4   Troubleshooting

4. Troubleshooting

Description of fault

Possible cause(s)

Suggested action

The alarm ”CONST FLOW
BLOCKED BY SAFETY GATE”
will be shown in the cabin module
display and in Microconf when a
constant flow button is depressed.

1. Safety lock lever signal not

connected.

2. Safety lock lever signal

incorrectly connected/

incorrectly configured.

3. Safety gate open.
4. Safety gate closed at system

start.

1. Check that the safety lock

lever signal is installed.

2. Check that the safety lock

lever signal is correctly

connected and correctly

configured.

3. Close the safety gate.
4. Open and close the safety

gate.

After a 2-second audible signal
from the DC2 cabin module,
the selected function will stop
working.

Activation interval exceeded.

During the activation system,
the constant flow button must be
released within 2 seconds.

Nothing happens when a constant
flow button is held down for 3
seconds or more.

Constant flow incorrectly
configured.

Check the constant flow installation
and configuration according to
9000224 Installation Instructions.

When the program sequence
is complete and the activation
sequence is performed, nothing
happens on the programmed
function.

The programmed function is not
activated for constant flow.

Check that the constant flow
configuration on the selected
function is activated for constant
flow activation.

The alarm ”CONST FLOW
BLOCKED BY PARAMETER
ERROR” will be shown in the
cabin module display and in
Microconf.

Incorrect parameter entry in the
cabin module.

Contact support.

13

Summary of Contents for 9000225

Page 1: ...User manual Constant flow Article 9000225 Language Country Original Instructions...

Page 2: ...he market leader in tiltrotators and tools for excavators We represent innovation knowledge and experience and we develop our products with a focus on the customer s needs Please visit our website for...

Page 3: ...crapping and recycling 4 1 3 Technical support and spare parts 4 1 4 Product approval 5 1 4 1 Declaration of Incorporation 5 2 Safety 2 1 General 6 3 Operation 3 1 Programming sequence 9 3 2 Activatio...

Page 4: ...ny other supplementary information in a safe manner and such that it is always available 1 2 Scrapping and recycling engcon makes constant efforts to reduce its environmental impact engcon s products...

Page 5: ...rds Designation SS EN ISO 13849 1 2008 Safety of machinery Safety related parts of control systems Part 1 General principles for design SS EN ISO 12100 2010 Safety of machinery General principles for...

Page 6: ...hem The following warning levels are used in this user manual DANGER Indicates that an accident will occur if the regulation is not followed Risk of personal injury or death WARNING Indicates that an...

Page 7: ...are determined in the programming sequence 2 Activation sequence the activation sequence starts constant flow to selected functions 3 Deactivation when constant flow is deactivated all active functio...

Page 8: ...3 Operation IMPORTANT Maintenance and repair of the electrical system may only be carried out by professionally qualified persons 8...

Page 9: ...grammed to a roller and button EXTRA 2 2146492 2 Press the constant flow button after 3 seconds a buzzer will sound in the DC2 cabin module Release the function roller button Speed and direction are l...

Page 10: ...elected functions are activated with the programmed speed and direction 2147270 2 After 3 seconds a buzzer will sound in the DC2 cabin module If the operator releases the button within 2 seconds after...

Page 11: ...sed within 2 seconds the constant flow function will start and the activation sequence must then be restarted WARNING Beware of moving parts A lack of awareness may lead to crush injuries Risk of pers...

Page 12: ...3 Operation The constant flow button is depressed The safety gate is opened Faulty constant flow button 12...

Page 13: ...cabin module the selected function will stop working Activation interval exceeded During the activation system the constant flow button must be released within 2 seconds Nothing happens when a constan...

Page 14: ...Notes...

Page 15: ...Version 1 3 engcon North America Inc 2666 State St 9 Hamden CT 06517 Phone 1 203 691 5920 northamerica engcon com www engcon com...

Reviews: