillance ou d Alerte sauvegard REMARQUE la m moire de l historiqu...

Page 78: ...st me de commande est en tat op rationnel de chauffage temps de marche de br leur Total Cycle Count Compte de cycles total Compte total accumul de cycles de chauffage Config CRC Config CRC Un nombre a...

Page 79: ...nsid rablement du param tre de point de consigne de fonctionnement Ces r glages sont ajust s de la m me mani re qu il l est d crit pour le Point de consigne de fonctionnement et le R glage diff rentie...

Page 80: ...utons vers le haut et vers le bas pour afficher tous les menus du syst me de commande partir du Menu principal Avec le menu Temp ratures s lectionn mis en vidence en noir dans l cran du Menu principal...

Page 81: ...age d sactiv Le chauffage est d sactiv par l interrupteur Marche Arr t en avant de l unit MENUS DU SYST ME DE COMMANDE partir de l cran de bureau le fait d appuyer sur le bouton Op rationnel directeme...

Page 82: ...est activ Les contacts du manostat du ventilateur se sont ferm s La coche est une confirmation visuelle de la fermeture des contacts L allumeur est activ GAS OFF O N Le r gulateur de gaz de 24 volts e...

Page 83: ...ts sont tous aliment s par le syst me de commande Les composants principaux du syst me de commande sont un UIM module interface utilisateur et un CCB tableau de commande principal L UIM se situe en ha...

Page 84: ...urnira galement le fonctionnement le plus conerg tique du chauffe eau L EAU CHAUDE PEUT BR LER Les chauffe eau sont destin s produire de l eau chaude L eau chauff e une temp rature qui conviendra au c...

Page 85: ...e l interrupteur MARCHE ARR T sur le tableau de INTERRUPTEUR D ACTIVATION D SACTIVATION MARCHE ARR T INSTRUCTIONS D UTILISATION 1 R gler le thermostat la position la plus basse 2 Mettre l interrupteur...

Page 86: ...ntilation bien fix s les p n trations du mur devront tre scell es de l int rieur en utilisant un produit d tanch it compatible avec le PVC 6 Tous les tuyaux de ventilation et entr es d air doivent se...

Page 87: ...u chauffe eau l ensemble terminaison de ventilation concentrique Voir Figure 29 pour un raccordement de tuyau appropri 8 Faire fonctionner pendant un cycle de chauffage pour s assurer que les tuyaux d...

Page 88: ...aison La trousse de terminaison positionn e o les vapeurs n endommageront pas les arbustes les plantes ou des quipements de climatisation La trousse de terminaison positionn e o elle ne sera pas affec...

Page 89: ...ement pour la trousse de terminaison REMARQUE Une terminaison de toit est pr f rable tant donn qu elle est moins susceptible aux d g ts qu elle a de moindres risques aux contaminants d admission et qu...

Page 90: ...E 30 5 cm 12 po AU DESSUS DU PLUS HAUT NIVEAU DE NEIGE ANTICIP TOIT NIVEAU DU SOL D GAGEMENT MINIMUM DE 30 5 cm 12 po AU DESSUS DU PLUS HAUT NIVEAU DE NEIGE ANTICIP OU DU SOL S PARATION MINIMUM DE 61...

Page 91: ...pi horizontalement Voir Figure 19 FOURREAU DE PLOMBERIE TYP LES DEUX TUYAUX MINIMUM 61 cm 24 po BOUCHE D ENTR E D AIR A B 30 5 cm 12 po AU DESSUS DU TOIT OU DU NIVEAU DE NEIGE ANTICIP BOUCHE DE VENTI...

Page 92: ...91 cm 3 pi C D gagement d une fen tre ferm e en permanence 15 cm 6 po J D gagement d une entr e d alimentation en air non m canique dans le b timent ou arriv e d air de combustion vers tout autre app...

Page 93: ...e 91 cm 3 pi C D gagement d une fen tre ferm e en permanence 30 cm 12 po J D gagement d une entr e d alimentation en air non m canique dans le b timent ou arriv e d air de combustion vers tout autre a...

Page 94: ...le gabarit A MURS LAT RAUX EN MA ONNERIE Buriner une ouverture d environ 1 3 cm 1 2 po plus large que le cercle marqu B MURS LAT RAUX EN BOIS Percer un trou pilote d environ 0 64 cm 1 4 po l ext rieur...

Page 95: ...de d terminer o le tuyau de ventilation se terminera Voir Figure 12 Figure 13A et Figure 14 La ventilation pourrait se terminer travers une paroi lat rale tel qu illustr dans la Figure 12 et Figure 14...

Page 96: ...PS 2PPS BG pour l vacuation 2PPS E90 2PPS BG pour l entr e Ventilation directe seulement 3 po 3PPS AD PPS PAC 3PPS LB 3PPS E90 3PPS 3PPS 3PPS BG pour l vacuation 3PPS E90 3PPS BG pour l entr e Ventila...

Page 97: ...s gaz de combustion La recirculation de gaz de chemin e d veloppera de la suie et du gel dans l entr e d air combustion lors des temps tr s froids Pour viter la recirculation des gaz de combustion mai...

Page 98: ...r de tuyauterie en cuivre fer ou tuyau en acier pour la conduite de vidange de condensat Les conduites de vidange des condensats doivent tre install es dans les zones climatis es seulement Des conduit...

Page 99: ...ui maintient une inspection p riodique de production des quipements de mat riels indiqu s pour r pondre aux exigences de la norme relative aux Relief Valves for Hot Water Supply Systems Soupapes de d...

Page 100: ...ITEMENT D AIR Figure 9 SYST MES D EAU FERM S Les syst mes d alimentation en eau peuvent en raison des exigences de codes ou de conditions telles que pression haute de conduite entre autres comporter d...

Page 101: ...Pa 14 po C E La pression d alimentation maximale est mesur e lorsque le gaz ne s coule pas pression statique ET lorsque le gaz s coule pression dynamique R GULATEUR DE GAZ D ALIMENTATION La pression d...

Page 102: ...ession de gaz d admission ne doit pas d passer de 3 5 kPa 14 po C E pour le gaz naturel et le gaz propane PL La pression de gaz d admission minimale figurant sur la plaque signal tique est celle qui p...

Page 103: ...nstallation des vannes Avant de changer le r glage d usine sur le thermostat lire la section R gulation de temp rature dans le pr sent manuel AVERTISSEMENT Danger de produits chimiques toxiques Ne pas...

Page 104: ...its horizontaux devront communiquer directement avec l ext rieur Voir Figure 7 Chaque ouverture de conduit aura une zone libre minimum de 1 100 mm 2 kW 1 po 2 2 000 Btu h du d bit calorifique global d...

Page 105: ...ace avec un chauffe eau des ouvertures suffisantes pour fournir de l air frais doivent tre fournies pour accommoder les exigences de tous les appareils dans la pi ce et du ventilateur d vacuation Des...

Page 106: ...NIT 75 GALLON Ne pas suivre ces instructions peut restreindre le d bit d air requis pour une combustion appropri e et ventuellement provoquer un incendie une asphyxie de graves blessures corporelles v...

Page 107: ...ntrepos s savoir garages entrep ts zones utilitaires etc Les liquides inflammables tels que essence solvants propane PL ou butane etc et autres substances telles que des adh sifs etc mettent des vapeu...

Page 108: ...e chose V rifier si le condensat peut s couler librement du coude d vacuation et si le tuyau et la bouche d vacuation d air sont libres de tout obstacle V rifier aussi que la longueur de la ventilatio...

Page 109: ...enceinte en plastique 13 Enceinte du module d affi chage 14 Ensemble coude d vacuation 15 Tube du condensat 16 Interrupteur Marche Arr t 17 tiquette d affi chage 18 Sortie d eau chaude 19 Alimentatio...

Page 110: ...27 28 34 30 32 Figure 1C UNIT 75 GALLON 14 15 33 13 ATTENTION LE HARNAIS A 120 VCA EN FONCTIONNEMENT Voir les sections Planification du r seau de tuyaux de ventilation Installation du r seau de tuyau...

Page 111: ...requise durant la fabrication de ce chauffe eau Cette bride NPT de 2 po n est pas un accessoire de nettoyage enlever la prise NPT de 2 po et utiliser cet accessoire aux fins de nettoyage pourrait ann...

Page 112: ...aturel 3 50 po 0 87 kPa Pression d alimentation minimum pour Gaz propane 8 00 po 1 99 kPa La pression minimale doit tre maintenue aussi bien vide qu en charge modes statique et dynamique TABLE 3 CAPAC...

Page 113: ...75 16 00 3 71 8 00 7 93 57 36 58 98 cm 164 4 115 9 70 5 40 6 9 4 20 3 20 1 145 7 149 8 Entr e et sortie haut 50G 3 4 po NPT 75G 1 po NPT Entr e et sortie c t 3 4 po NPT Entr e de gaz 1 2 po NPT CONNE...

Page 114: ...tion d taill s figurent galement dans ce manuel Ces sch mas serviront de r f rence pour l installateur Il est essentiel d installer l ensemble de la ventilation des conduites d eau des conduites de ga...

Page 115: ...les conduites de gaz ainsi que le robinet principal d arr t de gaz avant de v rifier l tanch it Installer un pi ge s diments conform ment la CAN CSA B149 1 Risque d incendie et d explosion AVERTISSEM...

Page 116: ...au y compris la sortie vers un drain appropri Les conduites de condensat doivent tre d pourvues de d bris et ne doivent pas permettre un retour d eau travers le boyau Les conduites de condensat doiven...

Page 117: ...u au fur et mesure que l eau commence s couler IL EST INTERDIT DE FUMER OU D AVOIR DES FLAMMES NUES PROXIMIT DU ROBINET AU MOMENT O IL EST OUVERT V rifier de couper l alimentation au chauffe eau avant...

Page 118: ...mani re d viter tout risque de blessure APPROBATIONS INSTALLATION UTILISATION ET SERVICE EN TOUTE S CURIT DANGER AVERTISSEMENT ATTENTION ATTENTION Symbole d alerte de s curit Utilis pour signaler les...

Page 119: ...ltitude 23 Remplissage du chauffe eau 23 INSTALLATION DE LA VENTILATION 24 Consid rations de l installation de ventilation 24 Installations avec Polypropyl ne 25 Terminaison du tuyau de ventilation 26...

Page 120: ...s t l phones se trouvant dans le b timent Se rendre imm diatement chez un voisin pour t l phoner au fournisseur de gaz Suivre ses instructions Dans l impossibilit de joindre le fournisseur appeler le...

Reviews: