Out-of-Band NAC Design Procedures
Enterasys NAC Design Guide 5-21
Figure 5-5 NAC Gateway Redundancy
It
is
important
that
the
secondary
NAC
Gateway
does
not
exceed
maximum
capacity
if
the
primary
NAC
Gateway
fails
on
the
network.
For
example,
let’s
say
that
two
NAC
Gateways,
both
running
at
maximum
load
on
the
network,
are
being
used
by
six
switches.
NAC
Gateway
#1
is
the
primary
gateway
for
switch
A,
switch
B,
and
switch
C,
and
NAC
Gateway
#2
is
the
primary
gateway
for
switch
D,
switch
E,
and
switch
F.
In
this
scenario,
NAC
Gateway
#1
should
not
be
configured
to
serve
as
secondary
for
NAC
Gateway
#2
and
vice
versa.
This
is
because
if
NAC
Gateway
#1
fails,
NAC
Gateway
#2,
which
is
already
running
at
maximum
capacity
before
NAC
Gateway
#1
ʹ
s
failure,
will
not
be
able
to
handle
the
end
‐
systems
failing
over
from
NAC
Gateway
#1.
To
avoid
exceeding
these
limits,
extra
NAC
Gateway
appliances
must
be
deployed
on
the
network
to
serve
as
secondary
NAC
Gateways
for
these
six
switches.
To
summarize,
NAC
Gateway
redundancy
may
be
accomplished
using
two
different
approaches:
•
Active
‐
standby
redundancy
In
this
redundancy
approach,
a
set
of
switches
are
configured
to
use
the
same
primary
NAC
Gateway
(assuming
these
switches
observe
the
NAC
Gateway
ʹ
s
capacity
limitations
previously
described)
and
use
the
same
secondary
NAC
Gateway
as
a
backup
(assuming
the
secondary
NAC
Gateway
is
the
same
model
as
the
primary).
The
secondary
NAC
Gateway
is
not
configured
as
a
primary
NAC
Gateway
for
any
switch
on
the
network
and
therefore
is
inactive
until
a
primary
NAC
Gateway
fails.
For
example,
if
switch
A,
switch
B,
and
switch
C
use
NAC
Gateway
#1
as
a
primary
gateway,
then
all
three
switches
can
be
configured
to
use
NAC
Gateway
#2
on
the
network
as
the
backup.
In
this
configuration,
if
switch
A,
switch
B,
or
switch
C
loses
connectivity
to
NAC
Gateway
#1,
the
switch
would
seamlessly
transition
to
using
NAC
Gateway
#2.
In
the
worst
‐
case
scenario
where
all
three
switches
lose
connectivity
to
NAC
Gateway
#1,
NAC
Gateway
#2
would
be
able
to
handle
all
authentication
requests
from
these
three
switches.
In
this
redundancy
configuration,
NAC
Gateway
#2
is
completely
idle
on
the
network
and
only
utilized
if
one
of
the
switches
cannot
communicate
to
NAC
Gateway
#1.
•
Active
‐
active
redundancy
In
this
redundancy
approach,
the
primary
NAC
Gateway
for
one
switch
is
a
secondary
NAC
Gateway
for
another
switch.
For
this
configuration,
the
same
primary
NAC
Gateway
is
utilized
for
a
group
of
switches,
with
this
NAC
Gateway
running
at
only
half
the
maximum
load.
Another
group
of
switches
utilizes
a
different
primary
NAC
Gateway
(assuming
it
is
the
same
model)
also
running
half
the
maximum
load.
Then,
each
group
of
switches
can
use
the
other
NAC
Gateway
as
the
secondary
gateway.
This
redundancy
configuration
guarantees
that
in
the
worst
‐
case
scenario,
when
all
switches
in
one
group
lose
communication
to
their
Summary of Contents for 9034385
Page 1: ...Enterasys Network Access Control Design Guide P N 9034385...
Page 2: ......
Page 4: ...ii...
Page 8: ...vi...
Page 22: ...Summary 1 12 Overview...
Page 98: ...Additional Considerations 5 34 Design Procedures...