One of the common faults faced in industrial plants is over-heating and burning of

3 phase motors due to the phase failure. “Thermic-magnetic device” which is an

essential element in motor protection is generally too slow due to both its electro-

mechanical structure and the use of high current setting range to assure demarrage

without tripping. Being designed to eliminate the above disadvantages, MKC-01

and MKC-03 Phase Failure Devices react within 0.2 seconds (fixed) against the

following faults and take the motor out of service.

PHASE FAILURE PROTECTION DEVICES

MKC-01, MKS-01, MKC-03, MKS-03, MKC-04

Connection Diagram

A4908 / Rev.4

Function Diagram

2. Phase Sequence (MKC-03, MKS-03, MKC-04)

When the phase sequence is correct (L1, L2, L3 in clockwise direction) the output

relay is activated; however, if the sequence is changed by any reason, the output

relay switches OFF immediately.

The voltage asymmetry causes the rise in motor temperature and a reduction of

the rated motor power.

1. Voltage Unbalance (Not Adjustable)

MKC-01 and MKC-03 have neutral connection.

Unbalanced voltage for Phase-Neutral (fixed). When the value exceeds the 40% for

MKC-03 and MKC-04 or 20% for MKC-01 and MKS-01 output relay switches-off the

motor.

    Unbalanced voltage may occured when;

    The mains are loaded with unbalanced distribution,

    One of the 3-phase of motor has lost. In this case, some amount of voltage which

produced by other phases will be inducted on the lost phase. Amount of this value

depends on both the motor type and amount of load.

   Output relay is activated when a phase has lost or an unbalanced phase-neutral

value, which is occured with any reason, is smaller than the Asymetrical value which

is defined for the device. If this unbalanced voltage exceeds the adjusted Asymetrical

value, output will release itself and motor will be Switched-off.

    In Applications; a proper device must be used regarding to the inducted voltage

value in two-phase which are remained after the other one has lost.

PK 22

PK 28

PK 25

PK 25

:  Please look at labels on the device.
: 3 phase and neutral 220-230 VAC
  4 Wires Star Connection (MKC-01, MKC-03, MKS-01, MKS-03)
: 3 Phase 380 VAC
  3 Wires Delta Connection (MKC-04)
: 3 Phase 220 V AC
  3 Wires Delta Connection (MKC-04)
: (0.9-1.1) x Un  (MKC-04)
  (0.8-1.2) x Un  (MKC-01, MKC-03, MKS-01, MKS-03)
: 50/60 Hz.
:  1 C/O, 8A, 250 V AC, 2000 VA, Cos

j

=1 (MKC-01, MKC-03, MKC-04)

   1 NO, 8A, 250 V AC, 2000 VA, Cos

j

=1 (MKS-01, MKS-03)

: LED output, normally ON (OFF for any fault)
  ON LED’i : On when supply voltage is present (MKC-01, MKC-03)
: 0.2 sec.
: -5 °C ; +50 °C
: IP 20
: Typ PK 22 (MKS-01, MKS-03)
  Typ PK 25 (MKC-01, MKC-03, MKC-04)
  Typ PK 28 ((MKC-01, MKC-03)
: Surface mounting or on the mounting rails.
  Panel mounting with screws and adapter is possible. (Refer to Figure 1)
: 0.08 kg. (MKS-01, MKS-03)
  0.1 kg. (MKC-01, MKC-03)
  0.2 kg. (MKC-04)

Rated Voltage  (Un)

Operating Range

Rated Frequency
Output Contacts

Warning  LEDs

Tripping Time
Ambient Temperature
Protection Class
Dimension

Installation

Weight

Dimensions

C1

T1

Stop

T1

M

3 ~

Start

L1
L2
L3

N

C1

N

L1 L2 L3

MKC-01
MKC-03

1 2 3

N

C1

T1

N

M

3 ~

L1
L2
L3

N

L3

N

L2

L1 1

2

MKS-01
MKS-03

C1

T1

Stop

T1

N

M

3 ~

Start

L1
L2
L3

N

C1

N L1 L2 L3

MKC-01
MKC-03

3

2

1

C1

T1

Stop

T1

N

M

3 ~

Start

L1
L2
L3

C1

L1 L2 L3

MKC-04

3

2

1

TYPE PK25

35 mm

90 mm

45 mm

62 mm

58 mm

32 mm

48 mm

35 mm

TYPE PK28

48 mm

34 mm

90 mm

35.3 mm

59.7 mm

45.4 mm

61.8 mm

36 mm

V

L3

V

L1

V

’

L1

V

’

L2

V

L2

V

Ref

V

Ref

= 220 VAC

x 100

Asymmetry % =

-

V

’

L1

V

’

L2

Fixed unbalance value

Hysterisis

L1
L2
L3

Output Relay (MKC-03)

TD = Tripping Time

TD

TD

Output Relay (MKC-01)

Wrong Phases Sequence

Precautions For Installation and Safe Use

Failure to follow those instructions will result in death or serious injury.
  Disconnect all power before working on equipment.
  When the device is connected to the network, do not remove the front panel.
  Do not try to clean the device with solvent or the like. Only clean the device
  with a dried cloth.
  Verify correct terminal connections when wiring.
  Electrical equipment should be serviced only by your compedent seller.
  Mount device to the panel.

No responsibility is assured by the manufacturer or any of its subsidiaries

for any consequences arising out of the use of this material.

Technical Data

Figure 1

23

mm

12

mm

35

mm

19

mm

19mm

61

mm

90

mm

28mm

48mm

58mm

45

mm

TYPE PK22

Vertrieb durch TDE Instruments GmbH

Reviews: