Programming the Turn Number:

This menu is available for CT-25 adapted devices. User enter

the turn number, which is the number of how many tour the current

cable has rounded into the CT-25. Numbers can be selected

between 1-20. Greater the number of turn means greater the

sensivity.

Note: 

If the voltage transformer is not used between the system

and  MPR-53/53S, voltage transformer ratio is entered as ‘1’.

Example:

 If a voltage transformer which has a ratio of 34.5KV/100V

is used between the system and MPR-53/53S; Voltage transformer

ratio is entered as 345. (34500/100)

Voltage Transformer Ratio Setup

In this menu, voltage transformer ratio is set between

0000,1 - 4000,0.

NETWORK ANALYSER

MPR-53/53S

2

Press SET button for 3 sec. (trA Fo menu is displayed)

By using UP-DOWN buttons find

“dE tý” menu.

Press SET button (First digit blinks.)

Demand Time Setup:

In this menu,demand time is set between 1-60 minutes.

Press ESC button one by one until (SAU E  SEt  yES) is displayed.

Press SET button. When “SAU E  SEt  yES” is displayed, if you

press ESC button or choose “no” option instead of “yES” option

by using UP-DOWN buttons, new data will be cancelled and

previous value will be activated.

Press SET button for 3 seconds (trA Fo menu is displayed)

Press SET button (trA Fo Ctr menu is displayed)

Press SET button. (Most right digit of 5th display blinks)

Press set  button, “CAL CUL Atý on” is displayed. (Data is entered

but is not activated yet. For activating the new data please follow

the below steps.)

Press ESC button one by one until “SAU E  SEt  yES” is displayed.

Press SET button. When “SAU E  SEt  yES” is displayed, if you

press ESC button or choose “no” option instead of “yES” option

by using UP-DOWN buttons, new data will be cancelled and

previous value will be activated.

By using UP-DOWN buttons, find

“CAL CUL Atý on” menu.

By using UP-DOWN buttons, select energy calculation method.

Reactive Energy Calculation Method Setting

0

2

4

1

3

5

Description

It is the most preferred reactive power calculation

methode.

Total value of the multiplication of Vn and In values up

to 19 th harmonics. This calculation methode is mostly

preferred for network analysers.

S

V

n

.I

n

.sin(

j

n

)

n=1

¥

Reactive Energy

(Q)

Digital Energymeter

(Each phase seperately)

Mechanical Energymeter

(Vectoral summation of 3-phase)

90° rotation of

voltage vector and

multiply with current

S

2

-P

2

S

2

-P

2

Power Triangle Methode : According to this methode;

Q =

(Q : Reactive power, S : Active power, P : Apparent power)

Press SET button for 3 seconds (trA Fo menu is displayed)

By using UP-DOWN buttons,

find “rES Et” menu.

Press SET button.

(“rESEt HL” menu is displayed)

By using UP-DOWN buttons, select

which parameter you want to reset.

Press SET button. (“rES Et dE / rES Et HL / rES Et E-1 / rES Et E-

2” is displayed. Data is entered  but is not activated yet. For

activating the new data please follow the below steps.)

Press ESC button one by one until (SAU E  SEt  yES) is

displayed.

Press SET button, one of the

parameter “rES Et dE / rES Et HL /

rES Et E-1 / rES Et E-2” is displayed.

Press SET button. When “SAU E  SEt  yES” is displayed, if you

press ESC button or choose “no” option instead of “yES” option

by using UP-DOWN buttons, new data will be cancelled and

previous value will be activated.

By using UP-DOWN buttons, if you want to delete the min., max.,

max. demand or energy; select “yES” otherwise select “no” option.

For erasing the values of min. and max. or energy counter,

In the measurement mode :

Monitoring and Erasing of  minimum, maximum and

energy values:

In this menu, values of min.,max. or energy counters are erased.

It saves the instantaneously measured min. and max. values of

MPR-53/53S into its memory. Please kindly look at to the section

of 

FUNCTIONS OF BUTTONS 

for min. and max. values.

 

 

Note :

 Measured electrical parameters which are saved to the

memory  are  not  affected  from  the  electric  interruptions.

In the “rESEt” menu; when you quit from all menus, if you confirm

the changes,min. and max. values of all parameters or energy

counter values are erased at the same time.

Enter the blinking digit value by scrolling UP/DOWN buttons.

Switch to the other digits by using SET button, use BACK button

to go to previous digit. After you entered the last digit press SET

button, “dE tý” is displayed. (Data is entered but is not activated

yet. For activating the new data please follow the below steps).

NETWORK ANALYSER

MPR-53/53S

7

Three different methods exist for reactive energy calculation in

MPR-53/53S. Brief informations about these methods are explained

in below table.

Related values which must be entered in the menu are also

indicated in the table in order to select reactive power calculation

method for mechanical and digital energymeters.

PK 26 Box Connection Diagram

*Available only for MPR-53S

~

Un

TR

 A B

Gnd

IN2H

IN2L

IN1H

IN1L

PUL2H

PUL2L

PUL1H

PUL1L

I

L3

I

L2

I

L1

+_

L3

L2

L1

1A

- + - +

(12-48V DC)

k

l

K

L

k

l

K

L

k

l

K

L

~

Un

TR

 A B

Gnd

IN2H

IN2L

IN1H

IN1L

PUL2H

PUL2L

PUL1H

PUL1L

I

L3

I

L2

I

L1

+_

Max: 30 VDC

L3

L2

L1

- + - +

(12-48V DC)

1A

k

l

K

L

k

l

K

L

~

Un

TR

 A B

Gnd

IN2H

IN2L

IN1H

IN1L

PUL2H

PUL2L

PUL1H

PUL1L

I

L3

I

L2

I

L1

+_

Max: 30 VDC

L3

L2

L1

1A

- + - +

(12-48V DC)

k

l

K

L

k

l

K

L

~

Un

TR

 A B

Gnd

IN2H

IN2L

IN1H

IN1L

PUL2H

PUL2L

PUL1H

PUL1L

I

L3

I

L2

I

L1

+_

Max: 30 VDC

N

L3

L2

L1

1A

- + - +

(12-48V DC)

k

l

K

L

k

l

K

L

k

l

K

L

Auxiliary

Supply Voltage Measuring Input Current Measuring Input

3 Phase neutral

L1

L2

L3

N

RS-485

Note: For CT-25 models:

1

2.00
120

2

1.00
60.0

3

0.66
40.0

4

0.50
30.0

5

0.40
24.0

6

0.33
20.0

7

0.28

17.1

8

0.24

15.0

9

0.22
13.3

10

0.20
12.0

11

0.18
10.9

12

0.16
10.0

13

0.15
9.23

14

0.14

8.57

15

0.13
8.00

16

0.12
7.50

17

0.11
7.05

18

0.11
6.66

19

0.10
6.31

20

0.10
6.00

Auxiliary

Supply Voltage Measuring Input Current Measuring Input

3 Phase without neutral current input  with

Aron wiring configuration

L1

L2

L3

N

RS-485

N

Auxiliary

Supply Voltage Measuring Input Current Measuring Input

3 Phase without neutral

L1

L2

L3

N

RS-485

N

Max: 30 VDC

Auxiliary

Supply Voltage Measuring Input Current Measuring Input

3 Phase without neutral current input  with

Aron wiring configuration

L1

L2

L3

N

RS-485

N

k: When CT-25 is used, Red cable is connected to k terminal.

l: When CT-25 is used, Black cable is connected to l terminal.

Reviews: