USER MANUAL V1.12
EnOcean GmbH
Kolpingring 18a
82041 Oberhaching
Germany
Phone +49.89.67 34 689-0
Fax +49.89.67
34
689-50
[email protected]
www.enocean.com
Subject to modifications
PTM 230 User Manual V1.12
June 4, 2008 2:02 PM
Page 8/12
PTM 230
2.3.4
Telegram Data
The PTM 230 transmits an EnOcean radio telegram which is provided at the serial output of
a RCM 120 or TCM 120 module with the following parameters:
Unique factory programmed 32bit ID
Data2, Data1, Data0=0
Data3 and Status as follows:
P=polarity, X=reserved, R=repeater counter
The polarity P is defined as follows:
SW1
SW2
ORG
Data3
Status
open
open
0x05
000PXXXX XX10RRRR
Vcc
open
0x05
000P0000 XX11RRRR
open
Vcc
0x05
001P0000 XX11RRRR
Vcc
Vcc
0x05
001P0001 XX11RRRR
PWR1
PWR2
P
+
-
1
-
+
0