background image

INSTALLATION:

 

 

 

Ensure all AC power is switched off.   

 

Spin the upper cover anti-clockwise to detach it. 

 

Connect the power and the load with the sensor as per 

the connection-wire diagram. 

 

Affix the sensor switch base to the desired location with 

the included screws. 

 

Reattach the upper cover and test the sensor switch. 

 

CONNECTION-WIRE DIAGRAM:

 

 

 

 

 

 

 

 

 

 

 

TESTING THE SENSOR SWITCH: 

 

Turn the LUX knob clockwise to maximum setting (sun). Turn the SENS knob clockwise 

to maximum setting (+).

 

 

 

Turn the TIME knob 

anti-clockwise to the 

minimum setting (10s).

 

 

 

When  you  switch  on  the 

power,  the  light  will  turn  on 

immediately.  10  seconds  later  the  light  should  turn  off  automatically.  If  motion  is 

detected after this, the light should turn on. This indicates normal operation. 

 

If the motion sensor detects movement while the light is still on, it will reset the on-timer 

delay, causing the light to remain on.   

 

Turn  LUX  knob  anti-clockwise  to  the  minimum  setting  (3).  If  ambient  light  levels  are 

less than 3 lux (darkness), the sensor switch will go into motion sensing mode. 

  Note: When testing in daylight, please turn LUX knob to the maximum setting (SUN) to 

allow the sensor to work. 

 

INSTALLATION NOTES:

 

 

This product must be installed & maintained only by a qualified, licensed electrician. 

 

Install the product in a secure location that does not sway or vibrate.   

 

Objects placed in front of the sensor may affect the sensing range. 

 

Avoid installation near metal or glass surfaces as this will affect reception range. 

 

For your safety, do not open case after installation (qualified electricians only). 

 

Install a 6A switch or circuit breaker in-line with the switched load to prevent sensor 

damage due to overloading.   

 

TROUBLESHOOTING: 

 

The connected load does not turn on: 

a.  Check  the  input  power  to  the  sensor.  Ensure  supplied  voltage  is  between 

220~240VAC.   

b. Check to see if the indicator light is turned on after triggering 

– if it is, check 

the wiring to the load.   

c. If the indicator light does not turn on after triggering, try increasing the value of 

the LUX daylight sensor settings.   

 

Poor motion detection sensitivity: 

a.  Ensure  there  are  no  objects  between  the  sensor  and  the  desired  sensing 

location as this could reduce the range.   

b.  Ensure  that  there  are  no  other  devices  using  the  5.8GHz  band  in  close 

proximity to the detector (eg: Wireless LAN, CCTV transmission equipment, etc.) 

c. Ensure the installation height is 1.5-3.5m. 

 

The sensor does not turn off the load: 

a. Check the TIME knob to ensure that the correct on-time delay has been selected. 

b. Ensure that there are no other devices using the 5.8Ghz band in close proximity to 

the detector (e.g. Wireless LAN, CCTV transmission equipment, etc).   

c. Ensure that the power drawn by the load is less than 1200W for a resistive load 

and 300W for an inductive load. 

 

Reviews: