Programming the Turn Number:
This menu is available for CT-25 adapted devices. User enter
the turn number, which is the number of how many tour the current
cable has rounded into the CT-25. Numbers can be selected
between 1-20. Greater the number of turn means greater the
sensivity.
Note:
If the voltage transformer is not used between the system
and MPR-53/53S, voltage transformer ratio is entered as 1.
Example:
If a voltage transformer which has a ratio of 34.5KV/100V
is used between the system and MPR-53/53S; Voltage transformer
ratio is entered as 345. (34500/100)
Voltage Transformer Ratio Setup
In this menu, voltage transformer ratio is set between
0000,1 - 4000,0.
NETWORK ANALYSER
MPR-53/53S
2
Press SET button for 3 sec. (trA Fo menu is displayed)
By using UP-DOWN buttons find
dE tý menu.
Press SET button (First digit blinks.)
Demand Time Setup:
In this menu,demand time is set between 1-60 minutes.
Press ESC button one by one until (SAU E SEt yES) is displayed.
Press SET button. When SAU E SEt yES is displayed, if you
press ESC button or choose no option instead of yES option
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated.
Press SET button for 3 seconds (trA Fo menu is displayed)
Press SET button (trA Fo Ctr menu is displayed)
Press SET button. (Most right digit of 5th display blinks)
Press set button, CAL CUL Atý on is displayed. (Data is entered
but is not activated yet. For activating the new data please follow
the below steps.)
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed, if you
press ESC button or choose no option instead of yES option
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated.
By using UP-DOWN buttons, find
CAL CUL Atý on menu.
By using UP-DOWN buttons, select energy calculation method.
Reactive Energy Calculation Method Setting
0
2
4
1
3
5
Description
It is the most preferred reactive power calculation
methode.
Total value of the multiplication of Vn and In values up
to 19 th harmonics. This calculation methode is mostly
preferred for network analysers.
S
V
n
.I
n
.sin(
j
n
)
n=1
¥
Reactive Energy
(Q)
Digital Energymeter
(Each phase seperately)
Mechanical Energymeter
(Vectoral summation of 3-phase)
90° rotation of
voltage vector and
multiply with current
S
2
-P
2
S
2
-P
2
Power Triangle Methode : According to this methode;
Q =
(Q : Reactive power, S : Active power, P : Apparent power)
Press SET button for 3 seconds (trA Fo menu is displayed)
By using UP-DOWN buttons,
find rES Et menu.
Press SET button.
(rESEt HL menu is displayed)
By using UP-DOWN buttons, select
which parameter you want to reset.
Press SET button. (rES Et dE / rES Et HL / rES Et E-1 / rES Et E-
2 is displayed. Data is entered but is not activated yet. For
activating the new data please follow the below steps.)
Press ESC button one by one until (SAU E SEt yES) is
displayed.
Press SET button, one of the
parameter rES Et dE / rES Et HL /
rES Et E-1 / rES Et E-2 is displayed.
Press SET button. When SAU E SEt yES is displayed, if you
press ESC button or choose no option instead of yES option
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated.
By using UP-DOWN buttons, if you want to delete the min., max.,
max. demand or energy; select yES otherwise select no option.
For erasing the values of min. and max. or energy counter,
In the measurement mode :
Monitoring and Erasing of minimum, maximum and
energy values:
In this menu, values of min.,max. or energy counters are erased.
It saves the instantaneously measured min. and max. values of
MPR-53/53S into its memory. Please kindly look at to the section
of
FUNCTIONS OF BUTTONS
for min. and max. values.
Note :
Measured electrical parameters which are saved to the
memory are not affected from the electric interruptions.
In the rESEt menu; when you quit from all menus, if you confirm
the changes,min. and max. values of all parameters or energy
counter values are erased at the same time.
Enter the blinking digit value by scrolling UP/DOWN buttons.
Switch to the other digits by using SET button, use BACK button
to go to previous digit. After you entered the last digit press SET
button, dE tý is displayed. (Data is entered but is not activated
yet. For activating the new data please follow the below steps).
NETWORK ANALYSER
MPR-53/53S
7
Three different methods exist for reactive energy calculation in
MPR-53/53S. Brief informations about these methods are explained
in below table.
Related values which must be entered in the menu are also
indicated in the table in order to select reactive power calculation
method for mechanical and digital energymeters.
PK 26 Box Connection Diagram
*Available only for MPR-53S
~
Un
TR
A B
Gnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
I
L2
I
L1
+_
L3
L2
L1
1A
- + - +
(12-48V DC)
k
l
K
L
k
l
K
L
k
l
K
L
~
Un
TR
A B
Gnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
I
L2
I
L1
+_
Max: 30 VDC
L3
L2
L1
- + - +
(12-48V DC)
1A
k
l
K
L
k
l
K
L
~
Un
TR
A B
Gnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
I
L2
I
L1
+_
Max: 30 VDC
L3
L2
L1
1A
- + - +
(12-48V DC)
k
l
K
L
k
l
K
L
~
Un
TR
A B
Gnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
I
L2
I
L1
+_
Max: 30 VDC
N
L3
L2
L1
1A
- + - +
(12-48V DC)
k
l
K
L
k
l
K
L
k
l
K
L
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
3 Phase neutral
L1
L2
L3
N
RS-485
Note: For CT-25 models:
1
2.00
120
2
1.00
60.0
3
0.66
40.0
4
0.50
30.0
5
0.40
24.0
6
0.33
20.0
7
0.28
17.1
8
0.24
15.0
9
0.22
13.3
10
0.20
12.0
11
0.18
10.9
12
0.16
10.0
13
0.15
9.23
14
0.14
8.57
15
0.13
8.00
16
0.12
7.50
17
0.11
7.05
18
0.11
6.66
19
0.10
6.31
20
0.10
6.00
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
3 Phase without neutral current input with
Aron wiring configuration
L1
L2
L3
N
RS-485
N
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
3 Phase without neutral
L1
L2
L3
N
RS-485
N
Max: 30 VDC
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
3 Phase without neutral current input with
Aron wiring configuration
L1
L2
L3
N
RS-485
N
k: When CT-25 is used, Red cable is connected to k terminal.
l: When CT-25 is used, Black cable is connected to l terminal.