ISA-60M

 

 

ENMET Corporation 

7

 

 

 

 

 

 

Table 1: Wiring ISA-60M

 

to

 

MRI-5175 

ISA-60M 

 

MRI-5175 

Channel 1, J16 

+24V (1) 

GND (2) 

 mA  (3) 

 

Power 

Ground 

Signal 

Channel 1, J4 

+24V 

GND 

mA 

Channel 2, J18 

+24V 

GND 

mA 

 

Power 

Ground 

Signal 

Channel 2, J4 

+24V 

GND 

mA 

Channel 3, J19 

+24V 

GND 

mA 

 

Power 

Ground 

Signal 

Channel 3, J4 

+24V 

GND 

mA 

Figure 5A: MRI-5175 Input and Output Terminals 

3.4.2 

ISA-60M

 Relay Contacts 

Relay contacts are available for each alarm; these are 

SPDT

, rated at 10Amp at 110

V

AC

 or

 

10Amp at 30

V

DC

 for restive loads, 

and may be latching or non-latching as required by the application.  They are accessed on the terminals next to each relay see 
Figure 2 & 5.  The contact positions are noted on the circuit board next to each terminal. 

These relay coils are energized when they are in the non-alarm state; the contact conditions given above are for the non-
energized state, which is identical to the alarm state. 

In addition, there is a fault relay, which changes state whenever the instrument is in a fault condition.  The contact positions are 
noted on the circuit board next to each terminal.  The coil of this relay is energized when the instrument is in the non-fault state; 
the contact conditions given on the circuit board next to the terminal, are for the non-energized state, which is identical to the 
fault state. 

The PC Board is labeled for the relays in their un-energized state.  If the relay is configured for failsafe, then this is also the alarm 
condition state.  Non-failsafe configured relays in the alarm state, are the reverse of the PC board labeling.  Note that the 
Fault(FLT) relay cannot be set to operate in a Non-Failsafe mode.  Please see the Table 2 below: 

Table 2 : Relay Failsafe Settings 

Position 

Failsafe-Alarm 

Non-Failsafe-Alarm 

J5  

Relay 1 - NO  

Normally Open 

Normally Closed 

J5  

Relay 1 - COM  

Common 

Common 

J5  

Relay 1 - NC  

Normally Closed 

Normally Open 

J6  

Relay 2 - NO  

Normally Open 

Normally Closed 

J6  

Relay 2 - COM  

Common 

Common 

J6  

Relay 2 - NC  

Normally Closed 

Normally Open 

J8  

Relay 3 - NO  

Normally Open 

Normally Closed 

J8  

Relay 3 - COM  

Common 

Common 

J8  

Relay 3 - NC  

Normally Closed 

Normally Open 

J10  

Relay 4 - NO  

Normally Open 

Normally Closed 

J10  

Relay 4 - COM  

Common 

Common 

J10  

Relay 4 - NC  

Normally Closed 

Normally Open 

J14  

Relay 5 - NO  

Normally Open 

Normally Closed 

J14  

Relay 5 - COM  

Common 

Common 

J14  

Relay 5 - NC  

Normally Closed 

Normally Open 

J15  

Relay 6/FLT - NO  

Normally Open 

N/A 

J15  

Relay 6/FLT - COM  

Common 

N/A 

J15  

Relay 6/FLT - NC  

Normally Closed 

N/A 

These relay contacts can be used to operate auxiliary alarms or other functions. 
 

MRI-5175 Lid, interior view 

(Optional) 

D– 
D+ 

mA 

GND 

24V 

J4 

Summary of Contents for ISA-60M

Page 1: ...w enmet com Manual Part Number 80003 500 MCN 13 002 04 29 13 ISA 60M with MRI 5175 OPERATION AND MAINTENANCE MANUAL Andersen Medical Gas 12 Place Lafi fitte Madisonville LA 70447 https www TheMedicalG...

Page 2: ...3 Fault Indications 9 4 4 Alarm Latching 9 4 5 Audio Defeat 9 4 6 Display 10 4 7 Operational Menu 10 5 0 Maintenance 11 5 1 Cleaning Instructions 11 5 2 Maintenance Menu ISA 60M 11 5 2 1 Set 4 20mA T...

Page 3: ...enu Flow Chart 11 Figure 9 Calibration MRI 5175 13 Figure 9 Calibration MRI 5175 20 Figure 10 MRI 5175 Sensor Replacement 21 List of Tables Table 1 Wiring ISA 60M to MRI 5175 7 Table 2 Relay Failsafe...

Page 4: ...l not honor any claims for damage This shipment was carefully inspected verified and properly packaged at our company and delivered to the carrier in good condition When it was picked up by the carrie...

Page 5: ...installed to the instrument Alarm 1 The top center A red alarm LED for all sensor transmitters Alarm 2 Near the center of the panel A green power indicator LED A red fault alarm LED Pushbutton Switche...

Page 6: ...g Flanges 4 places Menu Select SN XXXX 88 Power Fault XXX XXX XXX O2 by vol O2 O2 Display Front Cover Latch Audio Alarm Fault LED SELECT Switch Power LED OPTION Switch Alarm Defeat Alarm Acknowledge S...

Page 7: ...Figure 2 Feature Description Relay Terminals This group of terminals is located at the left side of the Circuit Board For the contacts for each of four alarm relays and for the contacts of a fault re...

Page 8: ...les the ambient air in the MRI environment It is recommended to use 8 drywall anchors and screws for mounting the ISA 60M to a drywall sheetrock surface Non magnetic mounting hardware is required Dime...

Page 9: ...of the two enclosure punch outs on the side or bottom of the enclosure See Figure 1 Follow state and local guidelines when selecting appropriate strain relief conduit and wiring Remote Sensor Each mus...

Page 10: ...the circuit board next to the terminal are for the non energized state which is identical to the fault state The PC Board is labeled for the relays in their un energized state If the relay is configur...

Page 11: ...g of 0 at the bottom of the range 20mA corresponds to a full scale reading of 30 Wiring requirements are the same as for the relays 3 4 4 Digital Outputs The RS232 RS485 connections are used for firmw...

Page 12: ...The differential Setting has no effect on alarm relays or on the audio alarm for alarm point 2 4 3 Fault Indications Fault indications are associated with sensor zero and calibration activities and ar...

Page 13: ...taken for a period of 45 seconds it returns to the operational display Figure 7 ISA 60M Operation Menu Flow Chart S S O O O S O Press Option switch S Press Select switch O No Function O No Function S...

Page 14: ...ation instructions can be found in Section 6 0 5 1 Cleaning Instructions CAUTION Never spray a cleaning solution on the surfaces of the ISA 60M or MRI 5175 devices Clean the exterior of the ISA 60M an...

Page 15: ...Fault led will show Red for 3 seconds and then flash red green red green red green 6 Press and release the Select switch to exit calibration and return to operation mode If the calibration was complet...

Page 16: ...e digit to the right when the last digit is accepted the display will read Ch O2 mAXmter NA Trim Press the SELECT switch to enter The display will read O2 20 8 3029 Trim Val 20 7 note this number will...

Page 17: ...STD is displayed Press the OPTION switch to toggle between STD and DIFF select the correct indicator Press the SELECT switch to lock in the correct indicator IF STD is selected ALARM 1 V L is displaye...

Page 18: ...d DIFF Locks selection STD S Alarm 1 DIFF BAND 000 v L 19 5 Alarm 1 O S Changes character indicated by underscore cursor Locks underscored character and moves cursor to next digit DIFF S O S Changes c...

Page 19: ...he OPTION switch to change the left digit select the correct digit Press the SELECT switch which locks the digit in place and moves the cursor one digit to the right Continue this process until the fo...

Page 20: ...e Set Relay Failsafe Configuration Flow Chart 5 2 10 Set New Password To change the password you must enter the maintenance menu Press the OPTION switch until Enter Maint Menu is displayed then press...

Page 21: ...ivation Each channel of the ISA 60M can be deactivated and activated as needed CAUTION Deactivated channels will not display or respond to connected sensor transmitters A fault indication occurs when...

Page 22: ...ibration and then flash red green red green If the calibration was unsuccessful following the 60 to 120 second stabilization time the Power Fault led will show Red for 3 seconds and then flash red gre...

Page 23: ...for 3 seconds NOTE If the calibration process indicates a failure wait 30 minutes and repeat process or contact ENMET Corporation Figure 9 Calibration MRI 5175 Power Fault LED MENU Switch SELECT Switc...

Page 24: ...er lid retention screws and remove the lid See Figure 10 Remove the old O2 sensor by unscrewing it and replace it with a new sensor See Figure 10 Replace cover lid with retention screws Turn on the el...

Page 25: ...Pa Mechanical ISA 60M Dimensions 11 x 9 x 6 inches 4 3 x 3 5 x 2 4 cm Weight 8 lbs 3 6 kg Strain relief 5 12 mm OD Material Engineered thermoplastic with hinged front cover Non magnetic hardware MRI 5...

Page 26: ...warranty period the customer is responsible for the difference between the most economical means and the expedient mode ENMET shall not be liable for any loss or damage caused by the improper use of...

Page 27: ...processing delays ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour All instruments sent to ENMET are subject to a minimum...

Page 28: ...nt Terms K COD Check one K VISA MasterCard______________________ ________ ________ Card number Expiration Card Code K American Express______________________ ________ ________ Card number Expiration Ca...

Reviews: