background image

AWAG Elektrotechnik AG   Sandbüelstrasse 2   CH-8604 Volketswil 

3210000.docx / 1876019 

Tel. +41 44 908 19 19  Fax +SW: UPD_V4_170505 / 15.05.2017 Seite 1 / 7 

UPD230/10 

Bedienungsanleitung  

Manual 

UP-Multi-Universaldimmer 

Flush mounted multi 

1-Kanal 

universal dimmer 1-channel 

 

Bezeichnung 

Typ / Type 

Art.-No./Item N° 

Designation 

UP-Multi-Universaldimmer 1-Kanal 300 VA  
automatische Lasterkennung RLC, Versorgungsspannung 230 V~ 

UPD230/10 

3210 000 

Flush mounted 

multi

 universal dimmer 1-channel 300 VA 

automatic load detection RLC, supply voltage 230 V~ 

K U R ZAN LE IT U N G 

  Dimmer gemäss Schema anschliessen 

  Drehschalter HEX auf 0 stellen 

  LRN 2 Sekunden drücken 

  Hand- oder Wandsender in der Nähe des Dim-

mers zweimal betätigen. CLR leuchtet während 
einer Sekunde, danach ist der Sender eingelernt 

  Weitere Sender einlernen 

  Zum Beenden CLR drücken 

B R IE F  IN S T R U CT ION    

  Attach dimmer according to schematic 

  Turn the rotary switch HEX to 0 

  Press LRN 2 seconds 

  Press handheld or wall mounted transmitter twice 

and keep it close to the actuator. CLR lights up for 
a second, after that the transmitter is programmed  

  Program further transmitters 

  To finish press CLR 

FU N K T ION E N  

  Dimmen mit Wippe / Taste 

  Treppenlichtfunktion 

  Schrittschalter (AW20) 

  Minuterie (AW23/24/25) 

  Soft-Ein/Aus 

  Programmierbare Szenen 

  Anwesenheitssimulation 

  Nebenstelleneingang mit Eintastenbedienung 

  Repeaterfunktion 

 

ARCO fähig (AWAG Remote Commissioning) 
 

FU N C T ION S  

  Dim with rocker-switch / push-button 

  Staircase light function 

  Step switch (AW20) 

  Timer (AW23/24/25) 

  Soft on/off 

  Programmable scenes 

  Presence simulation 

  Extension input with push-button function 

  Repeater function  

 

ARCO ready (AWAG Remote Commissioning)

EIGENSCHAFTEN 

  Optimiert für LED Leuchtmittel 

  Dimmbereich 0.5…100 % 

  Dimmlast 4…300 VA 

  Automatische Lasterkennung (R / L / C) 

FEATURES 

  Optimised for LED luminaires 

  Dim range 0.5…100 % 

  Dim load 4…300 VA 

  Automatic load detection (R / L / C) 

A LL GE ME IN  

Die Omnio Aktoren (Empfänger) werden über Funksignale der Omnio Sender an-
gesteuert.  Jeder Sender kann eine unbegrenzte Anzahl von Aktoren ansteuern. 
Die Funksender werden manuell durch ein einfaches Verfahren auf den Aktor ein- 
und ausgelernt. Jedem Sender können am Aktor eine Funktion und verschieden-
ste Parameter zugeordnet werden. 
 
Mit ARCO-Technologie lassen sich alle Omnio Aktoren vollständig und ohne 
manuellen Zugriff zum Gerät per Funk konfigurieren. Die leistungsstarke Software 
E-Tool bildet dabei das Herzstück, um Projekte beliebiger Grösse bequem am 
Schreibtisch zu planen, konfigurieren und dokumentieren. 

P R OD U K T B E S C H R E IB U N G  

Der Omnio UP-Multi-Universaldimmer 1-Kanal UPD230/10 mit Neben-
stelleneingang  ist ein Gerät zum Dimmen von  LED Leuchtmitteln und anderen 
elektrischen Verbrauchern. Dank automatischer Lasterkennung (R/L/C) wählt der 
Dimmer die  richtige Betriebsart sowie die ideale Dimmkurve für das angeschlos-
sene Leuchtmittel.  Bis zu 50 Omnio Funksender lassen sich  einlernen, wobei 
jedem dieser Sender eine Funktion zugeordnet werden kann wie z.B. Dimmen mit 
Wippe, Dimmen mit Taste, Treppenlichtfunktion,  vordefinierter Dimmwert, Schritt-
schalter (AW20), Minuterie (AW23/24/25), Soft-Ein/Aus, programmierbare Szenen 
oder  Anwesenheitssimulation.  Nicht dimmbare Lasten werden automatisch im 
Nulldurchgang geschaltet. Am Nebenstelleneingang angeschlossene konventio-
nelle  Taster sind fest mit der Funktion 

Dimmen mit  Taste

  belegt.  Bidirektionale 

Kommunikation,  EEP D2-01-03,  ARCO fähig (AWAG Remote Commissioning). 
Zusätzlich kann bei Reichweitenproblemen die eingebaute Repeaterfunktion 
aktiviert werden. Geeignet für die Unter- oder Aufputzmontage in Kunststoffdosen. 

 

GE N E R AL  

The Omnio  actuators (receivers) are controlled by radio signals coming from the 
Omnio transmitters. Each transmitter is able to control an unlimited amount of 
actuators. The radio transmitter can be manually programmed and deprogrammed 
to an actuator by following a simple procedure. Via actuator each transmitter can 
be given a certain function and different parameters.  
 
With ARCO technology, all Omnio actuators can be configured completely by 
radio without manual access to the device. The powerful software E-Tool consti-
tutes the key component for convenient planning, configuring and documenting 
projects of any size right at your desk. 

P R OD U C T   D E S C R IP T ION    

The Omnio flush mounted multi  universal dimmer 1-channel UPD230/10 with 
extension input is a device for dimming LED luminaires and other electrical loads. 
Thanks to automatic load recognition (R/L/C) the dimmer selects the right operat-
ing mode as well as the ideal dimming curve for the connected light source. Up to 
50 Omnio radio transmitters can be programmed. Each  transmitter can be as-
signed  a  function, for example dim with rocker-switch, dim with push-button, 
staircase light, predefined dim value, step-switch (AW20), timer (AW23/24/25), 
soft on/off, programmable  scenes  or presence simulation.  Non-dimmable loads 
are automatically switched at zero crossing. Conventional push-buttons connected 
to the extension input are permanently  assigned the function d

imming with key

Bidirectional communication, EEP D2-01-03, ARCO ready (AWAG Remote Com-
missioning). In addition this actuator can be used as repeater in case of range 
issues. Suitable for flush mounted sockets. 

AN ZE IGE - U N D   B E D IE N E LE ME N T E  

 
Klemmen 

  L 

Netzspannung L 110 – 240 V~ 

  N 

Netzspannung N 110 – 240 V~ 

  ~ 

Ausgang 

  T 

Nebenstelleneingang 

 

 
Bedienelemente 

  CLR 

Taste und LED Clear 

  LRN 

Taste und LED Learn 

  HEX 

Drehschalter 0..15 

D IS P L AY   AN D   OP E R AT IN G  E LE ME N T S  

 
Terminals  

  L 

line voltage L 110 – 240 V~ 

  N 

line voltage N 110 – 240 V~ 

  ~ 

output 

  T 

extension input 

 

 
Operating eleme

nts 

  CLR 

button and LED clear 

  LRN 

button and LED learn 

  HEX 

rotary switch 0..15 

 

 

 

 

EnOcean-Technologie (868 MHz) 

Summary of Contents for Omnio UPD230/10

Page 1: ...cher Lasterkennung R L C wählt der Dimmer die richtige Betriebsart sowie die ideale Dimmkurve für das angeschlos sene Leuchtmittel Bis zu 50 Omnio Funksender lassen sich einlernen wobei jedem dieser Sender eine Funktion zugeordnet werden kann wie z B Dimmen mit Wippe Dimmen mit Taste Treppenlichtfunktion vordefinierter Dimmwert Schritt schalter AW20 Minuterie AW23 24 25 Soft Ein Aus programmierbar...

Page 2: ...ler Geräteparameter ist in Tabelle 4 GERÄTEPARAMETER zu finden 1 Geräteparameter wählen 2 Drehschalter gemäss Tabelle 4 Spalte 1 einstellen 3 Einlernmodus durch einen langen Tastendruck 2 s auf aktivieren LRN leuchtet und CLR blinkt 4 Drehschalter gemäss Tabelle 4 Spalte 3 einstellen 5 drücken LRN und CLR erlöschen INST ALLAT ION This device is suitable for flush mounted sockets installed indoors ...

Page 3: ...TIONEN AWAG FUNCTIONS A01 Anwesenheitssimulation mit Wippe Taste O Aus zur Kontrolle schaltet das Licht 3 s ein und dann aus Taste I Ein zur Kontrolle schaltet das Licht 6 30 s ein und dann aus bevor die Anwesenheitssimulation startet 2 2 s drücken press 2 s 0 Wippe 2x drücken press rocker switch 2x drücken press 0 A01 Presence simulation with rocker switch Button O Off for checking purposes the l...

Page 4: ...s Dimmwert 60 Überblenddauer 1 s 0 10 Dim value 60 fade time 1 s Dimmwert 75 Überblenddauer 1 s 0 11 Dim value 75 fade time 1 s Dimmwert 90 Überblenddauer 1 s 0 12 Dim value 90 fade time 1 s Dimmwert 100 Überblenddauer 1 s 0 13 Dim value 100 fade time 1 s D05 Schrittschalter AW20 Einschalten 100 oder ausschalten 0 5 Taste 2x drücken press push button 2x D05 Step switch AW20 Switch on 100 or off D0...

Page 5: ...mitters remain Beispiele Examples Wippe beidseitig löschen 0 CLR 2 s drücken Wippentaste O 2x drücken Wippentaste I 2x drücken CLR Delete both sides of a rocker switch 0 press CLR 2 s press button O 2x press button I 2x CLR Taste löschen 0 CLR 2 s drücken Taste drücken CLR Delete push button 0 press CLR 2 s press button 2x CLR Gerät komplett zurücksetzen 0 CLR 2 s drücken 15 LRN 2 s drücken 13 LRN...

Page 6: ...smit them Only one device must be activated as a repeater within a radius of 5 meters Aus 15 2 s drücken press 2 s 0 drücken press X Off Level 1 Verstärkt nur Originaltelegramme 15 1 Level 1 Amplifies original radio telegrams Level 2 Verstärkt Originaltelegramme und bereits einmal verstärkte Telegramme 15 2 Level 2 Amplifies original radio telegrams and also retransmit ted radio telegrams RÜCKMELD...

Page 7: ...NISCHE DAT EN UPD230 10 T ECHNICAL SPECIFICAT IONS Spannungsversorgung 230 V 50 Hz Voltage supply Standby Verbrauch 0 6 W Standby power consumption Absicherung des Gerätes Sicherung automat 13 A Hardware protection automatic circuit breaker fuse Lastausgang Bemessungsstrom Ohmsche Last Glühlampen Induktive Last cosφ 0 8 Halogenlampen 230 V MOSFET nicht potentialfrei not potential free 0 5 A 230 V ...