DJM2.4 MANUAL
36
Oct 00 R2
condensate pump must be used. The condensate return line connection on the
humidifier must be sealed off if not in use.
-
The SH unit must be drained daily to reduce scaling from the minerals etc that are
left behind when the water is boiled off into steam. If this is not done the unit will
fail prematurely.
-
The SH unit must be de-scaled at least annually (will vary depending on water usage
and water quality).
-
There are water level controls sensing minimum and maximum water levels in the
water heater. A buildup of moisture and / or dirt on some portions of the sensor
ceramics may allow the heat to operate without proper water levels. This could
result in damage to the heat exchanger / SH tank. When servicing, these water level
sensors should be confirmed as operating correctly at least annually. If the unit
location is remote from suppliers and humidity control is important, stocking a spare
water level sensor control system is recommended. (As well other parts may be
stocked if desired).