![Enplus DC020K-FE-00 User Manual Download Page 10](http://html.mh-extra.com/html/enplus/dc020k-fe-00/dc020k-fe-00_user-manual_2414037010.webp)
- 9 -
Hydraulic Clamp
Clamp OT terminals
Diagonal Pliers
Cut cables
Percussion Drill
Drill screw holes
2) Cables & Materials
Name
Specification
Quantity
Power supply cable
≧
5*6mm
²
three-phase power supply cable
Depend on actual requirement
Insulated tape
0.15mm*18mm, 0~600V, 0
℃
~80
℃
Depend on actual requirement
Cable tie
4*200mm
Depend on actual requirement
2.1.3 Installation Process
1) Installation Notice
a) Electrical product should be installed, operated, serviced, and maintained only by qualified personnel. No
responsibility is assumed by the manufacturer for any consequences arising out of the installation of this
product.
b) A qualified person is one who has skills and knowledge related to the construction, installation and
operation of electrical product and who has received safety training to recognize and avoid the hazards
involved.
c) All applicable local, regional, and national regulations must be respected when installing, repairing, and
maintaining this product.
2) Layout cables
Power supply cables come from the top, fixed with cable slot. Cable slot should be laid on the wall against the
center line of parking place. Cable slot end should be above the ground at 1.3cm. Cables extend out of the slot
end with more than 30cm.
Distance from
ground