ENFORCER Outdoor Stand-Alone/Wiegand Keypad with Proximity Reader
2
SECO-LARM U.S.A., Inc.
This page is for installers looking to do a basic installation and programming of the keypad. For more
in-depth installation and programming instructions, see "Table of Contents" on pg. 4.
Quick Wiring Diagram:
Mounting Diagram:
NOTE:
For DC-powered electric strikes, connect the included diode as close as possible and in parallel
with the electric strike. This absorbs possible electromagnetic interference to prevent operation
of the strike from damaging the keypad. Do not connect a diode when using electromagnetic
locks or with AC powered strikes.
Quick Installation Guide:
Orange – Output (N.C.)
Blue – Output (N.O.)
Yellow – Egress Input (N.O.)
Black – Ground (–)
Gray – Tamper Alarm Output (GND)
Purple – Output (COM)
Red – 12VDC (+)
12VDC
Power
Supply
(+)
Egress
Button
(–)
(+)
(–)
Or
Cathode
Electric
Lock
IN4007
Output Relay
N.O. Output for Fail-secure Lock
N.C. Output for Fail-safe Lock
(+)
Alarm
(–)
Diode IN4007
(See note below)
Door Sensor
Brown – Door Sensor Input*
Green – Data 0
White – Data 1
Wiegand
Controller
2
3
4
9
0
7
8
5
6
*
Connect to ground if unused
Housing base
Security screw
Drill at least ø
3
/
8
"
(ø9mm) wiring hole
Choice of 2 pairs of
mounting holes