enervent greenair LTR-3 EC Planning, Installation And Operational Instructions Manual Download Page 11

11

Enervent® ECC EN 2010_2

M

AINTENANCE

BELT REPLACEMENT

 

Turn of the ventilation unit by switching off the main power supply, 

 

removing the fuse or disconnecting the wall plug.

 
 

Open the maintenance hatch.

 

Unplug the heat exchanger.

 

Pull out the heat exchanger from the ventilation unit.

 

Remove the lid by detaching the screws (pic 1).

 pic 1

 
 

Turn the heat exchanger on to its side so that the axle is in a 

 

vertical position. Remove the sealing strip (pic 2).

 

Detach the hexagonal screw and the screws in the u-beam.

 
 

Remove the u-beam.

 

Remove the old belt.

 pic 2

 
 

Remove any possible dirt from the rotors surface and carefully 

 

place the new belt inside the heat exchanger through outer shell 

 

and the gasket (pic 3 and 4).

 

Carefully pull the belt past the gasket and rotate the rotor at the 

 

same time. Assemble the u-beam.

 

Attach the beams screws and the hexagonal screw of the axle.

 

Put the belt on to the belt wheel and rotate the rotor away from 

 

the motor a couple of times (pic 5).

 

Clean the inside of the heat exchanger.

 

Close the lid.

 

Re-assemble the heat exchanger in to the ventilation unit and 

 

plug it in.

 

Turn on the ventilation unit and check that the heat exchanger is 

 

rotating.

 

Close the maintenance hatch.

 
 

NOTE! A spare belt is delivered with the ventilation unit, it is 

 

attached to the inside of the heat exchanger.

 

 pic 3

 pic 4

 pic 5

Summary of Contents for greenair LTR-3 EC

Page 1: ...Enervent greenair Planning installation and operational instructions manual Before installing and operating this unit please read this manual thorougly and retain it for future reference www enervent...

Page 2: ...air calibration About ventilation Control panel CONTROL 8 MAINTENANCE MAINTENANCE 9 BELT REPLACEMENT 11 SERVICE ALARM INDICATION 12 TROUBLESHOOTING 12 TECHNICAL INFORMATION TECHNICAL INFORMATION 13 DI...

Page 3: ...ives no mensioning alternating current fans control optional electrical heater FOREWORD All greenair ventilation units are designed and manufactured for use all year round In Finland the ventilation u...

Page 4: ...pply air A characteristic of the regenerative heat exchanger is its high rate of heat recovery or efficiency The efficiency varies from 75 to 85 depending on the proportion of supply air and exhaust a...

Page 5: ...the rear attachment bracket directly to the wall at required height An insula tion board can be installed behind the unit to reduce the transfer of machine noise or vibration Place the unit onto the l...

Page 6: ...ed Open the units maintenance hatch with the key provided when all the above mentioned installation work is done Check that the unit is clean on the inside that there are no spare parts inside the uni...

Page 7: ...has also a button 2 to turn on the electrical boost heater and to choose the supply air tem perature The four green LED lights show the supply air temperature as follows 17 C 19 C 21 C 23 C The higher...

Page 8: ...input for an emergency stop switch The emergency stop will turn off the ventilation unit It is restarted by de activating the emergency stop switch Cooling recovery The rotating heat recovery wheel c...

Page 9: ...owing through the air channels using compressed air Do not use a pressure washer and do not submerge the heat exchanger into water When restarting the unit after cleaning check that the heat exchan ge...

Page 10: ...ir in addition to the F5 plane filter 6 months Pingvin XL F5 bag filter F5 bag filter 6 12 months F7 cassette filter in the supply air 6 months Pandion F5 bag filter F5 bag filter 6 12 months F7 bag f...

Page 11: ...ossible dirt from the rotors surface and carefully place the new belt inside the heat exchanger through outer shell and the gasket pic 3 and 4 Carefully pull the belt past the gasket and rotate the ro...

Page 12: ...m is and reset the over heating protection SUPPLY AIR TOO COLD REDUCED AIR FLOW Reason Action Filters are blocked Change the filters Too small a fan speed is selected Select higher speed Blockage in t...

Page 13: ...m 707 mm 720 mm Weight 52 kg 52 kg 96 kg 130 kg 130 kg Duct connections 160 mm 160 mm 200 mm 250 mm 250 mm AC fans supply exhaust 130 W 0 57 A 185 W 0 80 A 300 W 1 40 A 450 W 3 20 A DC fans supply exh...

Page 14: ...ng 8 W 0 035 A 8 W 0 035 A 8 W 0 035 A 8 W 0 035 A VENTILATION UNIT PANDION PELICAN PEGASOS PEGASOS XL Width Depth Hight 785 mm 543 mm 895 mm 998 mm 590 mm 1 270 mm 1 250 mm 677 mm 1 400 mm 1 250 mm 6...

Page 15: ...AWINGS SERVICE HATCH 598 630 500 WASTE AIR OUTSIDE AIR SUPPLY AIR EXHAUST AIR 514 320 87 394 84 160 216 233 1 2 5 107 320 320 Enervent greenair PLAZA WASTE AIR OUTSIDE AIR SUPPLY AIR EXHAUST AIR 514 3...

Page 16: ...Y AB Tel 358 207 528 800 fax 358 207 528 844 Kipin tie 1 06150 Porvoo Internet E mail enervent enervent fi Paino kg Hyv Muutt Pvm Muutos No Lehti Muutos Piir no Nimitys Suhde Pvm File Hyv Tark Piirt V...

Page 17: ...ISO 13920 AE OUTSIDE AIR WASTE AIR No Muutos Pvm Muutt Hyv Osa Kpl Osan nimitys Tark Piirt Hyv File Nimitys Piir no Muutos Paino kg Pvm Valmiste Suhde Lehti SUPPLY AIR DIMENSION DRAWING C PLANERING P...

Page 18: ...0 110 560 110 110 330 390 555 E mail enervent enervent fi Tel 358 0 207 528800 Fax 358 0 207 528844 Kipin tie1 06150 Porvoo Hyv Muutt Pvm Muutos No Suhde Pvm Hyv Tark Piirt Paino kg Lehti Muutos Piir...

Page 19: ...8 mK Tel 358 207 528 800 fax 358 207 528 844 Kipin tie 1 06150 Porvoo E mail enervent enervent fi Paino kg Hyv Muutt Pvm Muutos No Lehti Muutos Piir no Nimitys Suhde Pvm File Hyv Tark Piirt Valmiste O...

Page 20: ...07 528 844 ISO 2768 mK Hitsatut rakenteet YLEISTOLERANSSIT EN ISO 13920 AE Koneistetut osat U suunnitelu PEGASOS 20050111 1 A PEGASOS 001 PEGASOS 8 1 20050111 J T DIMENSION DRAWING Nr Rev Dat Rit Blad...

Page 21: ...CTIONS 160 mm 25mm INSULATION PV IPL mineral wool MOUNTING WITH SERVICE HATCH UPWARDS OR TO THE SIDE SERVICE AREA 1000X650 479 t 2 Pienkone 032LTR3 Osa Kpl Osan nimitys Valmiste Piirt Tark Hyv File Pv...

Page 22: ...CE HATCH SUPPLY AIR EXHAUST AIR OUTSIDE AIR WASTE AIR Piir no Kipin tie 1 FI 06150 PORVOO tel 358 207 528 800 Internet e mail enervent enervent fi DIMENSION DRAWING INSULATION 25 mm pv ipl mineral woo...

Page 23: ...ERAL WOOL SERVICE HATCH SERVICE AREA 800x1700 707 2 5 0 20020822 U VAKIO T LTR S 007LTR7 450 325 183 EXHAUST AIR 720 334 183 450 2 5 0 SUPPLY AIR CONDENSE WATER DRAIN Osa Kpl Osan nimitys Valmiste Pii...

Page 24: ...MPERATURE EFFICIENCY Air amount l s Supply exhaust air ratio 1 0 Supply exhaust air ratio 0 85 70 75 80 85 90 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 87 82 75 79 ENERVENT PANDION HEAT RECO...

Page 25: ...exhaust air ratio 0 85 70 75 80 85 90 50 100 150 200 250 300 350 400 87 81 70 75 ENERVENT PEGASOS XL HEAT RECOVERY TEMPERATURE EFFICIENCY Air amount l s Supply exhaust air ratio 1 0 Supply exhaust air...

Page 26: ...ECOVERY TEMPERATURE EFFICIENCY Air amount l s Supply exhaust air ratio 1 0 Supply exhaust air ratio 0 85 70 75 80 85 90 20 30 40 50 60 70 80 90 100 110 87 81 77 80 ENERVENT LTR 3 HEAT RECOVERY TEMPERA...

Page 27: ...0 70 Plaza eco ECC supply and exhaust air characteristic curves with EU7 EU5 filters 0 50 100 150 200 250 0 10 20 30 40 50 60 70 80 90 80V 100V 120V 140V 160V 180V 200V 230V Air amount l s Available p...

Page 28: ...Pa SUPPLY AIR EXHAUST AIR Pingvin 120 ECC supply and exhaust air characteristic curves with EU7 EU5 filters 0 50 100 150 200 250 0 10 20 30 40 50 60 70 80 90 100 110 120 80 90 100 70 60 50 40 30 20 90...

Page 29: ...co XL ECC supply and exhaust air characteristic curves with F7 F7 filter SUPPLY AIR EXHAUST AIR 80 70 60 50 40 20 90 100 30 0 50 100 150 200 250 300 350 400 450 500 0 50 100 150 80 70 60 50 40 30 90 1...

Page 30: ...mount l s Available pressure Pa SUPPLY AIR EXHAUST AIR Pelican ECC supply and exhaust air characteristic curves with EU7 EU7 filters 0 50 100 150 200 250 300 350 400 0 50 100 150 200 80 70 60 50 40 30...

Page 31: ...V 230 V Air amount l s Available pressure Pa SUPPLY AIR EXHAUST AIR Pegasos XL ECC supply and exhaust air characteristic curves with EU7 EU7 filters 0 50 100 150 200 250 300 350 400 450 500 0 100 200...

Page 32: ...XHAUST AIR LTR 3 85 ECC supply and exhaust air characteristic curves with EU5 EU5 filters 0 50 100 150 200 250 300 350 400 450 500 0 50 100 150 200 250 300 350 400 Available pressure Pa Air amount l s...

Page 33: ...V 3 200V 230V 4 Air amount l s Available pressure Pa SUPPLY AIR EXHAUST AIR LTR 3 120 ECC supply and exhaust air characteristic curves with EU7 EU7 filters 0 50 100 150 200 250 300 350 400 0 20 40 60...

Page 34: ...nt l s Available pressure Pa SUPPLY AIR EXHAUST AIR LTR 6 ECC supply and exhaust air characteristic curves with EU7 EU7 filters 0 50 100 150 200 250 300 350 400 0 50 100 150 200 80 70 60 50 40 30 90 1...

Page 35: ...ailable pressure Pa SUPPLY AIR EXHAUST AIR LTR 7 ECC supply and exhaust air characteristic curves with EU7 EU7 filters 0 50 100 150 200 250 300 350 400 0 50 100 150 200 250 300 350 400 1 2 3 4 80V 100...

Page 36: ...ir amount l s Available pressure Pa SUPPLY AIR EXHAUST AIR LTR 7 eco ECC supply and exhaust air characteristic curves with EU7 EU7 filters Available pressure Pa Air amount l s 80 70 60 50 40 30 90 100...

Page 37: ...an speed 2 Screw S3 External input fan speed 3 Screw S4 External input fan speed 4 Screw OVERP External input push button over pressure Screw OVERP Screw ALARM External alarm input fire freezing prote...

Page 38: ...main switch door switch Screw LTO N Neutral for heat recovery motor Screw LTO E 230 VAC for heat recover motor Screw AFT HEAT N Neutral for electrical heater ECE models Screw AFT HEAT L 230 VAC for e...

Page 39: ...EMP TEMPERATURE CONNECTIONS SEE APPENDIX D X1 N SEE APPENDIX ELECTRIC HEATER N L1 L2 L3 C2 SUPPLY 1x16 A 230 VAC 3x2 5s ECE MODELS electric heater 2kW SUPPLY 3x16 A 400 VAC 5x2 5s ECE MODELS electric...

Page 40: ...AX 250VAC 1A OPERATORPANEL CABLE STANDARD 20m SENSOR TEMP TEMPERATURE CONNECTIONS SEE APPENDIX SEE APPENDIX ELECTRIC HEATER SUPPLY 1x16 A 230 VAC 3x2 5s ECE MODELS electric heater 2kW SUPPLY 3x16 A 40...

Page 41: ...e defrosting is active at the most 8 of the time The over pressure function over rides the defrosting function The defrosting function is activated by short circuiting the defrosting pins on the main...

Page 42: ...t Tel 358 0 207 528800 Fax 358 0 207 528844 Kipin tie1 06150 Porvoo 1 A 1 1 21 12 2007 ECE MALLIT MODELLER MODELS MAX 2KW ECC 05 NEF L MMITIN V RMARE HEATER TZA TZ ECC 05 1 2 HEAT AFT N L AFT HEAT C 1...

Page 43: ...VIHRE GULGR N YELLOWGREEN SI SININEN BL BLUE RU RUSKEA BRUN BROWN Valmiste 04 06 2007 Pvm Paino kg Muutos Lehti Suhde 1 2 4 3 KEVI SI RU A2 A1 K1 2T1 1L1 4T2 3L2 2 1 PDA 4 3 6 5 Q LTR SARJA SERIEN SER...

Page 44: ...B Box 366 184 24 KERSBERGA SVERIGE phone 46 8 540 87515 DeliVent Ab Markv gen 6 43091 H N SVERIGE phone 46 70 204 0809 Estonia As Comfort Ae Jaama 1 72712 PAIDE EESTI phone 372 38 49 430 Ireland Entro...

Page 45: ...ance 5 The obligation to perform a warranty repair and the warranty will expire if a The rating plate of the equipment has been modified or removed b The receipt of purchase and or installation cer ti...

Page 46: ......

Page 47: ...ters on the inside Changing plain filters Remove the filter cassettes from the device and loosen the filter fabric from the frame Replace new filter fabric back into the frame Replace the filter casse...

Page 48: ...nges and flashes when it indicates a problem See Service Alarm indication on page 12 QUICK GUIDE TO THE VENTILATION UNIT GENERAL INFORMATION ABOUT VENTILATION The basic function of the ventilation uni...

Reviews: