APPENDIX A: HORIZONTAL AND VERTICAL VENT CHART
Possible Vertical
vent length (fe
et)
Possible Horizontal vent length (feet)
For example, let’s imagine an installation consisting of a horizontal
vent coming out at the back of the stove on a total distance of 8 feet.
This horizontal run is followed by a tee and a 6-foot vertical rise. This
type of installation is not acceptable. As you can see, the vent
termination is clearly outside the allowed configuration zone on the
chart because the venting system proposed
does not have at least
one foot of vertical rise for each foot of horizontal run
.